Posted on

In-Depth Analysis and Solutions for ABB ACS550 Inverter F0002 Fault

Introduction

In the realm of industrial automation, inverters play a pivotal role in achieving precise motor control, directly impacting production efficiency and equipment longevity. The ABB ACS550 series inverter, renowned for its high performance and reliability, is widely utilized across various industries. However, the F0002 fault code, a common anomaly, often poses challenges for maintenance personnel. This article provides a thorough exploration of the F0002 fault’s definition, causes, on-site troubleshooting strategies, and repair methods, offering clear and practical guidance to help users swiftly restore normal operation.

Definition of the F0002 Fault

Within the ABB ACS550 series inverters, the F0002 fault code specifically indicates a DC bus overvoltage issue. When the inverter detects that the DC bus voltage exceeds its designed safety threshold, the control panel displays “F0002” or “OVERVOLTAGE” and triggers an automatic shutdown to protect the internal circuitry. This fault not only disrupts production but may also pose a risk of hardware damage, necessitating prompt diagnosis and resolution.

F0002

Analysis of Fault Causes

The F0002 fault stems from an abnormal rise in DC bus voltage, typically triggered by the following factors:

  1. Input Power Fluctuations
    Transient or persistent voltage surges on the L1, L2, and L3 input power lines can cause the inverter’s rectifier circuit to pass excessive voltage to the DC bus, activating the overvoltage protection.
  2. Excessive Regenerative Energy During Deceleration
    If the deceleration time is set too short (e.g., parameters 2203 or 2206), the regenerative energy generated by the motor during deceleration cannot be dissipated promptly, leading to a rapid increase in DC bus voltage.
  3. Inadequate Braking System Performance
    In applications requiring frequent braking or involving high-inertia loads, insufficient capacity of the braking resistor or chopper may fail to absorb regenerative energy, causing voltage buildup.
  4. External Load Feedback Energy
    In specific scenarios (e.g., downhill conveyors or hoists), the motor may be driven by external forces, entering a generator state and feeding excess energy back to the inverter, resulting in an overvoltage fault.

These causes may occur individually or in combination, requiring a comprehensive approach to fault analysis.

On-Site Troubleshooting Steps

When encountering an F0002 fault, users can follow these steps to address the issue on-site and restore operation:

Step 1: Confirm the Fault and Shut Down

  • Check the inverter display to verify the fault code as “F0002” or a prompt for “OVERVOLTAGE.”
  • Immediately stop the inverter to prevent further escalation, ensuring safety for equipment and personnel.

Step 2: Inspect the Input Power

  • Use a multimeter to measure the voltage across the L1, L2, and L3 input terminals to identify any anomalies.
  • If power instability is detected, consider installing a voltage regulator or contacting the power supply provider for adjustments.

Step 3: Adjust Deceleration Parameters

  • Access the parameter settings menu and review the deceleration time parameters (2203 or 2206).
  • If the time is too short, extend it (e.g., from 5 seconds to 10 seconds) to reduce the accumulation rate of regenerative energy.

Step 4: Check the Braking System

  • Verify that the braking resistor and chopper specifications match the load requirements.
  • Inspect the braking resistor for signs of burning or disconnection, replacing it with a higher-power unit if necessary.

Step 5: Reset and Test

  • After addressing potential issues, press the “RESET” button on the control panel to clear the fault.
  • Restart the inverter and monitor its operating status to ensure the fault does not recur.

Step 6: Continuous Monitoring

  • If the fault persists, record relevant operating data and consult a professional technician for further diagnosis.

These steps enable users to quickly pinpoint and resolve issues in the field.

Disassembly and Repair Process

If on-site troubleshooting fails to resolve the issue, disassembly and repair of the inverter may be required. The following is a detailed repair procedure:

1. Safety Preparation

  • Disconnect the inverter power supply and wait at least 5 minutes to allow internal capacitors to fully discharge.
  • Wear anti-static gloves to prevent damage to sensitive components.

2. Visual Inspection

  • Open the inverter casing and check the DC bus capacitors for swelling, leakage, or burn marks.
  • Inspect the IGBT modules for signs of overheating or breakdown.
  • If a braking resistor is installed, examine its surface for integrity.

3. Voltage Measurement

  • With power applied (exercise caution), use a multimeter to measure the DC bus voltage, referencing the standard values in the ACS550 technical manual.
  • Persistent high voltage may indicate issues with the capacitors or rectifier circuit.

4. Braking Circuit Testing

  • Test the operation of the braking chopper to ensure proper switching functionality.
  • Use an ohmmeter to measure the braking resistor’s resistance, confirming it matches the nominal value.

5. Control Circuit Troubleshooting

  • Check the main control board’s circuit connections for short circuits or breaks.
  • If equipped, use an oscilloscope to analyze the output signals of the voltage monitoring circuit.

6. Replace Damaged Components

  • Based on inspection findings, replace damaged capacitors, IGBT modules, or braking resistors, preferably with ABB original parts.
  • Ensure all connections are secure post-replacement to avoid poor contact.

7. Testing and Validation

  • Reassemble the inverter and conduct no-load and load tests after powering on.
  • Confirm that the fault code no longer appears and that operating parameters are normal.

Repair work should be performed by qualified personnel, adhering to safety standards. If unsure about specific steps, contact ABB technical support for assistance.

acs550

Preventive Measures and Recommendations

To minimize the occurrence of F0002 faults, users can adopt the following preventive measures:

  • Regular Power Quality Checks: Ensure stable input voltage to avoid faults caused by grid fluctuations.
  • Optimize Parameter Settings: Configure deceleration times based on load characteristics to prevent regenerative energy overload.
  • Upgrade the Braking System: For high-inertia load applications, select braking resistors and choppers with adequate capacity.
  • Routine Maintenance: Periodically clean dust from the inverter interior and inspect key components for signs of aging.

Conclusion

The F0002 fault in the ABB ACS550 inverter is a typical overvoltage issue, potentially arising from power anomalies, improper parameter settings, or inadequate braking. By following the on-site troubleshooting steps and repair procedures outlined in this article, users can systematically diagnose and resolve the problem. Additionally, implementing preventive measures can effectively reduce fault recurrence and extend equipment lifespan. This guide aims to provide practical reference material, supporting users in maintaining equipment and enhancing production efficiency.

Posted on

 Comprehensive Guide to Completely Uninstalling and Reinstalling Siemens TIA Portal: From Residual Cleanup to System Stability Restoration

1. Introduction & Scope

Siemens TIA Portal (V13–V19) leaves deep system traces during installation, including MSI product codes, Windows services, and drivers. Incomplete uninstallation causes version conflicts, GUID errors, and hardware issues (e.g., Code 19/45 for keyboards). This guide provides a fully automated, step-by-step solution to resolve these issues, covering:

  • Deep component removal (programs, drivers, services, registry)
  • Hardware error repair (Upper/Lower Filters)
  • Pre/post-installation checks (media validation, license recovery)
  • System health restoration (DISM/SFC/BCDEdit)
  • Rollback scripts and error lookup tables

2. Pre-Uninstallation Preparation

2.1 Backup Critical Data

  • Projects: Archive via TIA Portal’s “Archive” function (.zap13/14 files).
  • Licenses: Export via Siemens Automation License Manager (ALM) to USB.

2.2 Tool List

ToolPurposeSource
TIA AdministratorUninstall same-version packagesTIA installation media
CleanUpToolOfficial deep-clean scriptSiemens FAQ #109482460
Revo UninstallerAdvanced residual scanningrevouninstaller.com
PnPUtil/DevManViewRemove orphaned driversWindows ADK

3. Official Uninstallation Tools

3.1 TIA Administrator

  1. Open Siemens.TiaAdmin.msi from installation media.
  2. Filter “Installed” packages → Select TIA Portal version → Uninstall → Reboot.

3.2 CleanUpTool

  1. Download CleanUp_TIA_Vxx.exe from Siemens FAQ.
  2. Run as admin → Select target version → Reboot after completion.

4. PowerShell Script for Batch Uninstallation

powershell# C:\Cleanup_TIA_All.ps1$patterns = '*Totally Integrated Automation Portal*', '*SIMATIC*', '*TIA Admin*', '*PLCSIM*', '*WinCC*'$regPaths = 'HKLM:\SOFTWARE\Microsoft\Windows\CurrentVersion\Uninstall', 'HKLM:\SOFTWARE\WOW6432Node\...\Uninstall' $apps = foreach ($path in $regPaths) {  Get-ChildItem $path | ForEach-Object {    $displayName = (Get-ItemProperty $_.PSPath).DisplayName    if ($displayName -like $patterns) { $_ }  }} $apps | ForEach-Object {  Start-Process msiexec.exe -ArgumentList "/x $($_.PSChildName) /qn /norestart" -Wait}

Execution:

powershellSet-ExecutionPolicy Bypass -Scope Process -Force& C:\Cleanup_TIA_All.ps1

Reboot required after script completion.

5. Graphical Tools (Revo/Uninstall Tool)

  • Revo Uninstaller:
    1. “Forced Uninstall” → Search “Totally Integrated Automation” → Delete all residues.
  • Uninstall Tool:
    1. “Batch Mode” → Select Siemens software → “Deep Clean”.

6. Cleanup Legacy Drivers/Services/Registry

6.1 Remove Siemens Services

batchsc query type= service | findstr /I "Siemens SIMATIC TIA" > svc.txtfor /f %%s in (svc.txt) do (  sc stop %%s  sc delete %%s)

6.2 Fix Code 19/45 Keyboard Errors

  1. Open regedit → Navigate to:HKLM\SYSTEM\CurrentControlSet\Control\Class\{4D36E96B-E325-11CE-BFC1-08002BE10318}
  2. Delete UpperFilters/LowerFilters → Create a new multi-string value UpperFilters with kbdclass.

6.3 Remove Zombie Drivers

batchpnputil /enum-devices /problem > zombie.txtfor /f "skip=2 tokens=1,*" %%i in ('find "Problem" ^< zombie.txt') do (  pnputil /remove-device %%i /subtree /reboot)

7. System Health Check

batchdism /online /cleanup-image /restorehealth  # Repair component storesfc /scannow                                # Validate system filesbcdedit /enum {current}                     # Check for safeboot flags

To revert safeboot:

batchbcdedit /deletevalue {default} safebootbcdedit /deletevalue {default} safebootalternateshell

8. Reinstallation Guide

8.1 Media Validation

  • Verify ISO integrity via SHA-256 checksum or use Siemens MediaCreator.

8.2 Silent Installation

batchStart.exe /isolog:"C:\TIAinstall.log" /silent

Check C:\ProgramData\Siemens\Automation\Logs\Setup.log for errors.

8.3 Reboot Nodes

StepReboot Required?Notes
After CleanUpToolFree locked DLLs
Post-PowerShell scriptWindows Installer requirement
After STEP 7/WinCC/PLCSIMRegister drivers

9. Troubleshooting Guide

IssueRoot CauseFix
“Detected older version”Residual GUIDsRun PowerShell script
Keyboard Code 19/45Corrupted filtersRebuild UpperFilters
OPC UA Service failureLingering trace servicesDelete services + reinstall
CleanUpTool “reboot required”Pending uninstallsRestart

10. Automation & Best Practices

  • Package scripts (PowerShell, service cleanup, .reg fixes) into a Git repo.
  • Deploy via MDT/Intune for enterprise automation.
  • Reduce reinstall time from 4 hours to 30 minutes.

Final Note: This guide synthesizes official documentation, field testing, and community fixes to eliminate TIA Portal reinstallation headaches. Always test scripts in a non-production environment first!

Posted on

User Guide for Mitsubishi FR-A500 (A540 and A520) Series Inverter


The Mitsubishi FR-A500 series inverter, including models A540 and A520, is a widely used device in the field of industrial control. Its user manual serves as an essential guide for operating and maintaining the inverter. This article provides a detailed introduction to the operation panel functions, parameter settings, password management, external control, and fault handling of this series of inverters based on the user manual.

FR-A540

I. Introduction to Operation Panel Functions

The operation panel (FR-DU04) of the Mitsubishi FR-A500 series inverter is the primary interface for users to interact with the inverter, offering a range of display and operation capabilities:

  • Display Functions: The operation panel can display real-time key parameters of the inverter, such as operating frequency, output current, output voltage, and alarm information, facilitating user monitoring of the inverter’s status.
  • Key Functions:
    • MODE Key: Used to switch between different operation modes, such as monitor mode, frequency setting mode, and parameter setting mode.
    • SET Key: Used to confirm set values or enter the parameter setting interface.
    •  and  Keys: Used to increase or decrease set values, adjusting parameters or frequencies.
    • FWD and REV Keys: Used to issue forward and reverse commands, respectively, controlling the motor’s rotation direction.
    • STOP RESET Key: Used to stop the inverter or reset faults.

II. Parameter Initialization Settings

During the use of the inverter, it may be necessary to restore parameters to their factory settings. Users can perform parameter initialization through the following steps:

  • Clear All Parameters: Set parameter Pr.77 to 1, then press and hold the SET key for more than 1.5 seconds to restore all parameters (except Pr.77Pr.79Pr.80, and Pr.81) to their factory settings.
  • Clear User Parameter Groups: To clear user-defined parameter groups, use parameters Pr.174 and Pr.176 to clear the first and second user parameter groups, respectively.

III. Password Setting, Removal, and Parameter Access Restrictions

To protect the inverter’s parameters from being modified arbitrarily, users can set parameter access restrictions through the following methods:

  • Parameter Write Protection Selection (Pr.77):
    • When set to 1, parameters can only be written when the inverter is stopped.
    • When set to 2, writing to all parameters is prohibited (factory setting).
    • When set to 0, parameter writing is allowed during operation (note: safety considerations apply).
  • Password Function: Although the FR-A500 series inverter does not directly provide a password setting function, parameter write protection through Pr.77 can indirectly achieve a certain level of access control.

IV. External Control Functions

The Mitsubishi FR-A500 series inverter supports external terminal control, allowing users to configure it flexibly according to actual needs.

  • External Terminal Forward/Reverse Control:
    • Use terminals STF (forward start) and STR (reverse start) for forward/reverse control. When the STF signal is activated, the inverter operates in the forward direction; when the STR signal is activated, it operates in reverse.
    • Parameter Settings: Ensure that Pr.79 (operation mode selection) is set to external operation mode or combined operation mode to enable external terminal control.
  • External Potentiometer for Frequency Setting and Speed Control:
    • Frequency Setting Terminals: Use terminals 245, and 10 (or AU terminal, depending on parameter settings) for analog frequency setting. Typically, a potentiometer is connected between terminals 10 (or AU) and 5, and the input voltage is adjusted by rotating the potentiometer to set the operating frequency.
    • Parameter Settings: Set Pr.73 to select the voltage input range (e.g., 0-5V0-10V, etc.); ensure that parameters such as Pr.125 (analog input filter time constant) are set appropriately to ensure the stability of frequency setting.
FR-A540

V. Fault Codes and Handling Methods

The inverter may encounter various faults during operation, and the user manual provides detailed fault codes and handling methods. Below are some common fault codes and brief handling steps:

  • E.OC1 (Overcurrent Trip During Acceleration): Check if the load is too heavy, if the acceleration time is too short, and if the motor and cable insulation are in good condition.
  • E.OV1 (Regenerative Overvoltage Trip During Acceleration): Check if the power supply voltage is too high, if the deceleration time is too short, and if the braking resistor is damaged.
  • E.THM (Motor Overload Trip): Check if the motor load is too heavy, if the motor cooling is adequate, and if necessary, reduce the load or improve the cooling conditions.
  • E.UVT (Undervoltage Protection): Check if the power supply voltage is too low and if the power lines are properly connected.
  • E.FIN (Heat Sink Overheat): Check if the inverter’s heat sink is excessively dusty, if ventilation is adequate, and if necessary, clean the heat sink or improve ventilation conditions.

When the inverter stops due to a fault, the operation panel displays the corresponding fault code. Users should refer to the user manual based on the fault code and take appropriate handling measures. After handling, press the STOP RESET key to reset the inverter and restart operation.

VI. Conclusion

The Mitsubishi FR-A500 (A540 and A520) series user manual is an essential guide for operating and maintaining the inverter. Through this article, users should be able to master the operation skills of the operation panel functions, parameter initialization settings, password management, external control, and fault handling. In practical applications, users should configure the inverter parameters reasonably according to specific needs to ensure stable and efficient operation of the inverter. Additionally, regularly consulting the user manual to stay informed about the latest features and technical advancements of the inverter is also an important way to enhance equipment management capabilities.

Posted on

Comprehensive Analysis of “inh” Inhibition State: A Practical Guide to Safe Torque Off (STO) and Rapid Recovery for Nidec Control Techniques Unidrive M300

1. Introduction

When debugging or repairing the Unidrive M300 variable frequency/servo drive on-site, the sudden illumination of the “inh” (Inhibit) indicator on the panel often catches engineers off guard. This article systematically outlines the fundamental meaning, safety logic, ten common triggering causes, a six-step troubleshooting process, and preventive maintenance strategies for “inh” based on official manuals, Control Techniques FAQs, and years of maintenance experience. It aims to assist peers in quickly locating and eliminating faults, ensuring efficient and safe operation of production lines. The full text is approximately 4,800 words, catering to in-depth reading needs.

2. What is the “inh” State?

As clearly stated in the official “Quick Start Guide” under the “Status indications” table: inh = drive inhibited, output stage disabled; Safe Torque Off (STO) signal not ready or Drive Enable at low level. In this state, the inverter bridge is completely disconnected, and the motor outputs no torque.

Unlike a regular Trip (fault), inh is not logged in the Trip log and cannot be cleared using the reset button. Only by re-establishing the drive enable logic will the LED transition from inh → rdy → StoP/frequency in sequence.

INH

3. Working Principle of STO Function

Safe Torque Off is a safety function defined by EN 61800-5-2. When in the “disable” logic low level (< 5 V), it cuts off all IGBT drive signals, achieving IEC 60204-1 Stop Category 0 “uncontrolled stop.” Its “fail-safe” design ensures that even if a single fault occurs in the inverter stage, MCU, or I/O, the drive cannot be re-energized without authorization.

On the M300, terminals 31-STO1 and 34-STO2 serve as dual-channel redundant inputs; terminals 32 and 33 are their respective independent 0 V references. If either channel loses power, the drive immediately enters the inh state.

4. Ten Common Triggering Causes

No.On-site PhenomenonPossible CauseRemarks
1Inh immediately upon startup after maintenanceSafety door, emergency stop not reset; no +24 V at 31/34First check the safety loop
2Random transition to inh during operation24 V switching power supply fluctuation < 20 VMeasure T14→32/33
3Inh displayed after performing rotating/stationary autotune with a new motorDrive automatically inhibits after autotune completionBy design
4Inh displayed after restoring default parameters (Def.xx)Default requires disabling before re-energizing
5PLC outputs Drive Enable but LED remains inhPLC-COM not sharing 0 V with drive
6Unable to reset after adding a safety relayNormally closed relay contacts reversed/leakage voltage present
7Loose wiringScrews at 31, 34 loose, causing intermittent power lossRecommended torque: 0.2 N·m
824 V supply connected in series with other devicesLine voltage drop > 5 V triggers disable
9STO module not securely plugged inReseat ribbon cable or replace moduleRare occurrence
10Firmware detects hardware anomalyRequires factory repair“Sto” Trip will also appear

5. Six-Step Rapid Troubleshooting Process

Measure 24 V:

  • Measure the voltage between terminal 14 (+24 V) and 32/33 (0 V); it should be 23–25 V. If insufficient, repair the power supply first.

Confirm STO Channels:

  • Short-circuit test: Within safety limits, use a jumper to connect 31 and 34 to 14. If the LED changes to rdy, the issue lies in the external safety chain.

Verify Drive Enable Logic:

  • Recommend keeping Pr 11 = 5, with terminals 12/13 for forward/reverse operation, respectively.

Reset Autotune Inhibition:

  • After autotune, first disconnect, then reapply 24 V to 31/34, and finally issue the Run command.

Check Wiring Quality:

  • Tighten control terminals to 0.2 N·m; check for mixed hard/stranded wires causing screw rebound.

Diagnose External Safety Devices:

  • If using safety relays like Pilz or Schneider, check if both channels close synchronously; confirm their status via LEDs or diagnostic contacts.

If the LED remains inh after step 2, it likely indicates a fault with the STO board or mainboard, requiring factory repair.

M300

6. On-site Case Studies

6.1 Injection Molding Machine Retrofit Project
A 75 kW injection molding machine was retrofitted from a Siemens drive to M300. Upon completion, startup often displayed inh. Troubleshooting revealed that PLC-DO and drive 0 V were not sharing a common ground, causing the STO input to detect a 10 V floating ground potential, interpreted as a logic low. Resolving the floating ground issue restored normal operation.

6.2 Textile Winding Line Production
To facilitate maintenance, engineers modified the emergency stop circuit to a single-channel output, connecting only 31 and not 34, resulting in occasional inh states. Based on the STO “disable on low level in either channel” characteristic, connecting 34 to the safety relay’s NO contact stabilized operation.

6.3 Robot Joint Autotune
During a 2 kW servo motor’s rotating autotune, the panel remained inh afterward. The technician mistakenly assumed a fault, but it was actually by design: autotune completion requires re-enabling. Following the reset procedure resolved the issue.

7. Why Can’t You Simply “Clear the Fault”?

As stated in Control Techniques’ official FAQ: INH is not a Trip, so pressing RESET is ineffective; the only solution is to apply 24 V to the STO input. Arbitrarily short-circuiting the safety chain may violate machine CE/UL safety assessments and even incur legal risks.

Therefore, under the framework of industrial safety standards ISO 13849-1 / IEC 62061, it is imperative to identify the root cause of STO disablement, conduct a risk assessment, and confirm the shutdown or restoration of safety devices, rather than merely “silencing” the indication.

8. Preventive Maintenance and Improvement Recommendations

  • Independent 24 V Redundant Power Supply: For critical production lines, configure dual isolated power supplies with OR-ing Diode to prevent voltage drops.
  • Regular Terminal Tightening: Recommend tightening every six months, especially in high-vibration environments.
  • Safety Chain Monitoring: Select safety relays with diagnostic contacts like PNOZmulti or EasyE-Stop to record each opening/closing state.
  • Add Voltage Monitoring Signal: Use PLC to monitor T14 voltage and set an alarm for < 20 V to detect power supply failures in advance.
  • Parameter Backup: Use AI-Backup SD cards or Machine Control Studio to secure critical parameters, preventing enable logic loss after mistakenly restoring defaults.
  • Training and SOP: Develop a “Standard Operating Procedure for STO-Inhibit Resolution” to clarify the sequence of “disconnect, investigate, then re-energize” for on-site personnel.

9. Conclusion

“inh” is not a true fault but rather an active protection mechanism of the Unidrive M300’s safety architecture. A deep understanding of STO dual-channel logic, electrical wiring specifications, and parameter associations can both shorten downtime and enhance overall line safety. We hope this article provides you with a systematic approach and practical tools. If you encounter complex situations on-site, it is recommended to contact the Nidec CT authorized service center for further support. Do not arbitrarily short-circuit the safety loop. Wishing you smooth debugging and safe, efficient production!

Posted on

From ERR23 to ERR42 in ZHZK Inverter — Diagnosing and Repairing Hidden Fault Codes Not Found in Manuals


In field maintenance work, we often encounter situations where equipment displays fault codes that are not documented in the user manual. This is especially common with domestic brands or cloned inverters. This article details the entire process of diagnosing and repairing a ZHZK ZK880-N series inverter that first displayed an ERR23 fault (ground short circuit), and after repairs, encountered an ERR42 fault (speed deviation too large). Through fault code analysis and comparative research, we uncover the significant similarities between this inverter and the Inovance MD380 series and explore the logic issues that arise.

1. Equipment Background

The inverter was applied in an industrial fan system at a factory, used for speed control and energy saving. After years of operation, the equipment suddenly failed and displayed ERR23. The user tried replacing the motor without success, and then entrusted our team with on-site diagnosis and repair.

err23

2. First Fault: ERR23 — Ground Short Circuit

1. Fault Symptom

The inverter powered on and passed self-check, but tripped with an ERR23 alarm immediately upon startup. The motor did not rotate, and no output current was detected.

2. Fault Analysis

Based on experience, ERR23 typically indicates a ground short caused by:

  • Motor winding insulation breakdown
  • Damaged or damp output cables
  • Internal failure of power components (IGBT)

3. Troubleshooting and Repair

  1. Insulation Testing: Used a megohmmeter to check insulation between U/V/W and ground — >200MΩ, confirmed normal; cables also intact.
  2. Output Voltage Check: Powered on without load and checked inverter output with an oscilloscope — no PWM waveform, indicating power circuit issues.
  3. Drive Board Check: Found burn marks on the drive board; further inspection confirmed IGBT failure.
  4. Component Replacement: Replaced IGBT module and repaired burned-out optocouplers and resistors in the drive circuit.
  5. Testing: Simulated load in factory conditions — inverter output normal, PWM stable, fan rotates properly.

ERR23 fault was successfully resolved.

3. Post-Repair Fault: ERR42 — Speed Deviation Too Large

1. On-Site Issue

After reinstalling at the user site, the inverter powered on and passed self-check. Upon startup, it ran for about 1–2 seconds and then tripped with ERR42.

2. Confusion and Clue

The ZHZK manual did not mention ERR42, leaving no immediate path forward. We pursued two directions:

  • First, determine if it was a false alarm — due to interference or wiring.
  • Second, check for hidden parameters or compatibility issues — given the extremely brief manual.

3. Comparative Breakthrough — Inovance MD380

An engineer noticed that the ZHZK ZK880-N closely resembled the Inovance MD380 series in appearance, menus, and parameter structures. We referenced the MD380 manual and found:

ERR42: Speed deviation too large.
Applies when using encoder feedback in vector control (F0-01=1), and actual speed deviates significantly from target.

But the parameter F0-01 was set to 0, i.e., sensorless vector control (SVC), where no encoder feedback is involved. Logically, such an error shouldn’t occur in this mode.

4. Validation Through Trial and Error

We tested by changing F0-01 from 0 to 2 — i.e., switching to V/F control mode.

  • Upon restart, the inverter operated normally.
  • ERR42 no longer occurred.

This confirmed that:

  • Although ERR42 should only trigger in closed-loop vector control, ZHZK’s firmware retained some residual logic from MD380, allowing the error even in SVC mode.
err46

5. ZHZK ZK880-N vs. Inovance MD380 — An In-Depth Comparison

Several clues support that ZHZK is a cloned or customized variant of Inovance:

  1. Parameter numbering identical: Including F0-01, F9 group, etc.
  2. Fault codes mostly match: Even undocumented ZHZK codes behave like MD380 ones.
  3. Hardware layout extremely similar: IGBT drive and control board layout nearly identical.
  4. UI and navigation same: Menu structure, key functions, and parameter copy behavior identical.

Conclusion: ZHZK ZK880-N is highly likely based on early Inovance versions — a rebranded or cut-down variant, with leftover logic causing such confusion.

6. Key Repair Takeaways

  1. Don’t rely solely on manuals when fault codes are missing: Look at similar products.
  2. SVC mode in clone inverters is often unstable: Recommend V/F for reliability.
  3. Always document parameters and take screenshots: Helps future diagnostics.
  4. Validate by logic and testing: ERR42 was resolved by matching control logic with firmware behavior.

7. Conclusion

This case shows that engineers must go beyond the manual when diagnosing inverter faults — especially for custom or generic brands. The transition from ERR23 to ERR42 and its resolution illustrates the importance of comparative research, logical reasoning, and on-site validation.

For clone or OEM-modified inverters, avoid complex control modes like vector control unless absolutely necessary. Simplicity brings reliability in harsh field environments.

This process exemplifies how practical engineering insight bridges the gap between unknown errors and restored operation.

Posted on

SQ1000 Inverter User Manual Guide

I. Operation Panel Functions and Parameter Management

1. Operation Panel Function Introduction

  • Applicable Model: SQ-K01 Operation Panel (Refer to pages 8, 18-23 of the manual)
  • Core Functional Modules:
    • Key Functions:
      • Run/Stop: Controls the start/stop of the inverter. Press and hold the “Stop/Reset” key for free stop.
      • Function Key: Toggles between monitoring states and menu levels (Primary Menu → Secondary Menu → Parameter Editing).
      • Save/Confirm Key: Saves parameter modifications and jumps to the next parameter.
      • Shift Key (<<): Switches between monitoring parameters or moves the data editing position.
      • Increment (▲)/Decrement (▼) Keys: Adjusts parameter values or function code numbers.
    • Indicator Lights:
      • FWD/REV: Indicates forward/reverse operation status.
      • H/V/A/r/min: Correspond to display units for frequency, voltage, current, and speed, respectively.
      • Digital Display: 5-digit LED displays parameter values, fault codes, or operational data (e.g., output frequency 50.00Hz).
SQ1000 INVERTER

2. Parameter Initialization

  • Steps (Refer to parameter F2.00 on page 29 of the manual):
    1. Enter the primary menu and select -F2- (Auxiliary Settings Group).
    2. Enter the secondary menu and select F2.00 (Parameter Initialization).
    3. Set to 1 to restore factory settings, or 2 to clear fault records.
    4. Press the “Save” key to confirm, and the inverter will restart automatically to take effect.

3. Password Setting and Removal

  • Setting Password (Parameter F2.03 on page 29 of the manual):
    1. Enter F2.03 (Parameter Permission Modification Password) and input a value between 0-65535.
    2. After saving, entering this password will be required to modify other parameters.
  • Removing Password: Reset F2.03 to 0 to cancel password protection.

4. Parameter Access Restrictions

  • Setting Method: Set permissions via F2.01 (Parameter Write Protection) (Refer to page 29 of the manual)
  • Permission Options:
    • 0: Allows modification of all parameters (some parameters cannot be modified during operation).
    • 1: Only allows modification of the digital set frequency (F0.02).
    • 2: Prohibits modification of all parameters (only F2.01 and F2.03 can be adjusted).

II. External Terminal Control and Potentiometer Speed Regulation Settings

1. External Terminal Forward/Reverse Control

  • Wiring and Parameter Settings (Refer to pages 12-15, 46-48 of the manual):
    • Wiring Terminals:
      • Power Input: L/N (Single-phase 220V) or R/S/T (Three-phase 380V).
      • Control Terminals: X1-X6 are multi-function inputs, COM is the common terminal.
      • Example Wiring: X1 connected to the forward rotation button, X2 connected to the reverse rotation button, both short-circuited with COM to take effect.
    • Parameter Settings:
      1. F0.00: Set to 1 (External Terminal Control Mode).
      2. F4.00-F4.05: Define terminal functions (e.g., X1=5 “Forward Rotation”, X2=6 “Reverse Rotation”).
      3. F4.06: Select control mode (recommended 2 Two-Wire Control Mode 1, FWD/REV independently controlled).

2. External Potentiometer Frequency Speed Regulation

  • Wiring and Parameter Settings (Refer to pages 14-15, 36-37, 51 of the manual):
    • Wiring Terminals:
      • Analog Input: AII (0-10V) connected to the middle pin of the potentiometer, COM connected to the negative terminal, 10V terminal connected to the power positive terminal.
      • Jumper Setting: The J1 jumper on the control board needs to be short-circuited to the “V” side (voltage input mode).
    • Parameter Settings:
      1. F0.01: Set to 3 (External Analog Signal AII for Frequency Setting).
      2. F5.00-F5.03: Calibrate the input range (default 0-10V corresponds to 0-100% frequency).
      3. F5.04: Adjust the filtering time (default 0.2 seconds, for anti-interference purposes).

III. Fault Code Analysis and Handling Methods

Common Fault Codes and Solutions (Refer to pages 65-66 of the manual)

Fault CodeMeaningSolution
E001Acceleration OvercurrentCheck motor load, extend acceleration time (F0.06).
E004Acceleration OvervoltageIncrease deceleration time (F0.07), check braking resistor.
E009Radiator OverheatingClean the air duct, ensure ambient temperature ≤40℃.
E010Inverter OverloadReduce load or increase inverter capacity.
E011Motor OverloadAdjust F8.01 (Motor Overload Protection Coefficient).
E015Undervoltage During OperationCheck input power voltage, adjust F8.06 threshold.
E016EEPROM Read/Write FaultRestore factory parameters, contact the manufacturer to replace the storage chip.

General Fault Troubleshooting Steps:

  1. Power-Off Inspection: Disconnect the power supply for 5 minutes, check for loose or short-circuited wiring.
  2. Reset Operation: Press the “Stop/Reset” key to clear the fault and power on again.
  3. Parameter Verification: Confirm that key parameters (such as F0.03 maximum frequency, F3 group motor parameters) match the equipment.
  4. Contact Support: If the fault persists, record the code and contact the manufacturer (Phone: 17328677949).
SQ1000 INVERTER

IV. Conclusion

The SQ1000 inverter meets complex industrial demands through flexible parameter configuration and diverse control methods. Users must strictly adhere to the safety specifications in the manual (such as grounding and heat dissipation requirements) and perform regular maintenance to extend the equipment’s lifespan. Mastering the operation panel functions, external control settings, and fault handling techniques can significantly improve equipment operational efficiency and stability. It is recommended to keep the manual and refer to it regularly to ensure compliance and safety in operations.

Posted on

Schneider ATV71 VFD INF6 Fault Analysis and Repair Guide – Focused on Crane Applications


Meaning of the INF6 Fault Code

The INF6 fault in Schneider Electric’s ATV71 variable frequency drive (VFD) indicates an internal option card fault, specifically that the drive fails to detect or recognize an installed option card. This card could be a communication module, encoder feedback interface, or an I/O extension board, all of which are connected via internal slots to the main control board.

In crane applications, option cards are frequently used for advanced functions such as closed-loop vector control via encoder feedback or communication with PLCs or remote systems through fieldbus networks like Profibus, CANopen, or Modbus.


INF6

Typical Scenarios Leading to INF6 in Crane Environments

  1. Card Loose or Poor Contact Due to Vibration
    Cranes often cause mechanical vibration and shock, especially during lifting or brake engagement. These vibrations can loosen option cards that are not well-secured, leading to intermittent or complete disconnection from the control board.
  2. Incompatibility or Conflict Between Cards
    Installing incompatible option cards or using two mutually exclusive modules can lead to detection failures. For instance, some ATV71 models do not support simultaneous installation of multiple communication cards.
  3. EMI (Electromagnetic Interference)
    High-voltage motors, contactors, and solenoids in cranes generate strong electrical noise. If signal lines or the power supply to the card are interfered with, the card may fail during boot-up, leading to INF6.
  4. Hot-Swapping or Improper Handling
    Inserting or removing cards while the drive is powered can instantly damage internal circuits or corrupt detection logic.
  5. Card Failure or Aging
    Cards may fail due to temperature stress, component aging, or EEPROM corruption, particularly in harsh crane environments.

On-site Troubleshooting Process and Required Instruments

1. Safety Shutdown and Visual Inspection

  • Disconnect all power and wait for DC bus discharge.
  • Remove the front cover of the VFD and inspect the option card seating.
  • Re-insert and firmly fix the card to ensure solid contact.

2. Socket and PCB Inspection

  • Examine socket pins for oxidation, damage, or bent pins.
  • Use a flashlight and multimeter (in continuity mode) to check connection integrity between slot pins and main board.
  • Clean contacts with alcohol if dirt or corrosion is found.

3. Substitution Testing

  • Insert a known-good card to see if the error clears.
  • Try the faulty card in a different VFD. If the error moves with the card, the card is faulty. If not, suspect the VFD mainboard.

4. Firmware and Parameter Checking

  • Connect a PC via Schneider’s SoMove software and read diagnostic registers.
  • Check if the card appears in the identification menu. If not, it’s either faulty or incompatible.
  • Confirm compatibility of the card model with current firmware version.

5. Instrumental Diagnosis

  • Multimeter: Measure slot power pins (usually +5V or +24V).
  • Oscilloscope: Check clock/data lines of the card communication interface (e.g., SPI, I²C).
  • Thermal Camera: Detect abnormal heat signatures on card or mainboard.
  • Bus Analyzer: For communication cards, monitor if signals are transmitted at all.

ATV71 main control board and option card connection diagram

Maintenance and Repair Strategy

Basic Solutions

  • Reseat the card and retest.
  • Replace card if visibly damaged or if substitution confirms card failure.
  • Remove additional cards if there is a slot conflict.

Power Supply Repair

  • If slot voltage is missing or unstable, investigate the power regulator or filtering section of the mainboard.

Cold Solder Joint Repair

  • Check socket solder points under magnification. Repair any cracked or cold solder joints using a soldering iron.

Firmware Updates

  • If firmware mismatch is suspected, update the drive firmware using official Schneider tools.

Observe Handling Rules

  • Always power down before inserting/removing cards.
  • Avoid touching card contacts with bare hands.

Advanced PCB-Level Diagnostics (for Experienced Engineers)

If all above steps fail:

  1. Study Schematics
    Locate option slot pin functions and their connections to ICs or CPU.
  2. Signal Tracing
    Use an oscilloscope or logic analyzer to trace data lines between the card and CPU. Look for absence or corruption of signals.
  3. Component Testing
    • Check if line driver/receiver ICs (e.g., RS-485 transceivers) are working.
    • Verify presence of proper clock signals and EEPROM integrity.
  4. Chip Replacement
    • If suspect components (e.g., voltage regulators, buffer ICs) are identified, carefully desolder and replace them.
    • Use thermal camera post-repair to confirm heat profile normalization.

Summary

For a field engineer maintaining crane control systems, an INF6 error is not just a code—it’s a call for systematic diagnosis. Whether caused by vibration, poor contact, firmware mismatch, or a damaged card, INF6 can typically be resolved with structured inspection and substitution.

When the root cause lies deeper—within power supplies, communication buses, or chip-level failures—a disciplined approach using schematics, meters, and scopes becomes essential. Through careful inspection, methodical replacement, and sometimes PCB-level repair, an engineer can confidently restore the VFD’s full functionality.

Let this guide serve as your reference for future INF6 cases on Schneider ATV71 drives, ensuring minimal downtime and safe crane operation.


Posted on

In-depth Analysis and Practical Maintenance Guide for F30022 and A7852 Faults in Siemens SINAMICS G120L Inverter


Abstract
This article systematically examines a field case involving the co-occurrence of F30022 (Power Unit U_ce Monitoring Fault) and A7852 (External Alarm 3) in a G120L inverter used in a 315 kW water pump application. It delves into the fault mechanisms, provides a detailed eight-step troubleshooting process, outlines testing methods and replacement techniques for commonly damaged components, and summarizes five preventive maintenance points based on maintenance statistics.

sinamics g120l 
6sl3310-1ce36-6aa0

I. Fault Phenomena and Code Interpretation

Fault Code F30022: Power Module U_ce Monitoring Triggered

Definition: The power unit continuously monitors the collector-emitter voltage (U_ce) during IGBT conduction. If an abnormal voltage waveform is detected, a hard fault is triggered, and the pulses are locked out.

Common Causes:

  • Output phase-to-phase or phase-to-ground short circuits or motor winding breakdown.
  • IGBT module internal breakdown (due to overheating, aging, or surge impacts).
  • Loss of 24 V power supply to the gate drive or blown fuses on the circuit board.
  • Interruption of the fiber-optic link between the Control Unit (CU) and Power Module (PM), leading to sampling loss.
  • Improper system grounding, causing harmonic currents to return through the PE line and elevate the sampling ground potential.
FAULTS 0.F30022

Alarm Code A7852: External Alarm 3

Definition: A digital input is mapped via parameter p2117. When its status meets the trigger condition, the alarm is set. This does not shut down the power but only indicates an external interlock anomaly.

Typical Trigger Sources:

  • Closure of fire/emergency stop circuits.
  • Faults in cooling water pressure, oil station pressure, or PLC outputs.
  • Loose terminals or poor shielding grounding leading to interference pulses.

When F30022 and A7852 occur simultaneously, it often indicates hardware defects in the power stage and an alarm state in the field interlock, requiring separate handling.

II. Eight-Step Systematic Troubleshooting Process

StepOperation PointsPurpose and Acceptance Criteria
1Power-off insulation test: Measure U/V/W→PE with a 500 V megohmmeter (≥ 5 MΩ)Determine if motor/cable insulation is degraded
2Phase-to-phase short circuit test: Remove motor terminals and measure U-V/V-W/U-W resistance (should equal rated value)0 Ω indicates winding short circuit
3IGBT diode measurement: Use a multimeter’s diode mode to measure forward and reverseBidirectional 0 Ω indicates module breakdown
4Drive board 24 V verification: Check 24 V and 15 V supplies on the gate drive boardLack of power supply may falsely trigger F30022
5Fiber-optic link self-test: Check Rx/Tx indicators on CU and PM ends (should be constantly lit)Dim or flickering lights indicate link interruption
6Resolve A7852: View p2117 corresponding DI, short-circuit/disconnect to verifyConfirm the true source of the external alarm
7No-load test run: Remove U/V/W and power upIf F30022 does not reoccur, the problem is on the motor side
8Load retest: After replacing/repairing components, reconnect the motor for test runr0947 shows no faults, and operation is stable

III. Practical Maintenance Case

Device Overview: G120L-315 kW + CU240E-2PN control unit driving a circulating water pump. First occurrence of F30022 + A7852 after 5 years of operation.

Initial On-site Screening: Megohmmeter reading of only 0.2 MΩ indicates insulation breakdown. Line-to-line resistance measurement of U-V at 0.3 Ω (should be 0.75 Ω) confirms motor short circuit.

Power Module Inspection: U-arm IGBT measures bidirectional 0 Ω, indicating hard breakdown. The same-side drive board’s 24 V fuse is blown.

Component Replacement: Replace 2×1700 C-rated IGBTs, rewire, replace the fuse, and clean the cooling channel.

Fiber-optic Reset: Re-plug the CU-PM POF; indicators return to a constantly lit state.

External Alarm Handling: p2117=1101, corresponding to DI4. Found that the fire interlock test line was not reset → restored, and A7852 disappeared.

Test Run and Delivery: First, a no-load test run, followed by a 50 Hz full-load test run for 1 hour. No alarms occurred; delivered to production.

FAULTS 0.A7852

IV. Component Prices and Typical Labor Hours Reference

ItemPrice (CNY)Labor Hours (h)Notes
1700 C IGBT module ×211,800 ×2Original parts
POF fiber-optic docking kit2602 m
24 V fuse + terminals120
Maintenance labor16 ×350 = 5,600Includes disassembly, testing, debugging
Insulating materials/thermal maintenance500Cleaning + painting
Total≈30,00016Completed within two working days

V. Five Key Points for Preventive Maintenance

  1. Online Insulation Monitoring: Install an IDAX-M to issue an early warning when insulation drops below 2 MΩ.
  2. Quarterly Thermal Cleaning: Use compressed air to blow out air ducts and check r0035 temperature rise. Immediately address any rise >10 K.
  3. Standardized Power-Up Sequence: Turn on the main circuit first, followed by the 24 V control power supply to avoid false alarms due to premature power-up of the drive board.
  4. Layered External Alarms: Digest external alarm signals within the PLC and connect only the total OK contact to the drive to reduce false stops.
  5. Surge and Harmonic Suppression: Install a 690 VAC SPD + 3% reactor at the incoming line to reduce dv/dt impacts on the IGBTs.

VI. Conclusion

F30022 represents a “red alert” at the power stage level, while A7852 serves as a “yellow light” at the system level. When both codes occur simultaneously, it is essential to investigate both hardware and external interlocks. Through structured eight-step troubleshooting, rigorous component testing, replacement, and debugging, production can be restored for a 315 kW water pump within 48 hours. By implementing preventive measures such as insulation monitoring, thermal cleaning, grounding optimization, and surge/harmonic suppression, the risk of similar shutdowns can be significantly reduced. It is hoped that the cases and methodologies presented in this article will provide practical assistance to on-site maintenance engineers and serve as a reference for equipment managers in formulating preventive maintenance plans.



Posted on

LS Mecapion APD‑VP20 Servo Drive Absolute‑Zero Restoration — A Complete Maintenance Guide (S&T TNL‑120V Vertical Lathe Turret Case)

Applies to: Fanuc Series 0i‑TC CNC + S&T TNL‑120V vertical turning lathe. The turret axis uses an LS Mecapion APM‑SG20MKX1‑SNT servo motor driven by an APD‑VP20(SNT) servo amplifier. The motor is equipped with a TS5643N1 multi‑turn absolute encoder (2048 P/R).

Symptom: The internal lithium battery of the LS drive failed → drive raised AL‑14/AL‑15 absolute‑data/battery errors → the customer, suspecting a bad encoder, loosened the flexible coupling between encoder and motor → the encoder zero position no longer matches the motor’s electrical 0° → even after replacing the battery, absolute position is offset and the Fanuc CNC continues to alarm, rendering the machine inoperable.


APD-VP20(SNT)AT

Contents

  1. System architecture & fault background
  2. Relationship between absolute encoders and electrical 0°
  3. Root‑cause chain analysis
  4. Tools & safety preparation
  5. Step‑by‑step restoration workflow
       5.1 Replacing the drive battery
       5.2 Mechanical realignment of the coupling
       5.3 Drive parameter & menu operations
       5.4 Rebuilding the reference point inside Fanuc
  6. In‑depth explanations of key menus
       6.1 PC‑806 Z POS Search
       6.2 PC‑811 ABS Encoder Set
       6.3 HSIN/HSOUT handshake for absolute data
  7. Commissioning and verification
  8. Preventive measures & maintenance tips
  9. FAQ
  10. Closing remarks

AL_01

1 System Architecture & Fault Background

1.1 Machine configuration

  • Machine: S&T TNL‑120V vertical turning center with 8‑station turret.
  • Control: Fanuc Series 0i‑TC. Spindle and linear axes use standard FANUC α drives. The turret axis, however, is an LS Mecapion solution supplied by the OEM (S&T) for cost optimisation.
  • Turret servo package:
    • Drive: APD‑VP20(SNT) AC servo amplifier (200 – 230 VAC, 3‑phase).
    • Motor: APM‑SG20MKX1‑SNT, 2 kW @ 1 000 rpm, absolute encoder, IP‑65, with brake.
    • Encoder: TS5643N1 multi‑turn absolute optical/magnetic hybrid, ABZ incremental outputs + serial multi‑turn data.
    • Signal exchange with Fanuc is via dry‑contact and PMC bits for turret index, clamp/unclamp and axis ready.
S&T Machine Tool

1.2 Absolute‑backup battery

The APD‑VP20 houses a 3 V lithium cell (CR‑1/2AA or equivalent) that keeps encoder multi‑turn data and drive parameters alive. Low voltage triggers:

  • AL‑14 ABS Data Error
  • AL‑15 ABS Battery Error
  • AL‑16/17 Multi‑turn overflow

If the machine is powered with a dead battery the drive locks, Fanuc does not receive “Servo Ready” and the turret axis reports an alarm.


 TS5643N1 Encoder

2 Absolute Encoders vs. Electrical Zero

  • Electrical 0° — the reference angle for vector control, aligned with the rotor magnetic poles.
  • Mechanical zero (Z‑pulse) — one pulse per revolution supplied by the encoder and factory‑aligned to electrical 0°.
  • Multi‑turn count — stores the number of revolutions, maintained by battery or Wiegand energy harvesting.

Any movement of the encoder housing with respect to the motor shaft (loosening the flex coupling, removing fixing screws, etc.) destroys that alignment → field‑orientation fails → over‑current or inability to find the Z pulse.


3 Root‑Cause Chain Analysis

StepTriggerConsequence
Battery diesAL‑15, absolute data invalid
Encoder suspected faulty, coupling loosenedEncoder shifted relative to rotor
Re‑assembled randomlyZ‑pulse no longer equals electrical 0°
Battery replaced but no calibrationDrive still alarms, cannot Servo‑On
CNC continues to alarmTurret cannot index, machine down

4 Tools & Safety Preparation

  • 3 V CR‑1/2AA lithium cell (original or Panasonic welded type).
  • Phillips and Allen keys, torque driver.
  • Manual pulse generator (MPG) or low‑speed jog via PLC panel.
  • Insulated gloves, multimeter, oscilloscope (optional to watch Z‑pulse).
  • LS Loader PC utility + RS‑232 cable (optional).

Wait 5 minutes after power‑off until the ‘CHARGE’ LED is out (< 50 V DC bus) before opening the cabinet.


APM-SG20MKK1-SNT  MOTOER

5 Step‑by‑Step Restoration Workflow

5.1 Replace the Drive Battery

  1. Open the electrical cabinet → remove the small cover on top of the APD‑VP20 → pull out the old cell.
  2. Inspect for corrosion → insert new cell, mind polarity.
  3. Power up and verify AL‑15 clears. If still present, check PC‑802 Battery Test shows > 2.7 V.

5.2 Mechanical Realignment of the Coupling

  1. Loosen the two M3/4 screws of the flexible coupling on the encoder side — leave them finger‑tight.
  2. On the drive keypad select PC‑806 Z POS Search → press ENTER.
    • The motor rotates ~ 5 rpm forward; it stops at the first Z‑pulse.
  3. This is the encoder’s Z position but may not match electrical 0°. Use an oscilloscope or monitor Iq current to find the minimal torque point; gently rotate encoder housing until current dips and no over‑current trip occurs.
  4. Tighten coupling screws to 0.8 N·m.

5.3 Drive Parameter & Menu Operations

turret

For multi‑turn absolute encoders only:

  1. Run PC‑811 ABS Encoder Set; display shows “reset” for 5 s → writes new zero.
  2. AL‑14/16 should now clear.
  3. Check feedback position in PC‑401 ~ PC‑408; should read 0 or near.
  4. Re‑enable SVON; drive READY should be true and the axis can jog.

5.4 Rebuild Fanuc Reference Point

  1. In Fanuc PMC I/O diagnose page confirm LS READY bit (e.g., X/G0122) is ON.
  2. MDI: G28 T0 or OEM macro to home turret.
  3. PARAM > 1815 bit APZ set to 1 to store the new absolute zero.
  4. Power cycle; verify no SV420 TURRET REF LOST or SV041 AXIS ZRN alarms.

Fanuc Electric Control Cabinet

6 Key Menu Details

6.1 PC‑806 Z POS Search

  • Scans ABZ for the Z‑pulse.
  • If no Z within 10 s drive trips AL‑08 (position sensor fault). Check encoder wiring or [PE‑204] resolution = 2048.

6.2 PC‑811 ABS Encoder Set

  • Saves current single‑turn & multi‑turn counts as zero.
  • Clears AL‑14/16 flags and battery warning.

6.3 HSIN / HSOUT Handshake

  • If the PLC reads absolute coordinates via ABSCALL, request with SVON=OFF, set ABSCALL=ON. Reset to OFF when finished.
  • PLC toggles HSIN every 2 bits read, until 30 bits complete; avoids G28 homing but most shops prefer G28 for simplicity.

FANUJC Series OI-TC

7 Commissioning & Verification

  1. Set drive Torque Limit = 10 %; jog ±10 turns, observe MONIT1 < ±5 A.
  2. Execute T0101 → T0202 index cycle; single‑shot index, no clunk.
  3. Run > 100 continuous tool change cycles; confirm temperature & alarm count = 0.

8 Preventive Measures & Maintenance Tips

  • Log battery voltage every 6 months. Replace when < 2.8 V.
  • Apply thread‑locker to coupling screws; yearly torque check.
  • Backup all Fanuc parameters (including 9000 macros) and LS drive menus to both USB & cloud.
  • Prohibit unauthorised encoder disassembly; if required, mark mating parts or 3D‑scan the position.

9 FAQ

  1. Can we convert to an incremental encoder to avoid batteries?
    Incremental is supported, but you must rewrite Fanuc PMC logic for turret indexing and home every power‑cycle — not recommended.
  2. How to clear AL‑03 phase error?
    Redo Z POS Search and adjust coupling; also verify motor phases U‑V‑W match drive outputs.
  3. Can absolute data be backed up via RS‑232?
    LS Loader backs up menu parameters but not encoder EEPROM; multi‑turn info relies on the battery only.

10 Closing Remarks

This guide compiles a full troubleshooting‑calibration‑verification workflow for LS APD‑VP drives suffering absolute‑zero loss due to battery failure and mechanical disassembly, using the S&T TNL‑120V turret as a real‑world case. Following the four major steps herein you can restore turret operation within 2 hours and avoid repeated strip‑down.

Key takeaway: Replace batteries proactively & mark mechanical alignment. If disassembly is unavoidable, use the drive’s built‑in Z capture + ABS reset to re‑establish zero, then make the CNC store the new reference — fix it once, fix it right.

Posted on

User Guide for Xinshuangyuan AT Series Frequency Inverter

I. Introduction

The Xinshuangyuan AT Series Frequency Inverter is a widely used device in the field of industrial control. Its user manual serves as an essential guide for users to operate and maintain the inverter correctly. This document, based on the contents of the user manual, provides a detailed introduction to the operation panel functions, parameter setting methods, implementation of external control functions, and troubleshooting of fault codes for the AT Series Frequency Inverter, aiming to assist users in better understanding and utilizing the inverter.

AT1 INVERER

II. Introduction to Operation Panel Functions

The operation panel of the Xinshuangyuan AT Series Frequency Inverter is the primary interface for user interaction with the inverter. Through the operation panel, users can perform tasks such as parameter setting, status monitoring, and fault diagnosis. Below is an introduction to the functions of each key on the operation panel:

  • Programming Key: Used to select between normal mode and programming mode. This key is effective whether the inverter is running or stopped. To modify parameters, users must press this key to enter programming mode.
  • Function/Save Key:
    • Normal Mode: Pressing this key displays various information about the inverter’s status, such as target frequency, output frequency, current, and temperature.
    • Programming Mode: Pressing this key displays parameter contents and, when pressed again, saves any changed parameter values.
  • ▲ Key: Increases parameter numbers or values. A short press results in step-by-step changes, while a long press leads to rapid changes.
  • ▼ Key: Decreases parameter numbers or values.
  • Shift Key: Used for shifting in programming mode and jogging in normal mode.
  • Forward/Reverse Key: Toggles between forward and reverse rotation.
  • Start Key: Initiates the output of the inverter.
  • Stop/Reset Key: Stops operation and resets faults.

III. Parameter Setting and Password Management

1. Parameter Initialization

Although the user manual does not directly mention the steps for parameter initialization, users can achieve it through the following method:

  • Enter programming mode and locate the parameter group that needs to be initialized.
  • Restore the parameter values to their defaults.
  • Save the parameters and exit programming mode.

2. Password Setting

To protect the inverter’s parameters from unauthorized modifications, users can set a password. Below are the relevant parameters for password setting:

  • P008: Hidden password, with a range of 0-65535 and a default value of 00000 (no password). Users can set a password as needed.
  • P009: Password input. When the value of P009 equals the hidden value of P008, P008 and other parameter values can be changed. After a power-off restart, P009 will be cleared, and the password must be re-entered to modify parameters.

3. Parameter Access Restrictions

Some parameters of the Xinshuangyuan AT Series Frequency Inverter are only applicable to certain models. For example, gray parameters are exclusive to advanced models with PID/485 functions and are invalid for standard models. Additionally, specific parameters are exclusive to the AT2 model (such as P97, P98) and time counter models (such as *93, *94). Users should pay attention to the applicable range of parameters when setting them.

AT inverter

IV. Implementation of External Control Functions

1. External Terminal Forward/Reverse Control

The Xinshuangyuan AT Series Frequency Inverter supports external terminal forward/reverse control. Below is the wiring method for the AT3 model:

  • X4 Input Port 4: Line-controlled forward rotation. Short-circuiting X4 with COM activates the input signal.
  • X5 Input Port 5: Line-controlled reverse rotation. Short-circuiting X5 with COM activates the input signal.

For AT1, AT4, and AT2 models, although the user manual does not directly mention the specific terminals for external terminal forward/reverse control, users can achieve forward/reverse control through multifunction input settings.

2. External Potentiometer Frequency Regulation

The Xinshuangyuan AT Series Frequency Inverter supports external potentiometer frequency regulation. Below are the wiring and parameter setting methods:

  • Wiring: Users can achieve external potentiometer frequency regulation through external analog voltage input (VI1, 0-5V/10V) or external current signal input (CI, 4-20mA). Refer to the wiring diagram in the user manual for specific wiring methods.
  • Parameter Settings:
    • P010: Source of operating frequency. Select external analog signal (2) or CI (3) as the frequency source.
    • Other relevant parameters (such as P000-P007) may need to be adjusted to match the input range of the external potentiometer.

V. Fault Codes and Troubleshooting Methods

The Xinshuangyuan AT Series Frequency Inverter provides detailed fault codes and troubleshooting methods. Below are some common fault codes and their corresponding troubleshooting methods:

  • Err 1: Overcurrent/Output Short Circuit
    • Troubleshooting Method: Check the output circuit and motor for short circuits, and eliminate any short-circuit faults.
  • Err 2: Undervoltage Protection
    • Troubleshooting Method: Check if the input power supply voltage is normal and eliminate any issues with low power supply voltage.
  • Err 3: Overvoltage Protection
    • Troubleshooting Method: Check if the input power supply voltage is too high or if there is a fault in the inverter’s internal voltage detection circuit.
  • Err 4: Drive Circuit Fault
    • Troubleshooting Method: Contact professional maintenance personnel to inspect and repair the drive circuit.
  • Err 5: Start Input During Power-On
    • Troubleshooting Method: Check if there is an accidental start signal input during power-on and eliminate any misoperations or circuit faults.
  • Err 6: Overcurrent Protection
    • Troubleshooting Method: Check if the motor and load are overloaded or if there is a fault in the inverter’s internal current detection circuit.
  • Err 7: Timeout
    • Troubleshooting Method: Check the inverter’s runtime settings or related timer settings and eliminate any timeout faults.
  • Err 8: Radiator Overheating
    • Troubleshooting Method: Check if the radiator is blocked, if the ambient temperature is too high, or if there is a fault in the inverter’s internal temperature detection circuit.
  • Err 9: External Fault
    • Troubleshooting Method: Check the external control signal lines and equipment and eliminate any external faults.

VI. Conclusion

The user manual for the Xinshuangyuan AT Series Frequency Inverter is an essential guide for users to operate and maintain the inverter correctly. This document, based on the contents of the user manual, provides a detailed introduction to the operation panel functions, parameter setting methods, implementation of external control functions, and troubleshooting of fault codes. It is hoped that this document can assist users in better understanding and utilizing the Xinshuangyuan AT Series Frequency Inverter, thereby improving the operational efficiency and reliability of the equipment. In practical applications, users should refer to the user manual for operation and maintenance according to their specific needs and equipment models.