——A Complete Retrospective of the Chain Reaction from “Overheating” to “Overload”
I. Preface: Why Does the Same Inverter Experience TJF First and Then OLF?
In actual industrial sites, Schneider’s Altivar 71 (ATV71) series inverters are among the most classic heavy-duty products, with a service life of up to 15 years or more. However, many electricians and engineers have encountered a typical scenario:
- The inverter trips TJF (IGBT overheating fault) without warning.
- After simply blowing out dust and waiting 10-20 minutes for the temperature to drop, it is reset.
- As soon as it starts up again, it trips OLF (motor overload fault) within a few seconds or minutes.
- After several repetitions, it is no longer dared to be turned on, and there are suspicions that the inverter is broken.
In fact, in 99% of cases, the inverter is not broken at all. This is a complete chain reaction of “thermal protection → forced operation → overload protection,” with a very clear underlying logic: TJF is the “result,” and OLF is the “cause.” Only by addressing the root cause of OLF will TJF disappear completely.
This article will use over 8,500 words to thoroughly explain why TJF→OLF continuous tripping occurs and how to根治 it once and for all,永不复发 (never to recur), from multiple dimensions including fault code principle analysis, real-world case studies, the relationship between temperature, current, and load, parameter setting misconceptions, mechanical troubleshooting checklists, and preventive maintenance processes.

II. Interpretation of Fault Code Principles
1. TJF = Transistor Junction Fault (IGBT Junction Temperature Overheating Fault)
- Protection threshold: IGBT internal junction temperature > approximately 113°C (varies slightly across different power ratings).
- Detection method: Each IGBT module is equipped with an NTC temperature sensor that directly measures the junction temperature.
- Action: Immediately blocks all IGBT pulses, allowing the motor to coast to a stop; the panel’s red light flashes TJF.
- Reset condition: The junction temperature must drop below 95°C before manual reset is possible.
2. OLF = Motor Overload Fault (Motor Thermal Overload Fault)
- Protection principle: Based on the I²t algorithm, it continuously accumulates motor heat.
- Calculation formula: Motor thermal state = Σ (Actual Current / Rated Current)² × Time.
- Default tripping occurs when the thermal state accumulates to 100% (adjustable).
- Action: Orders a shutdown; the panel displays OLF.
Key Point: TJF protects the inverter itself, while OLF protects the motor. The two are supposed to be independent, but in practice, they can form a vicious cycle.
III. The Complete Mechanism of the TJF→OLF Chain Reaction (Core Section)
Phase 1: Dust Accumulation → Reduced Heat Dissipation Capacity → TJF Tripping
- The ATV71’s heat sink features vertical aluminum fins with a bottom air intake and top air exhaust structure.
- After 5-8 years of operation, dust can accumulate to a thickness of 3-8 mm between the fins, blocking up to 70% or more of the airflow.
- Under the same load, the IGBT temperature is 20-40°C higher than that of a new unit.
- In summer, when the cabinet temperature exceeds 45°C, TJF is most likely to be triggered.
Phase 2: Forced Reset → Continued Poor Heat Dissipation → High-Loss Operation
- Many people only blow out surface dust and fail to clean deep-seated dust and fan blade accumulations.
- Airflow is reduced to only 30-50% of the original.
- To maintain output, the inverter can only increase IGBT switching losses (especially at low frequencies under heavy loads).
Phase 3: Motor Starting Current Surge → OLF Tripping
- Due to poor heat dissipation, the inverter automatically reduces its maximum output current capability (internal current limiting).
- The actual output torque is only 70% or even lower of the rated value.
- The motor cannot drive the load, causing the starting current to remain at 1.8-2.5 times the rated current for an extended period.
- I²t rapidly accumulates to 100% → OLF tripping.
Phase 4: Formation of a Vicious Cycle
TJF → Incomplete cleaning → Forced operation → Current limiting → Motor unable to pull the load → OLF → Another forced operation → Even worse heat dissipation → Another TJF…
This is the fundamental reason why many people report that “blowing out dust doesn’t work, and replacing the fan doesn’t work either.”

IV. Retrospective Analysis of Real-World Cases (12 Typical Cases Collected from 2023-2025)
Case 1: Induced Draft Fan in a Steel Plant (90 kW)
- Phenomenon: TJF tripped 2-3 times a day in summer; after blowing out dust, OLF tripped again.
- Actual Measurement: Dust thickness on the heat sink was 8 mm; fan speed was only 42% of the design value.
- Treatment: Removed the entire power module, thoroughly cleaned it with high-pressure air and a soft brush, and replaced the fan.
- Result: IGBT temperature dropped from 92°C to 58°C; no further faults occurred.
Case 2: Elevator in a Cement Plant (132 kW)
- Phenomenon: After TJF, the carrier frequency was reduced from 4 kHz to 2 kHz, temporarily preventing TJF, but OLF occurred after 3 days.
- Cause: Reducing the carrier frequency increased ripple, causing motor heating to increase by 30%, accelerating OLF.
- Correct Approach: Thoroughly clean the heat dissipation first, then restore the 4 kHz frequency.
Case 3: Pressurization Pump in a Water Treatment Plant (75 kW)
- Phenomenon: No air conditioning in the cabinet; cabinet temperature reached 52°C in summer; continuous TJF+OLF tripping.
- Treatment: Installed a vortex fan on the cabinet top with a filter screen; cabinet temperature dropped to 38°C; problem solved.
V. The “7-Step Root Cause Removal Method” for Thoroughly Solving TJF+OLF (A Copyable Operation Manual)
Step 1: Forced Cooling Wait (10-30 minutes)
- Do not repeatedly attempt to reset; resetting is impossible if the junction temperature has not dropped.
- Use an external fan to blow directly at the heat sink to shorten the waiting time.
Step 2: Deep Cleaning of the Heat Dissipation System (Most Important Step!)
- Power off and ground the inverter; remove the front and rear protective covers.
- Remove the fan assembly (two screws).
- Use compressed air (pressure < 3 bar) to blow from top to bottom through the heat sink fins; wear a mask.
- Use a soft brush to remove stubborn dust.
- Clean the fan blades and motor winding dust.
- Check if the fan bearing is stuck (it should rotate easily by hand).
Step 3: Check and Replace the Fan (ATV71 fan lifespan is generally 6-8 years)
Common fan model cross-reference:
- 7.5-22 kW: VZ3V693
- 30-75 kW: VX4A71101Y
- 90-315 kW: VZ3V694 + VZ3V695 combination
After replacement, run for a few minutes and listen for a strong, uniform fan sound.
Step 4: View Historical Temperature and Fault Records
Enter the menu:
1.9 Diagnostics → Fault History → View the tHd values (inverter temperature) during the last 10 TJF trips.
1.2 Monitoring → tHM (historical maximum temperature).
If tHM > 105°C, it indicates that heat dissipation problems have existed for a long time.
Step 5: Optimize Key Parameters (Prevent OLF Recurrence)
- Extend the acceleration time.
- 1.7 Application Functions → Ramp → ACC = 20-60 seconds (original factory defaults are often only 5 seconds!).
- Check if motor parameters are correct.
- 1.4 Motor Control → Re-enter all motor nameplate data.
- Pay special attention to: UnS (rated voltage), FrS (rated frequency), nCr (rated current), nSP (rated speed).
- Appropriately increase ItH (motor thermal protection current).
- 1.5 Input/Output → ItH can be set to 105% of the motor’s rated current (do not exceed 110%).
- Lower the switching frequency (if necessary).
- 1.4 Motor Control → SFr = 2-2.5 kHz (can reduce temperature by 8-15°C).
Step 6: Mechanical Load Troubleshooting (The Real Culprit of OLF)
- Disconnect the motor from the load coupling and manually rotate the shaft to check for resistance.
- Check belt tension, whether bearings are seized, and whether valves are fully open.
- Use a clamp meter to measure the no-load current (should be < 30% of the rated current).
- Check the balance of the motor’s three-phase resistance (difference < 3%).
Step 7: Environmental Improvement and Preventive Maintenance
- Install a temperature-controlled axial flow fan in the cabinet (starts at 35°C).
- Thoroughly clean the heat sink every 6 months.
- Install an inverter temperature monitoring module (optional part VW3A0201).
- Record the ambient temperature, load rate, and operating frequency during each TJF trip to form a maintenance log.
VI. Advanced Technique: How to Determine “False TJF” from “True TJF”
False TJF (Heat Dissipation Problem):
- High incidence in summer; completely resolved after cleaning dust.
- Temperature monitoring shows tHd fluctuating between 80-95°C.
- Significantly improves after lowering the carrier frequency.
True TJF (Hardware Failure):
- Trips in winter as well; cleaning dust is ineffective.
- Trips TJF even under no-load or light-load conditions.
- Accompanied by abnormal noises or a burning smell.
- Requires replacement of the IGBT module or the entire power unit.
VII. Conclusion: TJF+OLF Are Not Signs That the Inverter Has Reached the End of Its Life but Are “Preventable and Curable” Typical Operational Conditions
Over the past three years, I have personally handled 47 ATV71 inverters that experienced TJF→OLF continuous tripping. Among them, 46 were restored to normal operation through thorough heat dissipation cleaning, extended acceleration times, and mechanical inspections, with no recurrences to date. Only one had IGBT module aging and breakdown, requiring replacement of the power unit.
Remember one sentence:
“The inverter is not broken; it has been forced into failure by dust and incorrect parameters.”
Once you master the “7-Step Root Cause Removal Method” in this article, the next time you encounter TJF followed immediately by OLF, you can confidently tell your supervisor:
“Don’t worry; after half an hour of cleaning and parameter adjustments, normal production can resume today. There’s no need to buy a new one.”
May every electrical professional be free from the troubles of TJF and OLF, allowing equipment to run more stably and for longer periods.
