Comprehensive User Guide for Yuchao Inverter YTA/YTB Series

  1. Operation Panel Functions and Parameter Settings
    1.1 Operation Panel Features

The YTA/YTB series features a 4-digit LED display panel with:

Status indicators‌: RUN (operation), STOP (stop), CTC (timer/counter), REV (reverse)
Function keys‌:
FUNC: Parameter setting
PROC: Parameter save
▲/▼: Frequency adjustment
FWD/REV: Forward/reverse control
STOP/RESET: Stop/reset
1.2 Password Protection and Parameter Initialization

Password Setup‌:

Press FUNC to enter parameter mode
Set D001 parameter (user password) to 1 for unlocking
Restore to 0 after modification to lock parameters

Factory Reset‌:

Unlock parameters (D001=1)
Locate D176 parameter (factory reset)
Set to 1 and press PROC to execute initialization

  1. External Control Implementation
    2.1 External Terminal Forward/Reverse Control

Wiring‌:

Forward: Connect FWD terminal to COM
Reverse: Connect REV terminal to COM
Common: COM terminal

Parameter Settings‌:

D032=1 (external terminal control)
D096=0 (FWD for forward/stop, REV for reverse/stop)
D036=2 (allow bidirectional operation)
D097 sets direction change delay (default 0.5s)
2.2 External Potentiometer Speed Control

Wiring‌:

Potentiometer connections:
Ends to +10V and COM
Wiper to AVI terminal
AVI range selection via DIP switch (0-5V or 0-10V)

Parameter Configuration‌:

D031=1 (frequency source from AVI)
Match potentiometer output range with DIP switch
Set D091-D095 for analog-frequency mapping

  1. Fault Diagnosis and Solutions
    3.1 Common Error Codes
    Code Meaning Solution
    Eo/EoCA Overcurrent Increase acceleration time (D011)
    EoCn Running overcurrent Check load/motor condition
    EoU Overvoltage Extend deceleration time (D012)
    EoL Overload Reduce load or increase capacity
    ELU Undervoltage Check power supply voltage
    3.2 Maintenance Guidelines

Regular Checks‌:

Clean heat sinks and vents every 3 months
Verify terminal tightness
Monitor operating current
Record fault history (D170-D172)

  1. Advanced Functions
    4.1 PLC Programmable Operation

Configuration‌:

D120=1/2/3 (select single/cyclic/controlled cycle)
D122-D136 set segment speeds
D141-D156 set segment durations
D137/D138 set direction for segments
4.2 PID Closed-loop Control

Setup‌:

D070=1 (enable PID)
D072-D074 set P/I/D parameters
Connect feedback signal to ACI terminal (4-20mA)
Set target value via AVI or panel
4.3 RS485 Communication

Parameters‌:

D160: Station address (1-254)
D161: Baud rate (4800-38400bps)
D163: Communication format (8N2 RTU mode)

This guide covers all operational aspects from basic controls to advanced applications of Yuchao YTA/YTB series inverters. For complex issues, please contact us.