ABB ASFC-01C Switch Fuse Controller,Used

$278.00

The ABB ASFC-01C is a Switch Fuse Controller designed to work specifically with ABB drive systems. It provides safe and intelligent control of fuses in multi-inverter setups, allowing monitoring of charging current, drive enable/disable control, and status feedback to a central PLC.

Category: Brand:

Description

ABB ASFC-01C Switch Fuse Controller

🔌 Section 1: Wiring Connections

1. Power Supply Terminal (X5 / X7 / X8)

X5:
  - Pin 1 (L): AC 230V Live
  - Pin 2 (N): AC 230V Neutral
  - Pin 3 (PE): Protective Earth
  - Pin 4 (LSOL): Solenoid Coil Control Line L
  - Pin 5 (NSOL): Solenoid Coil Control Line N

X7 (Optional):
  - 230V AC Input

X8 (Optional):
  - 115V AC Input

2. Auxiliary Output (X4)

- Pin 1: +15V DC (Output to external sensors or logic)
- Pin 2: AUX2 (Spare auxiliary output)
- Pins 3 & 4: GND

3. Charging Current Monitoring Inputs (X1/X2/X3)

These inputs monitor inverter DC bus charging current via external current sensors:

- X1: IR1+ / IR1− → Inverter 1
- X2: IR2+ / IR2− → Inverter 2
- X3: IR3+ / IR3− → Inverter 3

4. Control Signals (S1 to S3)

Each group handles one inverter:

- DIS: Disable command (input from PLC)
- EN: Enable command (input from PLC)
- UDC: DC bus voltage detect (optional)
- STAT: Status output (feedback to PLC or HMI)

⚙️ Section 2: Control Logic

  1. Startup & Power Management
    • 230V AC powers the ASFC-01C.
    • LSOL/NSOL are used to control external solenoids or contactors.
    • Charging current from each inverter is monitored; presence of current implies fuse is intact.
  2. Enable/Disable Logic
    • EN = HIGH, DIS = LOW → Inverter enabled.
    • EN = LOW or DIS = HIGH → Inverter disabled.
    • UDC input helps confirm DC bus voltage availability.
  3. Monitoring & Protection
    • If charging current (IR+) is not detected, fuse may be blown → ASFC disables power.
    • STAT signal provides real-time status feedback to PLC for alarms or logic handling.

📊 Section 3: Ratings

Parameter Value
Supply Voltage 230V AC, 50/60 Hz, 40 mA / 115V AC, 80 mA
Solenoid Control Output 115/230V AC, Max 2A / 3.5s
Excitation Voltage Output 15V DC, Max 10 mA
Charging Current Input Max 16A DC (per channel)
Operating Temperature Up to +70°C

🖼️ Section 4: Wiring Diagram

Wiring Diagram

This schematic shows the ASFC-01C controlling three inverters (INV1 to INV3), receiving control signals from a PLC, and monitoring current for fuse status.


✅ Application Scenarios

  • Multi-inverter control and fuse safety management