Posted on

Investigation into Configuration Error Issues with Siemens TIA Portal V20 S7-1500 Station_1

1. Default Generation of Station_1 and Compilation Check Behavior

In TIA Portal V20, when a new project is created and any S7-1500 CPU (e.g., 1517F-3 PN/DP) is added, a hardware station named “S7-1500/ET200MP station_1” (Station_1) appears in the project tree. This is a default behavior of the TIA Portal system: Whenever a PLC device is added, a station is created for hardware configuration, and automatic consistency/integrity checks are performed. Compared to the earlier STEP7 V5.x software, TIA Portal implements stricter compilation validation for hardware configurations. Even if only the default CPU itself is present without any added expansion modules, TIA Portal includes Station_1 in the compilation check scope to ensure the completeness and correctness of the hardware configuration. This is reflected in the official support documentation: Issues with incomplete station checks in older software versions have been improved in TIA to perform default integrity validations. Therefore, the automatic generation of Station_1 after adding a CPU to each new project and its verification during hardware compilation are normal system behaviors, not faults.

S7-1500/ET200MP station_1

2. Reasons for Integrity Errors Despite No Added Modules

Even when no expansion modules are added and only the CPU itself remains, hardware compilation still reports a configuration error for Station_1. The main reason lies in TIA Portal’s integrity and consistency checks on hardware stations, which encompass two aspects: hardware component integrity and security/access configuration integrity.

Firstly, from a hardware perspective, TIA checks whether the station lacks necessary modules or terminals. For example, in distributed I/O stations (such as ET200SP/ET200MP interface modules), if there is no at least one signal module or if the end “server module” (used for termination/power supply) is not inserted, compilation errors indicating incomplete configuration (e.g., “missing server module”) will be reported. This check mechanism aims to prevent empty or incorrect station configurations. For instance, some materials state: “The server module must be configured; otherwise, compilation will report an error indicating the absence of the server module.” Therefore, even if users do not manually add modules, the system performs integrity validation on Station_1 and reports errors when the default station does not meet the expected complete configuration.

Secondly, from a security configuration perspective, TIA Portal V20 introduces a new feature of local user management and access control (UMAC) to manage CPU access permissions. If access control is enabled (enabled by default in V19 and later versions), the integrity of the CPU’s security configuration is checked even without additional modules. This means that if essential users/roles are not configured, compilation errors will also be reported (see Section 4 for details). In summary, TIA Portal still performs station integrity checks even when no modules are added because the system assumes that even with only the CPU, minimum configuration requirements in terms of both hardware and security must be met; otherwise, a “configuration error” is indicated.

3. Default Requirements for Rail_0 Regarding Configuration Integrity

“Rail_0” under “S7-1500/ET200MP station_1” represents the rack/rail where the CPU is located. By default, this rail station is set to require configuration integrity, meaning basic configuration completeness conditions must be satisfied.

  • Module Configuration Integrity: For modular rail systems like ET200MP/ET200SP, TIA Portal requires that each station must be correctly configured with necessary modules and end pieces. For example, in an ET200SP station, the first slot must have a module, and a server module must be inserted at the end to close the backplane bus; otherwise, compilation errors will be reported. Although the S7-1500 main station integrates the backplane and does not require a separate server module like remote stations, Rail_0 still assumes by default that “unreasonable empty configurations” are not allowed. If a user adds a remote ET200MP station under Station_1 but does not place any modules, the system will also report errors during compilation indicating missing modules or accessories, thereby forcing the user to complete the hardware configuration.
  • Configuration Integrity Check Options: In TIA hardware configuration, there is no explicit requirement to fill in parameters such as “total number of slots” (the system automatically determines this based on the configured modules). However, the station itself has an implicit integrity validation mechanism that does not allow the absence of key components. This includes situations such as module absence mentioned above and the absence of security-related configurations in the case of safety CPUs. Rail_0 enables these integrity check rules by default, so even with only the CPU, it must pass security configuration checks (see the following section for details).

It should be noted that a power module is not a mandatory configuration item for the S7-1500 main station. The S7-1500 CPU comes with basic power supply and does not require a separate power module like the S7-300. Therefore, Rail_0 does not require a power module to be inserted for successful compilation (unless additional power supply expansion is actually needed). Rail_0 is more concerned with the logical integrity of the station: for remote stations, whether there are I/O modules and terminals; for local main stations, whether access control configurations are met, etc. Therefore, “Rail_0 requires configuration integrity” is manifested in the fact that errors are triggered by the absence of necessary modules or necessary configurations. This is a system default setting used to ensure that the hardware configuration is consistent with the actual hardware installation.

4. F-CPU Security Functions and User Role Requirements

When using an S7-1500 F-CPU with fail-safe functions (such as 1517F-3 PN/DP), compilation errors are often related to security access permission configurations. Since TIA Portal V19, a new mechanism of local user and role management (access control) has been introduced and is enabled by default for all newly added CPUs. Once enabled, the system requires that at least one user be granted full access permissions to the CPU; otherwise, hardware configuration cannot pass compilation. The official documentation clearly states: “At least one user must have full access permissions to the CPU; otherwise, the configuration cannot be compiled.” For fail-safe CPUs (F-CPUs), the requirements are further enhanced—this user must also have “full access including fail-safe” permissions to perform download and operation operations on the F-CPU. In other words, if an F-series CPU is used but no user is granted fail-safe access permissions in user management, compilation/download operations will terminate with error reports. This is usually manifested as error messages in the compilation information similar to “at least one user must have full access permissions including fail-safe.”

The reason for this requirement is that F-CPUs involve security functions. To prevent unauthorized changes, TIA Portal includes fail-safe permissions as part of the configuration integrity check. When access control is activated, the old method of protecting access levels through simple passwords is replaced by user/role permission management. Therefore, for CPUs like the 1517F, user role configurations must be in place (e.g., creating an “Admin” user and granting it the “full access (including F access)” role) before hardware can be successfully compiled and loaded. If the user does not configure any local user roles (the TIA Portal starts with an empty configuration for new projects), the compiler considers the security configuration incomplete and reports errors indicating configuration errors.

In short, security functions make F-CPUs subject to an additional check compared to ordinary CPUs: whether a user with sufficient permissions exists. If not, Station_1 will fail during compilation. This is the root cause of the problems encountered by many users and needs to be resolved by appropriately configuring user roles.

CPU 1518TF-4 PN/DP

5. Impact of Project Templates or System Default Settings

After investigation, it has been found that TIA Portal V20 does not have a special “project template” that would generate an ET200MP station for no reason and cause errors; the problems are more likely due to the combined effects of system default settings and the selected CPU type:

  • Local User Access Control Enabled by Default: As mentioned earlier, since V19, access control functions for CPUs have been enabled by default in new TIA projects. This is not a template specifically chosen by the user but a system-wide default behavior. Therefore, after adding a CPU to each new project, the “enable access control” option is already checked in its properties, forcing the user management mechanism to take effect. If the user is unaware of this change and directly compiles without configuring any users, errors will occur.
  • Default Requirements for Fail-Safe CPUs: When a user selects an F-series CPU, it is equivalent to enabling fail-safe support by default. This is not forced by a template but is triggered by the hardware’s own characteristics, which lead TIA Portal to require security configurations (i.e., requiring F-CPU to configure F user permissions). Therefore, it is not a template that causes errors in Station_1 but rather the incomplete default security settings that prevent successful compilation.
  • Automatic Generation of Station_1: When creating a new project in TIA Portal using a wizard, a PLC device (Station_1) may sometimes be automatically added. However, whether added manually or generated through default configuration, this station itself is not the source of errors; the errors lie in the incomplete configuration within the station. In other words, TIA does not generate an invalid station for no reason; instead, it generates a station that requires further configuration. If no modifications are made and compilation is performed directly, error messages will be seen. All of this is attributable to the system default configuration strategy of TIA Portal V20, not to the user selecting an incorrect project template.

In summary, the system default settings of TIA Portal V20 (enabling access control, hardware integrity checks, etc.) are the main reasons for compilation errors in Station_1. There is currently no evidence indicating the existence of an official project template that specifically “forces the generation” of this station and causes errors; rather, it is the general default mechanisms that are at play.

6. Solution Steps to Eliminate Such Hardware Compilation Errors

For Station_1 hardware configuration errors that occur when no additional modules are added, users have several feasible countermeasures to eliminate the errors:

  • Configure Local Users and Role Permissions: This is the officially recommended method. If access control functions continue to be used, add at least one user in the project’s “Users and Roles” editor and create/assign a role with full access permissions (for F-CPUs, assign the role of “full access (including fail-safe)”). For example, create a user named “Admin” and grant it full control permissions over the CPU. In this way, during hardware configuration compilation, TIA Portal will detect that the necessary user roles exist, and the errors will disappear.
  • Disable Access Control: If the project does not require enabling CPU user access management, this function can be turned off. Select the CPU and, in the property window’s “Protection & Security > Access control” tab, uncheck “enable access control.” After disabling it, TIA will revert to traditional simple access level protection (or no protection) and will no longer require configuring users/roles. It should be noted that after disabling access control, ensure that no CPU services requiring user authentication (such as Web servers, OPC UA servers, etc.) are enabled, as these services will also require at least one user to have corresponding access permissions if enabled. In general, disabling access control can immediately eliminate compilation errors caused by the absence of user roles.
  • Complete Hardware Station Configuration: If the error is not due to security settings but rather due to incomplete configuration of the station itself (e.g., an additionally added ET200MP remote station has no modules), the configuration should be completed according to hardware requirements. For example, add at least one I/O module to the remote station and insert a server module (e.g., the server end cap module for ET200SP systems) in the last slot, or delete unnecessary empty stations. Ensure that each hardware station has a reasonable composition: for the main station CPU, usually the CPU itself is sufficient; for remote stations, at least an interface module + I/O module + server end cap are required.
  • Replace with a Non-Safety CPU (Optional): If the project does not actually require safety functions and the error is only caused by selecting an F-CPU, consider replacing it with a corresponding standard CPU (e.g., replacing the 1517F with the 1517 standard model). Standard CPUs only require a “full access” user when access control is enabled and do not involve “fail-safe” permissions, making the configuration slightly simpler. However, this measure should only be adopted when it is certain that safety functions are not needed; usually, the problem can be solved by configuring user roles as mentioned above without replacing the CPU hardware.
  • Check and Delete Redundant Stations: Confirm whether there are duplicate or unused stations in the project unintentionally. For example, some users have encountered conflicts between two stations with the same name when uploading/merging projects. If there is an unfinished Station_1 in the project in addition to the main CPU station, it can be deleted. Usually, new projects do not generate extra stations for no reason, but this may happen when importing other configurations or templates. Therefore, keeping the hardware station list in the project clean and removing any unnecessary stations helps avoid compilation errors.

After following the above steps to handle the issue, recompile the hardware configuration, and the errors should be eliminated. For example, many users report that simply disabling the CPU’s access control or correctly creating user roles can resolve the “S7-1500/ET200MP Station_1” configuration error. In conclusion, the key to solving the problem lies in meeting TIA Portal’s requirements for station integrity: either complete the security settings or adjust the hardware configuration so that Station_1 is no longer considered an incomplete configuration. After making these adjustments, the hardware compilation in TIA Portal V20 will pass successfully without error messages.

Posted on

TIA Portal V15 Troubleshooting Guide for Downloading to S7-1500 via Ethernet

Overview of the Problem

Users attempting to download programs to an S7-1500 PLC (CPU 1517F-3 PN/DP, firmware version V3.1, order number 6ES7 517-3FP01-0AB0) using TIA Portal V15 on a Windows system via a direct Ethernet connection from the PC’s network port to the CPU’s X2 interface (IP address 192.168.1.1) encounter issues. Symptoms: The PC can ping the PLC, but TIA Portal fails to recognize or connect to the device online, reporting an “Incompatible device” error during download attempts. Users have also tried using an SD card to write the project to the PLC, but the PLC still fails to recognize it as a loadable project. Below, we analyze potential causes in detail and provide corresponding troubleshooting and resolution steps.


S7-1500 is in a stopped state.

Potential Cause Analysis

  1. Incompatibility between TIA Software Version and PLC Firmware Version: The hardware catalog in TIA Portal V15 may not include this newer CPU model (1517F-3 PN/DP, order number 6ES7 517-3FP01-0AB0), preventing the software from correctly identifying the device. The CPU’s firmware V3.1 is a relatively high version, and if the corresponding Hardware Support Package (HSP) is not installed or TIA is not upgraded, an “incompatible device” error may occur. Additionally, Failsafe CPUs require Safety option support; failure to correctly add the safety CPU model in the project can also cause recognition errors.
  2. Mismatch Between PLC Model or Firmware Configuration and Actual Hardware: If the PLC type/firmware version configured in the project does not match the actual hardware, online comparison will fail. For example, if the project uses a non-Failsafe model (e.g., not 1517F-3 PN/DP) or a lower firmware version, TIA will treat the actual device as “incompatible.” This is especially true for Failsafe CPUs, which require the correct F-series model to connect normally. Regarding firmware versions, Siemens PLC firmware is generally downward compatible: programs can usually run if the project’s firmware version is lower than or equal to the actual CPU version, provided the software can recognize the hardware. If TIA V15 does not contain information about CPU V3.1, the hardware catalog must be updated, or the project’s CPU version setting must be changed.
  3. PG/PC Interface and Network Configuration Issues: Incorrect PG/PC interface selection or improper network configuration can prevent TIA from finding the PLC. Possible scenarios include not setting the interface to the correct local network card in TIA, the PC not having an IP address in the same subnet as the PLC, or unrelated networks not being disabled in a multi-network card environment. The most common issue is an incorrect PG/PC interface port selection: the ping command is unaffected by PG interface settings, but TIA communication requires the correct interface configuration. For example, if the PC has both wireless and wired network cards and ping uses the correct card while TIA binds to another interface, the device can be pinged but not found in TIA.
  4. Firewall or Antivirus Software Blocking Communication: The Windows firewall or third-party security software may block communication ports required by the PLC, preventing TIA Portal’s ISO-on-TCP discovery messages from reaching the PLC even if pinging is successful. If the firewall does not allow these ports, TIA may not detect the PLC or connections may be refused. Common domestic security software (e.g., 360 Security Guard, QQ PC Manager) may also disable Siemens-related services/processes, causing connection failures. For example, if the PNIOMGR process is disabled, the PLC cannot be detected. Additionally, incompatible Windows system versions or incomplete TIA installations may affect communication drivers.
  5. Misconceptions in Using Memory Cards for Downloads: When using a memory card for offline downloads, improper procedures can prevent the PLC from recognizing the project or starting up. Common mistakes include not setting the memory card as a “program card” (loadable project), simply copying engineering files instead of writing them correctly via TIA, residual old project data or incomplete files on the card, incorrect CPU startup mode settings, or not removing the physical write protection on the storage card. These issues can result in the PLC failing to recognize a valid startup project even after writing it to the card. Pay special attention to the “loadable project” option configuration; otherwise, the CPU may remain in STOP mode and fail to run the new program.

Below, we provide detailed inspection and resolution steps for each potential cause.

1. Troubleshooting and Resolving TIA Version and PLC Firmware Compatibility Issues

Cause Analysis: When TIA Portal is outdated, its hardware catalog may not include newly released CPU models or firmware versions, leading to connection failures. The 1517F-3 PN/DP (6ES7 517-3FP01-0AB0) in this example is a subsequent product, and its firmware V3.1 may have been released after TIA V15. Without installing updates supporting this CPU, TIA V15 will fail to recognize it correctly, reporting an “incompatible device” error. Additionally, Failsafe CPUs require the corresponding safety CPU model in TIA (requiring the installation of the STEP 7 Safety option); otherwise, recognition errors will occur.

Inspection Steps:

  • Check Actual CPU Information: Confirm the CPU’s actual order number and firmware version through its built-in display or TIA’s “Online Diagnostics.” For example, the CPU panel may show the model 1517F-3 PN/DP and firmware version V3.1 (as seen in user-provided photos). Record this information.
  • Check CPU Configuration in the Project: Open the “Device Configuration” in the TIA project and verify that the selected CPU model and its firmware version match the actual hardware. Ensure the order number and type are correct. If a different model is used in the project (e.g., 1517-3 instead of 1517F-3, or a different order number suffix), it must be changed. For the firmware version, TIA generally allows selecting different versions supported by the model. Check the CPU properties in the project to confirm the firmware version setting matches or is lower than the actual firmware.

Resolution Steps:

  1. Update Hardware Support or Upgrade TIA: Ensure TIA Portal has installed the hardware support package (HSP) containing the 1517F-3 PN/DP (6ES7517-3FP01-0AB0). Visit the Siemens official website to download and install the latest HSP for TIA V15. If the HSP is unavailable or the CPU model still does not appear after installation, consider upgrading the software to V15.1 or higher for native support of the new CPU. Newer TIA versions are generally backward compatible with older projects and support newer firmware.
  2. Modify the CPU in the Project to the Correct Model: In the project tree’s device view, right-click the original CPU module and select “Change Device…”. Locate 1517F-3 PN/DP in the CPU selection list and match the correct order number (note the difference between 3FP00 and 3FP01) and firmware version. For example, select 6ES7517-3FP01-0AB0 with firmware V3.1 (if V3.1 is unavailable in TIA V15, select the highest V2.X version). When changing the device, check “Retain Program” and hardware configuration to avoid losing written logic. After confirmation, the project’s CPU will update to the new model.
  3. Ensure Project Firmware Version Compatibility: For firmware version mismatches, follow the principle that the project’s firmware version ≤ actual firmware version for normal downloads. For example, a project configured with V2.6 can be downloaded to a CPU with actual firmware V3.1 and run, but new features in V3.1 will not be available. If TIA V15 can only select V2.6 and the CPU is V3.1, this is acceptable. However, if the project’s firmware version is higher than the actual version, lower the project’s version or update the PLC firmware.
  4. Install the STEP 7 Safety Option (if applicable): Confirm that TIA has the corresponding version of the Safety module installed and a valid safety programming license. If the initial project used a non-Failsafe CPU due to the lack of Safety support, install Safety support first, then replace the CPU with an F-series model and recompile the project. Failsafe PLCs can only download full-featured projects when configured as safety CPUs in the project.
  5. Attempt Download Again: After making the above changes, recompile the project hardware and try “Download to Device > All.” TIA should now recognize the compatible CPU and no longer report device incompatibility errors. If the error persists, carefully check for differences in the order number/model or consider upgrading TIA.

Note: If upgrading TIA is not possible due to objective constraints, consider downgrading the PLC firmware to a version supported by TIA (not recommended for beginners). For example, some cases involve downloading the program using a higher TIA version, downgrading the CPU hardware information, and then downloading with an older TIA version to enable connection. However, this process is complex and risky; upgrading the software to match the hardware is generally preferred.

Additionally, as a high-end model, the 1517F-3 PN/DP requires a Simatic Memory Card as load memory to run programs (S7-1500 series CPUs must have a card inserted to run; without a card, the CPU cannot enter RUN mode). Therefore, ensure that a non-write-protected SIMATIC memory card is inserted into the PLC during downloads (see the memory card section below for details). Otherwise, downloads may fail or report errors.

TIA failed to connect to S7-1500.

2. Troubleshooting and Resolving PLC Model or Project Configuration Mismatches

Cause Analysis: The hardware configuration in the project must exactly match the actual PLC type; otherwise, connection and download attempts will be rejected. For example, in this case, the CPU is a Failsafe model, but if a standard CPU is mistakenly used in the project, TIA will detect the hardware mismatch and report an “incompatible” error. Similarly, if the project’s firmware version is higher than the PLC’s actual version, download attempts will also fail (usually with a version error message). Additionally, if a project previously downloaded by a higher TIA version remains on the CPU, downloading a lower-version project with an older TIA version may cause conflicts, preventing the PLC from recognizing the new project or reporting version inconsistencies. In such cases, the PLC may not recognize the new project or report errors.

Inspection Steps:

  • Open the project’s device configuration and verify that the station nameCPU model, and interface configuration match the physical device. Focus on checking whether the correct 1517F-3 PN/DP model is selected (not another model), whether the interface (X2) IP setting is 192.168.1.1, and whether the subnet mask matches the actual network.
  • Check the CPU properties for the firmware version setting (if selectable). Ensure it is not higher than the actual PLC firmware. If the project’s firmware version is lower, it is generally acceptable, but you can adjust it to match the actual version as needed to eliminate warnings. Right-click the CPU in the project device and select “Properties” to view the currently configured version and order number, which can be compared with the actual PLC information.
  • If a previous download attempt was unsuccessful, residual project data may remain on the PLC’s memory card, causing conflicts during subsequent downloads. Check the CPU display or online diagnostics for information on residual projects or error states (e.g., Memory card LED or maintenance light).

Resolution Steps:

  1. Correct the CPU Model and Order Number: If the project’s CPU model is incorrect (e.g., 1517 instead of 1517F), follow the previous steps to change it to the correct 1517F-3 PN/DP model. Ensure the order number suffix matches the device (e.g., FP01 vs. FP00). After making changes, regenerate the hardware and software compilation.
  2. Adjust the Firmware Version Configuration: In the project, set the CPU firmware version to no higher than the actual version. TIA allows switching firmware versions within a certain range (right-click the CPU > Change Version, if available). For example, if the actual PLC is V3.1 and TIA V15 supports up to V2.6, set the project’s CPU version to V2.6. The program can still run, but new features in V3.1 will not be available. If TIA has installed an HSP supporting V3.x, select V3.1 to match exactly.
  3. Ensure Consistent Project and Station Names (generally does not affect downloads, but recommended for consistency): Ensure that the project’s PLC station name does not conflict with the PLC’s default name, or set a unique name for the CPU as needed and select the appropriate option during download (overwrite the device’s name or retain the device’s name).
  4. Clear Old Project Data from the PLC: If previous download attempts have left newer version projects or incomplete data on the memory card, clear it first. Method: Format the memory card via the CPU panel or, with the CPU in STOP mode, select “Format Memory Card” in TIA’s “Online & Diagnostics > Functions” to clear the card’s project data. Do not format the SIMATIC card using Windows; only delete project files within it, as formatting with Windows will render the card unusable. Alternatively, remove the memory card, use a PC card reader to delete project files in the SIMATIC.S7S directory (to clear old projects), then reinsert the card and reset the CPU power to prepare it for a clean download.
  5. Redownload the Project: After ensuring the project configuration matches the hardware and the PLC’s memory card is clean, try downloading again. In TIA, select “Download to Device (Software + Hardware)” and check “Selected Stations” for the current project’s CPU. TIA should now detect the correct device type. If a confirmation dialog appears (e.g., “No project information on the device, load as new station?”), select Load as New Station. During the download, if version warnings appear, follow the prompts and select “Continue” (if it is a firmware upgrade prompt, generally select “No” to retain the current firmware). After completion, a successful download message should appear.
  6. Check the Running State: After downloading, observe whether the PLC enters RUN mode. If it remains in STOP and displays an “incompatible” message, there may still be configuration mismatches. Use TIA’s “Online > Accessible Devices” to scan and see if the CPU is correctly identified with its firmware. If the device is marked red and labeled “incompatible” in the scan results, the project configuration still does not match the device, requiring you to recheck the above steps.

Note: When a project downloaded by a higher TIA version exists on the PLC, it may leave version information on the memory card, preventing a lower TIA version from directly overwriting it. This is why downloading a V16 project and then attempting to download with V15 fails. Clearing the memory card or formatting it resolves this issue. Therefore, in environments with multiple TIA versions, it is crucial to keep the TIA version consistent with or higher than the project version on the PLC. If you must downgrade the project version, first delete the newer version project data on the PLC before downloading the lower-version project.

3. Troubleshooting and Resolving Network Connection and PG/PC Interface Settings

Cause Analysis: Improper network parameter configuration is a common yet often overlooked cause. Although users can ping the PLC, this does not guarantee proper TIA connection. Common issues include an incorrectly selected PG/PC interface, incorrect IP address/subnet mask settings, conflicts from multiple network cards, or interference from switches or network devices. The ping command typically uses the operating system’s routing to automatically select the network interface, while TIA communication requires sending proprietary protocols through its configured PG interface. Therefore, selecting the wrong interface can result in a situation where the device can be pinged but not found in TIA. Additionally, if the PC and PLC are not in the same subnet or the gateway is unreachable, the device cannot be discovered.

Inspection Steps:

  • IP Address and Physical Connection: Confirm that the PC’s IP settings are in the 192.168.1.x subnet (not 192.168.1.1 to avoid conflicts with the PLC) with a subnet mask of 255.255.255.0. Ensure that the Link light on the PC’s network port connected to the PLC is solidly lit. The Profinet green light (Link) on the PLC’s X2 interface should also be lit, indicating a physical connection. If a switch is used, check its indicator lights for normal operation. For testing, connect the PC directly to the PLC to rule out issues with intermediate devices.
  • PG/PC Interface Settings: In TIA Portal, open “Set PG/PC Interface” or click the PG/PC interface icon at the bottom of the software to view the selected interface. Choose the actual network card’s TCP/IP interface used (e.g., “PN/IE -> Intel(R) Ethernet … (192.168.1.x)”). Do not select virtual network cards such as those for PLC simulation or VMware if they are not in use. If multiple interfaces are present, try disabling unused network adapters to ensure TIA binds to the correct card.
  • Accessible Devices Scan: In TIA, select “Online > Accessible Devices”, choose the corresponding network card interface, and click “Update”. Check if the PLC and its IP are listed. Ideally, it should display information such as “CPU 1517F-3 PN/DP … IP=192.168.1.1 … Firmware V3.1”. If the list is empty or the device is not found, it may be an interface/firewall issue. If the device is found but marked red as incompatible, return to the previous model matching issue.
  • Third-Party Network Environment: If non-standard switches/routers are used, confirm they are not blocking Profinet DCP broadcasts. Profinet device discovery relies on the DCP protocol, which may not work if the switch does not support it. For testing, connect the PC directly to the PLC to rule out switch-related issues.

Resolution Steps:

  1. Configure Correct IP Settings: Set the PC’s network card IPv4 address to the same subnet as the PLC (e.g., 192.168.1.100) with a subnet mask of 255.255.255.0. The gateway is not required (or can be set to 192.168.1.1). After setting, ping the PLC IP again to confirm connectivity.
  2. Set the PG/PC Interface: In TIA, select “Online > Set PG/PC Interface” and choose the “TCP/IP -> Local Network Card Name (PN/IE)” option. Ensure the IP address displayed matches the PC’s recently set address. If unsure, select the interface corresponding to your PC’s IP in the interface options. Apply the settings and restart TIA’s device scanning function. With the correct interface settings, TIA should now detect the PLC as easily as connecting to a regular network device. If the wrong port was previously selected, the device should now be found in the scan.
  3. Resolve Network Adapter Conflicts: If the PC has multiple networks (e.g., WiFi and wired), disable unused adapters to prevent TIA from confusing routing. This is especially important in VMware or other virtual network environments, where you must specify bridging to the correct physical network card. In virtual machines using TIA, configure the virtual network to bridge the physical network card and select the corresponding virtual network card interface in TIA. Additionally, disable the host firewall if necessary. Ensure that only one active network is used for PLC communication.
  4. Search Again or Connect by Specifying IP: After adjusting the settings, refresh the “Accessible Devices” list in TIA, which should now display the CPU. If the device is still not automatically detected, try manually specifying the IP address for connection in the TIA download dialog: In the download window, click the dropdown arrow next to “Show all accessible devices” and enter 192.168.1.1 in the address bar before pressing Enter. This forces TIA to attempt connecting to the PLC at that IP. In many cases, as long as the network and interface are correct, this step will find the device and allow downloading to proceed.
  5. Check for Special Network Factors: If connectivity issues persist, consider whether other software on the computer is occupying ports or filtering traffic. For example, some VPN clients, firewall policies, or group policies may restrict PN port 102 communication. Use the Windows command netstat -ano | find "102" to check if the port is in use. If necessary, test connectivity on a different computer to determine if the issue is environment-specific.
  6. Ensure No PLC IP Address Conflicts: Confirm that no other device on the network is using the 192.168.1.1 address. Although pinging is successful, it is possible to ping a different device (this can be ignored for direct connections). If multiple PLCs or HMIs are on the network, ensure they all have unique IP addresses.

Note: Ping connectivity only indicates that the ICMP protocol is working, but TIA downloads use the S7 protocol (TCP port 102, etc.). Therefore, it is essential to correctly configure the PG interface and disable the firewall (see the next section) to complete S7 communication. Additionally, Profinet device discovery uses DCP broadcasts, which will not work across subnets or through routers. For cross-subnet downloads, UDP forwarding or direct IP specification methods are required on the router. In most cases, placing the PC and PLC on the same subnet resolves these issues.

4. Troubleshooting and Resolving Firewall and Security Software Issues

Cause Analysis: The Windows firewall and third-party security software may block communication ports required by TIA to access the PLC. A typical manifestation is successful pinging but failure to detect or download from TIA. When the firewall is enabled and does not allow Siemens-related ports, local network connections may be blocked. TIA Portal primarily requires TCP port 102, UDP port 48879, and the DCP protocol for device discovery. If the firewall blocks these, TIA will report connection timeouts or fail to detect devices. Additionally, some domestic antivirus software (e.g., 360 Security Guard, QQ PC Manager) may disable Siemens background services/processes (such as PNIOMGR, S7DOS Service) to optimize the system, causing communication failures. Therefore, both firewall and antivirus software impacts must be considered.

Inspection Steps:

  • Firewall Status: Open “Windows Defender Firewall & Network Protection” and check if the firewall is enabled for the current network (domain, private, or public), especially in domain environments where policies may be strict. Try temporarily disabling the relevant firewall and then search for devices in TIA to see if the PLC can be detected. If connectivity is restored immediately after disabling the firewall, the firewall is likely blocking communication.
  • Security Software Impact: Check if third-party antivirus or optimization software is installed on the system. These programs may prevent certain services from starting. Open Task Manager or the Services list and look for services with “Siemens” or “S7” in their names, such as “SIMATIC IEPG Help Service” or “SIMATIC S7DOS Service”, and ensure they are running. If any are not running, try starting them manually. Then, check if the security software’s “startup optimization” feature has disabled the PNIOMGR.exe process. This process is crucial for Profinet device management; if disabled, the PLC cannot be detected. If blocked, add it to the security software’s trust list or restore its startup.
  • Port Testing: Use Windows PowerShell’s Test-NetConnection -ComputerName <PLC_IP> -Port 102 command to test port connectivity, or use third-party tools (e.g., TCPing) to test whether the PLC’s TCP port 102 is reachable. If the port is unreachable despite successful pinging, the firewall is likely blocking it.

Resolution Steps:

  1. Disable the Firewall for Testing: To quickly verify, temporarily disable the Windows firewall (for both private and public networks) in the Control Panel’s Windows Defender Firewall settings. Then, retry connecting with TIA. If connectivity is restored, add exception rules for Siemens applications in the firewall instead of leaving it disabled. Open the firewall’s “Allowed apps” settings and ensure TIA Portal and related rules (e.g., “SIMATIC Manager”) are checked, allowing access to required ports (TCP 102, UDP 48879, etc.). For Profinet Discovery, you can also allow the “Profinet Discovery” protocol in the firewall’s advanced settings. After adding rules, re-enable the firewall and observe if connectivity is maintained.
  2. Adjust or Uninstall Security Software: If using 360 Security Guard, Huorong, QQ PC Manager, or similar software, try temporarily exiting or uninstalling them and then test connectivity. Many cases show that third-party security software secretly blocks industrial communication. If confirmed as the cause, add TIA Portal to the software’s trust list or disable its network protection module. In 360’s “Optimization Accelerator,” restore any disabled Siemens-related services/processes (e.g., if PNIOMGR is disabled, re-enable it in the startup items and restart the computer). Ensure the PNIOMGR process is running (located in C:\Program Files\Common Files\Siemens\Automation\Simatic OAM\bin by default; can be started manually).
  3. Check System Policies: On some company computers, group policies may disable RPC services or apply AppLocker rules that block TIA components. These can also affect communication. Try installing TIA on a clean personal computer and connecting it directly to the PLC for testing to determine if the issue is environment-specific. If connectivity is restored on a different PC, work with the IT department to restore default firewall rules or disable unnecessary security policies on the original PC.
  4. Network Isolation Devices: If firewalls or routers are present between the PC and PLC, configure them to allow relevant traffic (e.g., hardware firewalls must allow UDP 67, 68 for DCP and TCP 102). If unsure, the simplest method is to connect directly or use a simple switch for direct connection to avoid interference from network
Posted on

S7-1500 Memory Card Offline Programming Process and Analysis of “Empty Card” Issues

I. Correct Process for Offline Programming of S7-1500 Memory Cards in TIA Portal

In TIA Portal, you can directly download a compiled project offline to an SIMATIC memory card for the S7-1500, creating a “program transfer card” for loading programs onto the PLC without an internet connection. The recommended steps are as follows:

Hardware Preparation: Use an official Siemens SD card reader and insert an SIMATIC memory card (e.g., 6ES7 954-8LC04-0AA0) into the computer’s USB port. Ensure the card is not write-protected (slide the side switch to the unlocked position). TIA Portal will automatically recognize the card reader.

Memory Card Identification: In the TIA Portal project tree, expand the “Card Reader/USB Memory” node to view the corresponding memory card drive (e.g., “(G:) SIMATIC MC [Program]”). If it does not appear, refresh it via the menu “Online > Display SIMATIC Card Reader”.

Download Project to Memory Card: Select the CPU station in the project tree (e.g., “PLC_1 [CPU 1516-3 PN/DP]”) and drag it to the memory card drive node. Release the mouse, and TIA Portal will prompt a download dialog. Compile and confirm the write operation as instructed. Alternatively, use the menu option “Online > Write to Memory Card”.

Completion of Writing: If the project compiles and writes successfully, TIA Portal will indicate completion. The memory card now contains the program data files for PLC startup. Safely eject the card from the reader, insert it into the target S7-1500 CPU slot, and power on or reset the CPU to load the program from the card.

Additional Note: The drag-and-drop method generates an S7_JOB.S7S (or .SYS) file and a “SIMATIC.S7S” project folder on the memory card, containing all user program data for the PLC. This allows for offline upgrades without an online PLC connection. If TIA Portal is unavailable, generate the project to a PC folder or USB drive first, then transfer it to the memory card.

6ES7 517-3FP01-0AB0

II. Possible Reasons for Controller Identifying Memory Card as Blank

When an S7-1500 CPU displays “Empty card,” it means no valid user program has been detected on the card. For example, the memory card type is identified as “Empty card,” with 0 used space, as shown below.

An S7-1517F CPU displays the memory card type as “Empty card,” indicating no valid program data has been detected.

Common causes include:

Unsuccessful Project Data Writing: If the offline programming process is not completed correctly (e.g., compilation without “Write to Memory Card” execution, or interruption during download), the card may lack the S7_JOB.S7S file and “SIMATIC.S7S” folder. The CPU will then treat the card as empty. Interruptions (e.g., network/power failures) can result in incomplete project data, preventing CPU recognition.

Memory Card File System or Structure Issues: SIMATIC memory cards for S7-1500 use the FAT32 format with pre-installed hidden system files. Non-official formatting, accidental deletion of hidden files, or file system errors can prevent CPU recognition. For instance, hidden “LOG” and “crdinfo.bin” files are essential for card identification; their deletion or corruption may render the card unrecognizable, causing the CPU to treat it as uninitialized and blank.

Project-CPU Incompatibility: Although not directly causing an “empty card” display, if the card contains a higher-version project unsupported by the CPU firmware or inconsistent project data, the CPU may ignore the card contents. For example, a project version higher than the current TIA Portal engineering version may prevent loading (though the CPU displays an empty card, it actually does not recognize the program). Resolving version mismatches requires firmware upgrades or project regeneration.

Hardware or Operational Factors: A damaged or poorly connected memory card can also cause reading failures. Ensure the card is not write-protected; otherwise, while the CPU can read the program, TIA Portal will reject writes (write protection does not cause a blank card but prevents program updates).

Note: According to Siemens official manuals, an “empty memory card” lacks the user program job file (S7_JOB.S7S) and project data folder (SIMATIC.S7S). When detecting an empty card, the S7-1500 CPU will attempt to copy its internal load memory contents to the card (and clear the internal memory) by default or remain unchanged if automatic copying is prohibited. If the CPU also lacks a program, inserting an empty card will leave it without a user program to run, necessitating normal downloads or offline programming as described.

III. Methods to Confirm Valid Program on Memory Card

To ensure the memory card contains a valid PLC program, verify the following:

Check Memory Card File Structure: Use Windows Explorer to open the memory card drive via the reader and check for the presence of the S7_JOB.S7S file and “SIMATIC.S7S” folder in the root directory. The S7_JOB.S7S file contains job instructions for CPU startup, while the “SIMATIC.S7S” folder holds compiled STEP 7 program block data (OBs, DBs, etc.). These files are essential indicators of successful TIA Portal programming; their absence indicates an unsuccessful write.

TIA Portal Property Check: Right-click the identified memory card drive in the TIA Portal project tree (e.g., “(F:) SIMATIC MC [Program]”) and select “Properties” to open the “Memory Card” dialog. Confirm the card type is “Program,” the file system is FAT32, and the used/available storage capacity matches the project size. For example, a 4MB card may show increased usage after programming. If the card remains blank or capacity is unchanged, the write operation likely failed, requiring a retry.

In TIA Portal, viewing SIMATIC memory card properties reveals the card type as “Program” and the file system as FAT32. If a project has been written, the card’s capacity usage should increase accordingly.

CPU Display and Status: Insert the card into the CPU and power it on. Observe the CPU display and indicator lights. Normally, the CPU should recognize the card as a “Program Card” and enter RUN mode. If it displays “Empty card” or remains in STOP mode, the program did not load successfully. Check the CPU panel’s “Memory Card Information” for project name/version (if available) to confirm CPU recognition.

Verify Operational Effect: Finally, observe the CPU’s RUN mode and controller behavior to indirectly confirm program loading. For example, if the program contains startup OBs or output logic, check the corresponding output states after power-on or use TIA Portal’s online monitoring (if connected) to verify CPU program blocks match the offline project.

Tip: SIMATIC memory card program data is encrypted and cannot be directly identified from file contents. However, file existence and structural integrity are sufficient to confirm successful programming. Always safely eject the memory card after writing to prevent incomplete writes or file corruption.

empty card

IV. Memory Card Recovery and Reprogramming Methods

If the memory card is still recognized as blank after insertion into the CPU, take the following steps to restore functionality:

Format via CPU Display: Switch the CPU to STOP mode and access the “Format Memory Card” function in the CPU’s LCD menu (usually under “Functions”). Confirm execution to clear all user data and rebuild the necessary system file structure. This method requires no additional software and is suitable for quick on-site card clearing. After formatting, the display should indicate card initialization.

Format via TIA Portal: Connect to the target CPU in TIA Portal (or via “Accessible Devices”) and open the “Online & Diagnostics” window. Navigate to “Functions > Format Memory Card,” click “Format,” and confirm. This restores the card to factory-blank status (retaining essential hidden files). After formatting, reprogram the card following the correct offline process.

Manual Cleanup via PC Reader: Insert the card into the reader and connect it to the computer. Open the card drive in Windows Explorer and delete the S7_JOB.S7S file and “SIMATIC.S7S” folder (and any other folders like DataLogs, Recipes, if present). Note: Do not format or delete invisible system hidden files (e.g., “LOG,” “crdinfo.bin”). After manual cleanup, the card becomes blank and can be reprogrammed via TIA Portal.

After any recovery step, reprogram the project data onto the memory card following the correct offline process. Ensure no old project residues remain on the card to prevent confusion with new data. If the card is suspected to be faulty (e.g., physical damage or end-of-life from repeated writes), replace it with a new SIMATIC memory card.

V. Siemens Official Guidelines on Programming Operations and Recognition Rules

Siemens provides detailed official documentation on SIMATIC memory card usage:

TIA Portal Offline Programming Process Guide: Siemens Industrial Support Center’s FAQ (Document ID 48711409) explains how to generate and store project data on S7-1200/1500 memory cards for offline program transfer to the CPU. It covers three methods: using a card reader, USB drive, or local folder, and describes the resulting file structure (including S7_JOB.S7S and SIMATIC.S7S).

Memory Card (Program Card) Usage Rules: The S7-1500 series user manual outlines memory card behavior as load memory (program card). For example, inserting a program card prompts the CPU to replace its internal program with the card’s program at startup and requires the card to remain in the CPU as external load memory. Removing the program card during operation stops the CPU and triggers an error due to the missing program. Regarding empty cards, the manual states that if an empty card is detected and automatic copying is not prohibited, the CPU copies its internal program to the card at power-on, then clears the internal memory. The CPU must then start from the card. These mechanisms govern how the S7-1500 determines if a memory card contains valid programs and takes appropriate actions.

Posted on

Siemens G120C Inverter F30004 Fault: Analysis and Troubleshooting Strategies


1. Fault Definition and Background

The “F30004” fault is a common error code in the SINAMICS G120C series of Siemens inverters. It indicates:

  • Power unit: Overtemperature heatsink AC inverter

In other words, the temperature of the power module’s heatsink has exceeded the permissible threshold. When the heatsink temperature reaches a warning level (typically around 5°C below the fault threshold), the inverter will raise an alarm (A05000). If the temperature continues to rise, it will escalate into fault F30004, leading to an immediate shutdown.

FAULT 0.F30004

2. Possible Causes of F30004

Based on official documentation and field experience, the core causes of F30004 can be categorized as:

  1. Cooling Fan Failure
    • Internal fans may become jammed, damaged, or run at reduced speed, preventing effective heat dissipation.
  2. Blocked or Poor Heatsink Ventilation
    • Dust accumulation or airflow obstruction can significantly reduce the cooling capacity of the heatsink.
  3. High Ambient Temperature
    • According to the manual, the intake air temperature for air-cooled drives should not exceed 42°C. Exceeding this temperature will increase thermal stress.
  4. Overload or High System Load
    • The drive may be continuously running at high torque or with excessive mechanical load, leading to heat buildup in the power module.
  5. Excessively High Pulse Frequency (Switching Frequency)
    • While high switching frequency improves output wave quality, it also increases internal power loss and heating.
  6. Sensor or Parameter Issues
    • Although rare, a malfunctioning temperature sensor or incorrect settings may lead to false overheating detection.

G120C

3. Diagnostic Steps for F30004

Upon encountering an F30004 fault, follow this step-by-step diagnostic procedure:

1. Check for Preceding Warnings

Use the BOP/IOP panel or engineering software to check if warning A05000 appeared before the F30004 fault. This can confirm if the fault was due to gradual overheating rather than an instant anomaly.

2. Inspect the Cooling Fan

  • Listen for fan noise or visually inspect fan rotation.
  • Remove the fan to check for blockages or dust.
  • Replace the fan module if it shows signs of failure or aging.

3. Evaluate Ambient and Ventilation Conditions

  • Measure the internal cabinet or intake air temperature.
  • Clean all dust and obstruction near the heatsink or vent path.
  • Improve ventilation or consider adding a cabinet cooling fan or air conditioning unit if needed.

4. Check Load Conditions

  • Verify whether the motor is running with excessive load or mechanical resistance.
  • Inspect parameter settings such as p0640 or p1341 (current limits).
  • If operating near thermal limits for extended periods, reduce load or increase cooldown intervals.

5. Reduce Pulse Frequency

  • Use parameter p1800 to lower the switching frequency.
  • Avoid unnecessarily high values that can accelerate heat generation.

6. Validate Temperature Sensor

  • Read diagnostic values such as r2124 and r0037.
  • Replace the sensor or disable overheating fault response if the sensor is faulty.

4. Solutions and Preventive Measures

4.1 Immediate Fixes

  • Let the inverter cool down before clearing the fault.
  • Verify all hardware and environmental factors before restarting.
  • Reset the fault using the control panel or via software tools.

4.2 Long-Term Prevention

  1. Routine Maintenance
    • Clean the inverter regularly, especially the heatsink, fan blades, and air filters.
  2. Temperature Monitoring and Thermal Management
    • Install a cabinet temperature sensor and configure automatic cooling triggers.
  3. Fan Replacement Strategy
    • Implement predictive maintenance based on fan usage hours or set a replacement schedule.
  4. Optimize Load and Parameters
    • Avoid long-term high torque operations.
    • Set appropriate acceleration/deceleration times.
  5. Adjust Switching Frequency Wisely
    • Do not set p1800 too high unless required by motor or application.
  6. Configure Redundant Monitoring (if applicable)
    • Some models support backup temperature detection or allow disabling fault response under certain safety-controlled conditions.

6SL3210-1KE28-4UB1

5. Conclusion and Insights

The F30004 fault in SINAMICS G120C is essentially a protective shutdown triggered by thermal overload. It’s often the result of long-term thermal stress rather than sudden failure. The key principles in addressing it are:

  • Diagnose Systematically: Start from fan, environment, load, parameters, and sensors.
  • Recover Cautiously: Clear the fault only after ensuring proper cooling and safe conditions.
  • Prevent Proactively: Use regular maintenance, parameter tuning, and environmental control.

Unlike faults caused by short circuits or ground failures, thermal faults may seem benign at first, but repeated F30004 events can severely degrade inverter life or lead to power module damage. Preventive measures and automated monitoring are essential to ensure long-term reliable operation.


6. Additional Recommendations

  1. Install a temperature probe in the cabinet to monitor in real-time;
  2. Activate pre-warning thresholds to raise an alarm before reaching F30004;
  3. Monitor for F30035 (intake overtemperature) as it often occurs alongside F30004;
  4. Entrust trained professionals to replace internal fans or disassemble power modules.

This in-depth analysis of fault code F30004 aims to help users not only resolve current errors but also establish best practices in long-term inverter maintenance. For advanced technical assistance, consult Siemens’ certified support service.


Posted on

Siemens SIMODRIVE 611 Module Overview: Functions, Wiring, Parameter Settings, Commissioning, and Maintenance Tips


Siemens SIMODRIVE 611 is a modular, high-performance servo/spindle drive system widely used in CNC machines, automated production lines, high-speed machining centers, and other industrial applications. The system comprises a power module (rectifier/regenerative unit), drive modules (UM/FM), and control interface units, forming a complete motion control solution.

This article provides a comprehensive analysis of the SIMODRIVE 611 system, covering its functional description, standard wiring methods, parameter setting and commissioning steps, common fault diagnosis, and practical maintenance tips.


SIMODRIVE 611

I. Functional Overview of SIMODRIVE 611 System

1. Power Module (E/R Module)

  • Model example: 6SN1146-1BB00-0EA1, a rectifier + regenerative feedback module.
  • Main function: Converts 3-phase AC power (380V480V) into DC link voltage (typically 540V600V DC), and feeds back braking energy to the grid during motor deceleration.
  • Features fault indication lights (RED/GREEN/YELLOW), supports pre-charging, DC discharge, and electronic monitoring.

2. Drive Modules

  • Includes UM (Universal Module) and FM (Spindle Module).
  • Responsible for controlling the motion of servo/spindle motors, including speed, torque, and position regulation.

3. Control Interface Modules

  • Provide signal handling for PROFIBUS, analog I/O, power/enable feedback, encoder feedback, and more.

II. Wiring Methods and Interface Descriptions

1. Power Module Wiring

  • Input: 3-phase AC supply 3AC 380~480V
  • Output: DC-Link voltage connected to drive modules
  • X111 terminal block wiring:
    • T48-112-9: Checks whether the DC bus is charged
    • T63-9 / T64-9: Controls power enable for the drive module
    • Terminals T74/T73: Startup signal status (Open/Closed determines power state)
    • T5.1 / T5.2 / T5.3: Motor over-temperature, braking resistor, and drive fault alarm inputs

2. Wiring Precautions

  • X181 port terminals NS1-NS2 must be shorted; otherwise, the system will not power up
  • Never connect wires while the module is powered on
  • Discharge circuits should be used to safely eliminate residual DC bus voltage

SIMODRIVE 611 Control Cabinet Internal Wiring Structure Diagram

III. Parameter Setting and Commissioning

SIMODRIVE 611 parameters are configured using Siemens’ SimoCom U software tool.

1. Required Tools

  • SimoCom U software (Windows compatible)
  • Communication cable (RS232 or USB-to-RS232 converter)
  • Connect to the module via X471 communication port

2. Parameter Setup Procedure

  1. Establish communication between PC and module
  2. Read the current parameter set
  3. Configure essential parameters:
    • Power module identification (Pn1)
    • Encoder type and feedback (Pn11~Pn13)
    • Current limits, acceleration/deceleration times (Pn30, Pn35, etc.)
    • Alarm thresholds (voltage, current, temperature)
  4. Save settings and reboot the system for changes to take effect

SIMODRIVE 611 System Structure Diagram

IV. Fault Diagnosis and Maintenance Tips

SIMODRIVE 611 features comprehensive fault diagnostics through LED indicators and signal terminals. Voltage and logic signal checks can quickly help pinpoint issues.

1. LED Status Indicators

  • RED: Electronic hardware fault (e.g., DC bus failure, power fault)
  • YELLOW: Pre-charging or module not ready
  • GREEN: System is operating normally

2. Common Fault Cases

Case 1: T48-112-9 Not Conducting

  • Symptom: DC bus voltage is only 27V after power-on, green LED is lit
  • Possible causes: NS1-NS2 on X181 not shorted, pre-charge failure, protection not cleared

Case 2: T63-9 / T64-9 Not Conducting

  • Symptom: Drive module inactive
  • Troubleshooting: Manually short T63-9 and T64-9; if no response, check control board or upstream enable signal

Case 3: Constant RED Light

  • Symptom: Module powered but no output
  • Troubleshooting: Verify terminal shorts, drive connections, and presence of critical alarm codes

3. Maintenance Tips

  • Diagnosis order: Check low-voltage logic terminals first (e.g., X111), then inspect if DC bus voltage is established
  • Use a multimeter for voltage and continuity checks (especially at control terminals)
  • Use a T20 Torx screwdriver to disassemble modules—avoid using incorrect tools
  • Wait at least 5 minutes after power-off before performing any service work due to high residual voltage

V. Conclusion

SIMODRIVE 611 is a robust and well-designed industrial drive system. Its power modules not only rectify three-phase AC to DC but also provide regenerative feedback capability, making it highly efficient. For optimal performance and safe maintenance, correct parameter configuration, proper wiring, and methodical troubleshooting are essential.

This article aims to provide engineers and maintenance personnel with a complete overview of SIMODRIVE 611’s operation and diagnostics. For advanced customization or onsite support, please consult Siemens-certified service providers or original factory support.

Posted on

Interpretation and Solutions for SINAMICS G120 Fault Code F30001 (Overcurrent)


1. Introduction

The SINAMICS G120 frequency converter series by Siemens is widely used in industrial automation for its modular structure, flexible control modes, and robust diagnostics. However, during operation, users may occasionally encounter fault codes such as F30001, which can interrupt production or system functionality. This article provides an in-depth explanation of the F30001: Power Unit Overcurrent fault, covering its causes, field-level troubleshooting, internal repair tips, and preventive strategies.


SINAMICS G120

2. Meaning of Fault Code F30001

Definition

F30001 refers to a severe fault in the power module:

“Overcurrent detected by power unit. Output is shut off immediately to protect internal components.”

This is a protective measure triggered when the output current exceeds the safe limit of the power module (typically IGBT modules), preventing hardware damage.


Internal Detection Mechanism

The converter continuously monitors the output current of each phase (U, V, W). The fault is triggered under these conditions:

  • Phase current exceeds the hardware threshold.
  • Significant imbalance between the output phases.
  • Motor stall or sudden torque demands exceed current capacity.
  • Control loop errors cause false current surges.

Diagnostic parameter r0949 can be used to identify the affected phase (0=unknown, 1=U, 2=V, 3=W, 4=DC bus current).


SINAMICS G120

3. Common Causes of F30001

A. Load-Side Problems

  • Motor winding short circuit or insulation breakdown.
  • Damaged or incorrectly connected output cables.
  • Motor blocked, causing high inrush current.
  • Converter powered on without connecting a load (not supported in some configurations).

B. Parameter Misconfiguration

  • Acceleration/deceleration time too short (p1120/p1121).
  • Incorrect motor parameters (p0300, p0310) lead to wrong current ratings.
  • Overcurrent response time (e.g. p0974) set too aggressively.

C. Power Supply Issues

  • Unstable or unbalanced 3-phase input.
  • Contactors dropping voltage momentarily.
  • Absence of line reactors leading to high inrush current.

D. Internal Hardware Failures

  • Damaged IGBT power modules.
  • Current sensing circuitry failure.
  • Loose connections or dry solder joints on the driver board.

F30001

4. On-Site Troubleshooting and Recommendations

Step 1: Basic Electrical Checks

  • Use an insulation tester to verify that motor windings have no shorts to ground (usually >1MΩ).
  • Inspect cables for mechanical damage, aging, or moisture.
  • Verify correct wiring (star or delta) per motor nameplate.

Step 2: Optimize Control Parameters

  • Extend acceleration time (p1120) to 5–10 seconds.
  • Correct the motor’s rated current value (p0310).
  • Perform motor identification (p1910 = 1) before first start-up.
  • Avoid no-load testing on some modules.

Step 3: Reset and Re-Test

  • Clear the fault on the operator panel or through fieldbus.
  • Re-energize and monitor output behavior.
  • If fault reoccurs, move to deeper diagnostics.

5. Internal Hardware Inspection (For Qualified Personnel Only)

⚠️ WARNING: Wait at least 5 minutes after power-off to allow DC bus capacitors to discharge.

Disassembly & Inspection:

  • Open the PM240 cover and check for signs of damage or burn marks.
  • Measure resistance between U/V/W and DC terminals to detect IGBT short circuits.
  • Visually inspect drive board connectors and test points for cold joints or oxidation.
  • If possible, swap power modules or control boards for cross-verification.

6. Preventive Maintenance Tips

TaskFrequency
Clean dust and ventsMonthly
Tighten terminal connectionsQuarterly
Check cable insulationSemi-annually
Monitor current values (r0051)Continuously
Configure tolerant protectionInitial setup

7. Conclusion

F30001 is a typical fault in SINAMICS G120 that stems from overcurrent events. With proper analysis, parameter optimization, and electrical inspection, most such issues can be resolved at the field level. Technicians must understand not only the electrical behavior of the load but also how the inverter monitors and reacts to current flow.

If the issue persists after external causes are ruled out, contacting our technical support or replacing the power module may be necessary to ensure safety and long-term reliability.


Posted on

User Guide for Siemens V20 Frequency Converter Based on the User Manual

Operation Panel Function Introduction

The Basic Operation Panel (BOP) of the Siemens V20 frequency converter serves as the primary interface for user interaction, integrating multiple critical functions. It provides real-time monitoring of key parameters including operating frequency, output current, and DC bus voltage, displayed on a high-brightness LED screen with two-line readability up to 1.5 meters. The membrane keypad design includes six functional keys:

  • OFF1 Stop Key: Initiates ramp stop by single press, decelerating the motor to stop according to preset deceleration time (P1121).
  • Start/Reverse Key: Controls motor start/stop in manual mode, with long-press (2 seconds) for direction reversal.
  • Multi-Function Key (M): Navigates menus, confirms parameter edits, switches display screens, and initiates bit editing when combined with OK key.
  • OK Key: Enables mode switching, rapid parameter confirmation, and password entry (long-press for 3 seconds).
  • Direction Keys: Traverses menu hierarchy, adjusts parameter values, and fine-tunes frequency settings; scrolls fault history in alarm state.
  • Fault Reset Key: Integrated with OK key functions through combination operations.

The panel adopts a three-level menu structure with four main modules: Operation Status, Parameter List, Fault Records, and System Settings. In parameter editing mode, bit-by-bit modification is supported with rapid saving via OK key. Notably, the BOP supports offline parameter backup through dedicated interfaces.

Parameter Initialization and Security Settings

Parameter Initialization Procedure

V20

The Quick Commissioning function enables parameter reset and basic configuration:

  1. Enter P0010=1 commissioning mode
  2. Configure motor parameters (P0304-P0311)
  3. Select connection macro (Cn001 for terminal control or Cn002 for communication control)
  4. Set application macro (e.g., P1300=20 for fan/pump loads)
  5. Execute P3900=1 to complete calculations

This process automatically configures over 20 core parameters including ramp functions and overload protection, reducing commissioning time by 60% compared to traditional methods.

Access Control Mechanism

The V20 converter employs a hierarchical access management system:

  • Access Level (P0003): Five levels from 0 (user-defined) to 4 (service)
  • Parameter Group Locking: Restricts accessible parameter groups via P0004
  • Password Protection: 4-digit password required for critical parameter modifications at expert level (3)

To remove password protection, downgrade P0003 to level 2 or below, or reset via service interface using specialized tools. Access restrictions can be applied to individual parameters, such as allowing P1080 (minimum frequency) adjustments while blocking P1120 (acceleration time) modifications.

External Control Implementation

Forward/Reverse Terminal Control

Utilizing digital input terminals (DI1-DI4) for direction control:

  1. Wiring Configuration: Connect DI1 for forward command (24VDC) and DI2 for reverse command
  2. Parameter Settings:
    • P0701=1 (DI1 as ON/OFF1 command)
    • P0702=2 (DI2 as reverse command)
    • P0700=2 (command source set to terminal control)
    • P1000=3 (frequency source set to analog input)

This configuration supports pulse commands for forward/reverse operations, automatically executing deceleration-stop-reverse acceleration sequence to prevent mechanical shocks.

Potentiometer Speed Control

Implementing analog input terminal (AI1) for stepless speed regulation:

  1. Wiring Requirements: Connect 10kΩ linear potentiometer with mid-tap to AI1 (10V power supplied by converter)
  2. Parameter Configuration:
    • P0756=2 (AI1 set to 0-10V voltage input)
    • P1000=2 (frequency source set to analog input)
    • P1080=5Hz (minimum frequency)
    • P1082=50Hz (maximum frequency)
    • P0759=0 (zero calibration)
    • P0760=100% (full-scale calibration)

Input filtering time (P0771) is recommended at 50ms to suppress interference pulses from contactor operations.

V20

Fault Diagnosis and Resolution

Typical Fault Code Reference

Fault CodeDescriptionPossible CausesSolutions
F1OvercurrentMotor cable short, short acceleration timeCheck insulation, extend P1120
F3UndervoltagePower supply fluctuation, braking resistor shortVerify power quality, check R0001 resistor
F4Converter OverheatPoor ventilation, high pulse frequencyClean air ducts, reduce P1800 carrier frequency
F12Temp Sensor FaultTemperature detection circuit openCheck T1/T2 terminal connections
F54Motor I²t OverloadProlonged overload operationReduce load, adjust P610 thermal time constant
F79Motor StallMechanical jamming, sudden load changeCheck transmission, optimize P1237 stall detection time

Systematic Fault Handling

  1. Fault Verification: Check current fault code and timestamp via BOP
  2. Parameter Backup: Execute P0971=1 to prevent data loss during troubleshooting
  3. Root Cause Analysis:
    • Electrical Issues: Measure terminal resistance (phase-to-phase insulation >1MΩ)
    • Mechanical Issues: Verify coupling alignment (allowable deviation <0.05mm)
    • Parameter Anomalies: Compare with P0005 parameter change history
  4. Recovery Procedure:
    • Temporary Fix: Restore factory settings via P0970=1 (after backup)
    • Permanent Repair: Replace components or optimize control logic per fault code guidance

Maintenance and Optimization Recommendations

  1. Preventive Maintenance:
    • Clean cooling fans every 2000 operating hours
    • Calibrate potentiometer linearity quarterly (error <2%)
    • Perform insulation resistance test annually (≥1MΩ@500VDC)
  2. Energy Efficiency:
    • Enable P1300=20 fan/pump macro for automatic V/f² characteristic
    • Match P1120/P1121 ramp times with load inertia
    • Activate P3300=1 energy-saving mode for automatic frequency reduction at no-load
  3. Communication Expansion:
    • Enable USS protocol via P2010[0]=1
    • Configure P2011=9.6kbps baud rate
    • Set Modbus address mapping using P2021-P2024

This guide is based on V20 firmware version V4.7.16. Always refer to the manual corresponding to your device’s firmware version. Execute parameter backup via P0971=1 before critical modifications and manage versions with P0970=2. For complex applications, use STARTER tool for offline programming and online monitoring.

Posted on

 Comprehensive Guide to Completely Uninstalling and Reinstalling Siemens TIA Portal: From Residual Cleanup to System Stability Restoration

1. Introduction & Scope

Siemens TIA Portal (V13–V19) leaves deep system traces during installation, including MSI product codes, Windows services, and drivers. Incomplete uninstallation causes version conflicts, GUID errors, and hardware issues (e.g., Code 19/45 for keyboards). This guide provides a fully automated, step-by-step solution to resolve these issues, covering:

  • Deep component removal (programs, drivers, services, registry)
  • Hardware error repair (Upper/Lower Filters)
  • Pre/post-installation checks (media validation, license recovery)
  • System health restoration (DISM/SFC/BCDEdit)
  • Rollback scripts and error lookup tables

2. Pre-Uninstallation Preparation

2.1 Backup Critical Data

  • Projects: Archive via TIA Portal’s “Archive” function (.zap13/14 files).
  • Licenses: Export via Siemens Automation License Manager (ALM) to USB.

2.2 Tool List

ToolPurposeSource
TIA AdministratorUninstall same-version packagesTIA installation media
CleanUpToolOfficial deep-clean scriptSiemens FAQ #109482460
Revo UninstallerAdvanced residual scanningrevouninstaller.com
PnPUtil/DevManViewRemove orphaned driversWindows ADK

3. Official Uninstallation Tools

3.1 TIA Administrator

  1. Open Siemens.TiaAdmin.msi from installation media.
  2. Filter “Installed” packages → Select TIA Portal version → Uninstall → Reboot.

3.2 CleanUpTool

  1. Download CleanUp_TIA_Vxx.exe from Siemens FAQ.
  2. Run as admin → Select target version → Reboot after completion.

4. PowerShell Script for Batch Uninstallation

powershell# C:\Cleanup_TIA_All.ps1$patterns = '*Totally Integrated Automation Portal*', '*SIMATIC*', '*TIA Admin*', '*PLCSIM*', '*WinCC*'$regPaths = 'HKLM:\SOFTWARE\Microsoft\Windows\CurrentVersion\Uninstall', 'HKLM:\SOFTWARE\WOW6432Node\...\Uninstall' $apps = foreach ($path in $regPaths) {  Get-ChildItem $path | ForEach-Object {    $displayName = (Get-ItemProperty $_.PSPath).DisplayName    if ($displayName -like $patterns) { $_ }  }} $apps | ForEach-Object {  Start-Process msiexec.exe -ArgumentList "/x $($_.PSChildName) /qn /norestart" -Wait}

Execution:

powershellSet-ExecutionPolicy Bypass -Scope Process -Force& C:\Cleanup_TIA_All.ps1

Reboot required after script completion.

5. Graphical Tools (Revo/Uninstall Tool)

  • Revo Uninstaller:
    1. “Forced Uninstall” → Search “Totally Integrated Automation” → Delete all residues.
  • Uninstall Tool:
    1. “Batch Mode” → Select Siemens software → “Deep Clean”.

6. Cleanup Legacy Drivers/Services/Registry

6.1 Remove Siemens Services

batchsc query type= service | findstr /I "Siemens SIMATIC TIA" > svc.txtfor /f %%s in (svc.txt) do (  sc stop %%s  sc delete %%s)

6.2 Fix Code 19/45 Keyboard Errors

  1. Open regedit → Navigate to:HKLM\SYSTEM\CurrentControlSet\Control\Class\{4D36E96B-E325-11CE-BFC1-08002BE10318}
  2. Delete UpperFilters/LowerFilters → Create a new multi-string value UpperFilters with kbdclass.

6.3 Remove Zombie Drivers

batchpnputil /enum-devices /problem > zombie.txtfor /f "skip=2 tokens=1,*" %%i in ('find "Problem" ^< zombie.txt') do (  pnputil /remove-device %%i /subtree /reboot)

7. System Health Check

batchdism /online /cleanup-image /restorehealth  # Repair component storesfc /scannow                                # Validate system filesbcdedit /enum {current}                     # Check for safeboot flags

To revert safeboot:

batchbcdedit /deletevalue {default} safebootbcdedit /deletevalue {default} safebootalternateshell

8. Reinstallation Guide

8.1 Media Validation

  • Verify ISO integrity via SHA-256 checksum or use Siemens MediaCreator.

8.2 Silent Installation

batchStart.exe /isolog:"C:\TIAinstall.log" /silent

Check C:\ProgramData\Siemens\Automation\Logs\Setup.log for errors.

8.3 Reboot Nodes

StepReboot Required?Notes
After CleanUpToolFree locked DLLs
Post-PowerShell scriptWindows Installer requirement
After STEP 7/WinCC/PLCSIMRegister drivers

9. Troubleshooting Guide

IssueRoot CauseFix
“Detected older version”Residual GUIDsRun PowerShell script
Keyboard Code 19/45Corrupted filtersRebuild UpperFilters
OPC UA Service failureLingering trace servicesDelete services + reinstall
CleanUpTool “reboot required”Pending uninstallsRestart

10. Automation & Best Practices

  • Package scripts (PowerShell, service cleanup, .reg fixes) into a Git repo.
  • Deploy via MDT/Intune for enterprise automation.
  • Reduce reinstall time from 4 hours to 30 minutes.

Final Note: This guide synthesizes official documentation, field testing, and community fixes to eliminate TIA Portal reinstallation headaches. Always test scripts in a non-production environment first!

Posted on

In-depth Analysis and Practical Maintenance Guide for F30022 and A7852 Faults in Siemens SINAMICS G120L Inverter


Abstract
This article systematically examines a field case involving the co-occurrence of F30022 (Power Unit U_ce Monitoring Fault) and A7852 (External Alarm 3) in a G120L inverter used in a 315 kW water pump application. It delves into the fault mechanisms, provides a detailed eight-step troubleshooting process, outlines testing methods and replacement techniques for commonly damaged components, and summarizes five preventive maintenance points based on maintenance statistics.

sinamics g120l 
6sl3310-1ce36-6aa0

I. Fault Phenomena and Code Interpretation

Fault Code F30022: Power Module U_ce Monitoring Triggered

Definition: The power unit continuously monitors the collector-emitter voltage (U_ce) during IGBT conduction. If an abnormal voltage waveform is detected, a hard fault is triggered, and the pulses are locked out.

Common Causes:

  • Output phase-to-phase or phase-to-ground short circuits or motor winding breakdown.
  • IGBT module internal breakdown (due to overheating, aging, or surge impacts).
  • Loss of 24 V power supply to the gate drive or blown fuses on the circuit board.
  • Interruption of the fiber-optic link between the Control Unit (CU) and Power Module (PM), leading to sampling loss.
  • Improper system grounding, causing harmonic currents to return through the PE line and elevate the sampling ground potential.
FAULTS 0.F30022

Alarm Code A7852: External Alarm 3

Definition: A digital input is mapped via parameter p2117. When its status meets the trigger condition, the alarm is set. This does not shut down the power but only indicates an external interlock anomaly.

Typical Trigger Sources:

  • Closure of fire/emergency stop circuits.
  • Faults in cooling water pressure, oil station pressure, or PLC outputs.
  • Loose terminals or poor shielding grounding leading to interference pulses.

When F30022 and A7852 occur simultaneously, it often indicates hardware defects in the power stage and an alarm state in the field interlock, requiring separate handling.

II. Eight-Step Systematic Troubleshooting Process

StepOperation PointsPurpose and Acceptance Criteria
1Power-off insulation test: Measure U/V/W→PE with a 500 V megohmmeter (≥ 5 MΩ)Determine if motor/cable insulation is degraded
2Phase-to-phase short circuit test: Remove motor terminals and measure U-V/V-W/U-W resistance (should equal rated value)0 Ω indicates winding short circuit
3IGBT diode measurement: Use a multimeter’s diode mode to measure forward and reverseBidirectional 0 Ω indicates module breakdown
4Drive board 24 V verification: Check 24 V and 15 V supplies on the gate drive boardLack of power supply may falsely trigger F30022
5Fiber-optic link self-test: Check Rx/Tx indicators on CU and PM ends (should be constantly lit)Dim or flickering lights indicate link interruption
6Resolve A7852: View p2117 corresponding DI, short-circuit/disconnect to verifyConfirm the true source of the external alarm
7No-load test run: Remove U/V/W and power upIf F30022 does not reoccur, the problem is on the motor side
8Load retest: After replacing/repairing components, reconnect the motor for test runr0947 shows no faults, and operation is stable

III. Practical Maintenance Case

Device Overview: G120L-315 kW + CU240E-2PN control unit driving a circulating water pump. First occurrence of F30022 + A7852 after 5 years of operation.

Initial On-site Screening: Megohmmeter reading of only 0.2 MΩ indicates insulation breakdown. Line-to-line resistance measurement of U-V at 0.3 Ω (should be 0.75 Ω) confirms motor short circuit.

Power Module Inspection: U-arm IGBT measures bidirectional 0 Ω, indicating hard breakdown. The same-side drive board’s 24 V fuse is blown.

Component Replacement: Replace 2×1700 C-rated IGBTs, rewire, replace the fuse, and clean the cooling channel.

Fiber-optic Reset: Re-plug the CU-PM POF; indicators return to a constantly lit state.

External Alarm Handling: p2117=1101, corresponding to DI4. Found that the fire interlock test line was not reset → restored, and A7852 disappeared.

Test Run and Delivery: First, a no-load test run, followed by a 50 Hz full-load test run for 1 hour. No alarms occurred; delivered to production.

FAULTS 0.A7852

IV. Component Prices and Typical Labor Hours Reference

ItemPrice (CNY)Labor Hours (h)Notes
1700 C IGBT module ×211,800 ×2Original parts
POF fiber-optic docking kit2602 m
24 V fuse + terminals120
Maintenance labor16 ×350 = 5,600Includes disassembly, testing, debugging
Insulating materials/thermal maintenance500Cleaning + painting
Total≈30,00016Completed within two working days

V. Five Key Points for Preventive Maintenance

  1. Online Insulation Monitoring: Install an IDAX-M to issue an early warning when insulation drops below 2 MΩ.
  2. Quarterly Thermal Cleaning: Use compressed air to blow out air ducts and check r0035 temperature rise. Immediately address any rise >10 K.
  3. Standardized Power-Up Sequence: Turn on the main circuit first, followed by the 24 V control power supply to avoid false alarms due to premature power-up of the drive board.
  4. Layered External Alarms: Digest external alarm signals within the PLC and connect only the total OK contact to the drive to reduce false stops.
  5. Surge and Harmonic Suppression: Install a 690 VAC SPD + 3% reactor at the incoming line to reduce dv/dt impacts on the IGBTs.

VI. Conclusion

F30022 represents a “red alert” at the power stage level, while A7852 serves as a “yellow light” at the system level. When both codes occur simultaneously, it is essential to investigate both hardware and external interlocks. Through structured eight-step troubleshooting, rigorous component testing, replacement, and debugging, production can be restored for a 315 kW water pump within 48 hours. By implementing preventive measures such as insulation monitoring, thermal cleaning, grounding optimization, and surge/harmonic suppression, the risk of similar shutdowns can be significantly reduced. It is hoped that the cases and methodologies presented in this article will provide practical assistance to on-site maintenance engineers and serve as a reference for equipment managers in formulating preventive maintenance plans.



Posted on

In-Depth Analysis of Alarms 1080 (Trace Data Save) in Siemens SINAMICS S120 Drives


1. Introduction

In modern industrial automation, Siemens SINAMICS S120 drives are widely employed across various applications such as CNC machine tools, textile machinery, printing presses, papermaking equipment, robotics, and other sectors demanding high dynamic performance and precision. SINAMICS S120 offers a modular design, advanced control capabilities, and a robust diagnostic system. When an abnormal condition occurs or when the drive simply wishes to notify the user of a particular state, it displays corresponding alarm or fault codes on the Basic Operator Panel (BOP), in the STARTER/TIA Portal software, or on an external HMI (Human-Machine Interface).

Among the many potential fault and alarm messages, Alarms 1080—often accompanied by the text “comp trace data save”—commonly appears in actual usage. Some engineers or first-time users of S120 may misinterpret this alarm as a sign of major damage or serious malfunction. However, Alarms 1080 is typically an information-level or process-level alert, indicating that the drive is saving trace (data logging) information. It is neither a hardware breakdown nor a critical fault demanding immediate shutdown. Understanding and properly handling this alarm is important for maintaining the stability of the drive system and prolonging equipment life. This article will thoroughly explain Alarms 1080’s background, implications, and recommended actions.


alarms 1808

2. Definition and Background of Alarms 1080

2.1 Overview of the Trace Function

Siemens SINAMICS S120 includes a built-in Trace (data logging or “oscilloscope”) feature. This function records specified operating parameters or signals (e.g., current, speed, position feedback, torque commands) within the drive’s memory. When the Trace function is enabled—either manually by the user in the engineering software (STARTER or TIA Portal) or triggered automatically by certain system conditions—these signals are sampled at set intervals or in response to defined triggers. The sampled data is then stored in the drive’s internal memory or on a connected storage card (such as a CF card).

Once the sampling cycle or trigger condition is completed, the drive writes or finalizes the captured data. During this process, the drive issues a notification to indicate that it is actively saving data. This valuable dataset can later be analyzed to optimize control parameters or diagnose intermittent or complex errors.

2.2 What Alarms 1080 Signifies

When you see Alarms 1080 with a description along the lines of “comp trace data save” or “Trace data is being saved,” it specifically indicates that the drive is performing the data save operation for an active Trace task.

  • This message does not imply hardware damage or a system crash.
  • It is typically a “system event” or “user-level” notification that does not disrupt the drive’s primary function.

2.3 How It Differs from Fault Codes

Unlike “Fault” codes (e.g., F07802, F30003) prefixed with “F,” which usually shut down or block the drive until reset, an alarm such as Alarms 1080 does not force the drive into a faulted or disabled state. Serious faults typically demand manual acknowledgment or system logic to reset them; meanwhile, Alarms 1080 is more akin to an informational prompt. Once data saving completes and no other higher-level issues exist, the system will clear or deactivate the alarm automatically.


3. Common Causes and Scenarios

In practice, Alarms 1080 (“comp trace data save”) most often arises from these scenarios:

  1. Manually Enabled Trace During Commissioning
    In many cases, an engineer sets up a Trace task in STARTER, TIA Portal, or directly on the panel to diagnose specific motor or drive behavior. For example, if you want to observe speed-loop responses or current-waveform patterns, you configure sampling frequency, trigger conditions, and the signals to track. As soon as the sampling finishes, the drive writes the data to storage, resulting in Alarms 1080.
  2. Automatic Background Trace
    Some drive configurations automatically initiate the Trace function for advanced monitoring or “fault logging.” When the system detects certain threshold conditions or a fault event, the drive begins collecting data. Once the event is captured, it proceeds to save it, displaying Alarms 1080 in the process.
  3. Leftover Trace Settings
    In some projects, the Trace function was used at one point but never deactivated. Even after the main commissioning is done, the drive may still be periodically recording data and subsequently saving it, inadvertently causing recurring Alarms 1080 messages. Though typically benign, these messages might raise questions among less-experienced personnel.

S120 drives

4. Impact on System Operation

Because Alarms 1080 is an informational or process-level alert, it does not necessarily prevent normal drive operation or motor control, as long as there are no simultaneous major fault codes. However, keep in mind the following:

  1. Do Not Interrupt Power During Saving
    If the drive is in the middle of saving Trace data and power is lost or intentionally shut off, it may lead to incomplete data or, in rare cases, corruption of the storage medium. In general, it is best to avoid powering down the drive while Alarms 1080 is active unless absolutely necessary.
  2. Resource Consumption
    The Trace function may consume a portion of the drive’s internal resources, including CPU and memory. Although typically minimal, high sampling rates combined with large data sets can create significant overhead. If the user no longer needs Trace data, disabling it can free up resources.
  3. Parallel Occurrences with Faults
    If a severe drive fault (e.g., F07802 “Infeed Not Ready”) appears alongside Alarms 1080, the fault should take priority for troubleshooting. Alarms 1080 in that case merely indicates that trace data related to the fault was captured or saved, but it is not the cause of the fault itself.

5. Handling and Disabling Methods

When you see Alarms 1080 on the drive, and you confirm that a Trace save is in progress, you can use the following approaches to manage or eliminate it:

  1. Wait for the Save to Complete
    Typically, the drive only needs a short interval—ranging from a few seconds to maybe a minute—for large data sets—to store the captured Trace data. The alarm will then disappear on its own once the operation finishes.
  2. Deactivate or Remove Trace Tasks
    If data logging is no longer required, you can open the Trace or Recording screen in STARTER or TIA Portal, locate any active Trace configurations, and disable or delete them.
    • Certain drive operator panels (like BOP20) may also allow you to view or halt ongoing Trace recordings if the firmware supports it.
  3. Check Storage Space and Write Permissions
    Occasionally, if the alarm persists, the storage medium (internal memory or CF card) might be full, write-protected, or otherwise inaccessible. Ensure you have enough free space or switch to a larger-capacity CF card if needed.
  4. Reset Alarms If Needed
    Usually, purely informational alarms clear automatically without requiring a reset. However, if Alarms 1080 coincides with an actual Fault, you may need to perform a fault reset (via the panel or a higher-level controller) after addressing the underlying issue.

6. Common Questions and Answers

Q1: “Does the presence of Alarms 1080 mean the drive is damaged?”
A1: Not at all. Alarms 1080 almost always indicates that the drive is recording or saving Trace data, not that any component has malfunctioned. If no additional serious alarms or faults are active, the system can continue operating normally.

Q2: “Will repeatedly seeing Alarms 1080 negatively affect the system?”
A2: In most cases, no. It simply appears whenever trace-saving occurs. Unless you are sampling enormous volumes of data at high frequencies, system performance typically remains unaffected. If you do not need the Trace feature, consider disabling it to keep messages streamlined.

Q3: “How do I check Trace configurations or the storage location?”
A3: Within STARTER or TIA Portal, navigate to the corresponding drive object, and look for “Trace” or “Recording” in the function tree. There, you can view and edit active tracing tasks. On certain operator panels, you might find a Diagnostics → Trace Logs menu that shows ongoing traces and storage status.

Q4: “What else can the Trace function be used for?”
A4: Beyond fault diagnosis, the Trace feature is invaluable for capturing transient oscillations, optimizing control loops (like speed-loop gains or filter time constants), and logging multiple signals simultaneously. It helps improve control accuracy and pinpoint root causes of sporadic or short-lived anomalies.


7. Case Study

Consider a textile production line where an engineer needs to diagnose oscillations in the S120 drive. By enabling two Trace channels (one for current loop, one for speed loop) at a high sampling rate, the system collected large volumes of data. While saving these data sets, “Alarms 1080: comp trace data save” appeared repeatedly on the drive’s screen. Initially, on-site maintenance personnel feared a serious error; however, it quickly became clear that the drive was simply finalizing the recording.

Once the trace was stored, Alarms 1080 cleared by itself. Analyzing the newly captured data, the engineer discovered a PID tuning issue. By fine-tuning the relevant parameters, they significantly reduced mechanical vibration. This real-world experience illustrates how Alarms 1080 is part of a normal diagnostic workflow and can be harnessed for performance improvements rather than being an indication of a critical failure.


8. Conclusion

In summary, Alarms 1080 (“comp trace data save”) in the Siemens SINAMICS S120 drive primarily indicates the system is saving Trace data—a process-level or informational message rather than a hardware or software malfunction. Proper use of the Trace function can substantially enhance commissioning and fault diagnosis, making it possible to observe internal drive states and parameter changes in great detail. If you do not need data logging, you can disable or remove the trace configuration to prevent recurrent alarms.

If a severe fault (e.g., an “Fxxxx” code) accompanies Alarms 1080, prioritize investigating the fault itself. Ensure power and wiring integrity, confirm that no IGBT or module fault exists, and only then determine whether to proceed with or discontinue trace logging. But in the absence of critical errors, Alarms 1080 simply signals that the drive is working as intended to capture and save valuable diagnostic data.

By correctly recognizing Alarms 1080 and using it appropriately, maintenance and commissioning personnel can leverage the drive’s powerful built-in diagnostic capabilities without undue worry. This alarm can assist with targeted data capture, enabling users to optimize performance and quickly resolve intermittent failures. We hope this article clarifies the nature of Alarms 1080 in SINAMICS S120 and helps you confidently manage and benefit from its Trace functionality in real-world industrial scenarios.