Posted on

Anchuan G9300 Series Frequency Inverter User Manual: Usage Guide

Abstract

The Anchuan G9300 series frequency inverter is a high-performance vector inverter widely used in various industrial automation applications. This article will provide a detailed introduction to the operation panel functions, parameter settings, password management, external terminal control, and fault codes and their solutions for the G9300 series frequency inverter, helping users better understand and utilize this equipment.


G9300

1. Operation Panel Function Introduction

The operation panel of the Anchuan G9300 series frequency inverter is designed to be simple and functional, mainly consisting of the following parts:

  • Display Screen: Used to display current operating status, parameter settings, and other information.
  • Function Keys: Include PRG (Programming Key), ENTER (Confirm Key), SHIFT (Shift Key), RUN (Start Key), STOP/RST (Stop/Reset Key), and MF.K (Multi-Function Key).
  • Increment and Decrement Keys: Used to adjust parameter values or browse menus.

1.1 Restoring Factory Settings

Before using the G9300 series frequency inverter, it is usually necessary to restore the parameters to factory settings to ensure the device is in a known state. Here are the steps to restore factory settings:

  1. Enter Parameter Setting Mode: Press the PRG key to enter the first-level menu, then press the ENTER key to enter the second-level menu.
  2. Select Parameter Initialization Function: In the second-level menu, find the PP-01 (Parameter Initialization) function code.
  3. Restore Factory Parameters: Set PP-01 to 1, then press the ENTER key to confirm. At this point, all parameters of the frequency inverter will be restored to factory settings.

1.2 Setting and Removing Passwords

To protect parameter settings from being arbitrarily changed, the G9300 series frequency inverter provides a password protection function. Here are the steps to set and remove passwords:

  1. Setting a Password:
    • Enter the parameter setting mode and find the P7-11 (User Password) function code.
    • Set P7-11 to the desired password value (range 0~32766), then press the ENTER key to confirm.
  2. Removing a Password:
    • Enter the parameter setting mode and find the P7-11 function code.
    • Set P7-11 to 0, then press the ENTER key to confirm, and the password will be removed.

1.3 Parameter Access Restrictions

To further protect parameter settings, the G9300 series frequency inverter also provides a parameter locking function. Here are the steps to set parameter access restrictions:

  1. Locking Parameters:
    • Enter the parameter setting mode and find the PP-04 (Parameter Lock) function code.
    • Set PP-04 to 1, then press the ENTER key to confirm. At this point, all parameters will be locked and cannot be changed.
  2. Unlocking Parameters:
    • Enter the parameter setting mode and find the PP-04 function code.
    • Set PP-04 to 0, then press the ENTER key to confirm, and the parameter lock will be removed.

2. External Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The G9300 series frequency inverter supports forward/reverse control and potentiometer speed regulation through external terminals, making it very flexible and convenient in industrial automation control.

2.1 External Terminal Forward/Reverse Control

To achieve external terminal forward/reverse control, the following wiring and parameter settings are required:

  1. Wiring:
    • Connect the forward control signal to the DI1 terminal.
    • Connect the reverse control signal to the DI2 terminal.
    • Ensure the ground terminal (GND) is correctly connected.
  2. Parameter Settings:
    • Enter the parameter setting mode and find the P4-00 (DI1 Terminal Function Selection) and P4-01 (DI2 Terminal Function Selection) function codes.
    • Set P4-00 to 1 (Forward Operation), and P4-01 to 2 (Reverse Operation), then press the ENTER key to confirm.

2.2 External Potentiometer Speed Regulation

To achieve external potentiometer speed regulation, the following wiring and parameter settings are required:

  1. Wiring:
    • Connect the output of the potentiometer to the AI1 terminal.
    • Ensure the ground terminal (GND) is correctly connected.
  2. Parameter Settings:
    • Enter the parameter setting mode and find the P0-03 (Main Frequency Source A Selection) function code.
    • Set P0-03 to 4 (Keypad Potentiometer), then press the ENTER key to confirm.

3. Fault Codes and Their Solutions

During the use of the G9300 series frequency inverter, various faults may be encountered. Here are some common fault codes and their solutions:

Fault CodeFault DescriptionSolution
E001IGBT Short Circuit FaultCheck the IGBT module and its drive circuit, replace the IGBT module if necessary.
E002Acceleration OvercurrentCheck if the acceleration time setting is too short or if the load is too large, adjust the acceleration time or reduce the load.
E003Deceleration OvercurrentCheck if the deceleration time setting is too short or if the load is too large, adjust the deceleration time or reduce the load.
E004Constant Speed OvercurrentCheck if the load is too large or if the motor parameters are set correctly, reduce the load or reset the motor parameters.
E005Acceleration OvervoltageCheck if the acceleration time setting is too short or if the bus voltage is too high, adjust the acceleration time or check the bus voltage.
E006Deceleration OvervoltageCheck if the deceleration time setting is too short or if the bus voltage is too high, adjust the deceleration time or check the bus voltage.
E007Constant Speed OvervoltageCheck if the bus voltage is too high or if the load is too small, adjust the bus voltage or increase the load.
E008Stop OvervoltageCheck if the stop mode setting is correct or if the bus voltage is too high, adjust the stop mode or check the bus voltage.
E009UndervoltageCheck if the input voltage is normal or if the power line is in good contact, ensure the input voltage is stable.
E010Inverter OverloadCheck if the load is too large or if the heat dissipation is good, reduce the load or improve the heat dissipation conditions.
E011Motor OverloadCheck if the motor load is too large or if the heat dissipation is good, reduce the load or improve the heat dissipation conditions.
E012Input Phase LossCheck if the input power supply is missing a phase, ensure all three phases are normally powered.
E013Output Phase Loss or Three-Phase Output ImbalanceCheck if the output line is normal, ensure the three-phase output is balanced.
E014Module OverheatCheck if the heat sink is blocked or if the ambient temperature is too high, ensure good heat dissipation.
E015External FaultCheck if the external control line is normal, ensure the external control signal is correct.
E016Communication AbnormalityCheck if the communication line is normal or if the communication parameters are set correctly, ensure stable communication.
E017Motor Tuning AbnormalityCheck if the motor parameters are set correctly, re-perform motor tuning.
E018Parameter Read/Write AbnormalityCheck if the parameter settings are correct, reset the parameters.
E019Inverter Hardware AbnormalityCheck if the inverter hardware is normal, contact after-sales service if necessary.
E020Motor Ground Short CircuitCheck if the motor line is short-circuited, ensure the motor insulation is good.
E021AD Zero Drift Too LargeCheck if the analog input circuit is normal, contact after-sales service if necessary.
E022Inverter Hardware Abnormality (Clear Latch Timeout)Check if the inverter hardware is normal, contact after-sales service if necessary.
E023Motor Ground Short CircuitCheck if the motor line is short-circuited, ensure the motor insulation is good.
E024AD Zero Drift Too LargeCheck if the analog input circuit is normal, contact after-sales service if necessary.
E025User-Defined Fault 1Check if the setting of user-defined fault 1 is correct, ensure the logic is correct.
E026User-Defined Fault 2Check if the setting of user-defined fault 2 is correct, ensure the logic is correct.
E027Power-On Time ReachedCheck if the power-on time setting is correct, adjust the power-on time appropriately.
E028PID Feedback Disconnection FaultCheck if the PID feedback line is normal, ensure the feedback signal is stable.
E029PID Feedback Overlimit (Overvoltage) FaultCheck if the PID feedback signal is too large, adjust the PID parameters appropriately.
E030Keypad STOP Key Stop FaultCheck if the STOP key is normal, ensure the control logic is correct.
E031Hardware Current Limit TimeoutCheck if the current limit setting is correct or if the load is too large, adjust the current limit parameters or reduce the load.
E032Auto-Reset Count ExceededCheck if the auto-reset count setting is correct, adjust the reset count appropriately.

Standard Wiring Diagram for G9300

4. Conclusion

The Anchuan G9300 series frequency inverter is a powerful and high-performance industrial automation device. Through this article, users can better understand and use this equipment, including operation panel functions, parameter settings, password management, external terminal control, and fault codes and their solutions. In practical applications, users should perform parameter settings and fault troubleshooting according to specific needs to ensure the stable operation and high efficiency of the equipment.

It is hoped that this article can help users better master the usage methods of the Anchuan G9300 series frequency inverter and improve the efficiency and quality of industrial automation control.

Posted on

K-DRIVE KD600M Series Variable Frequency Drive User Manual Guide

Introduction

The K-DRIVE KD600M series variable frequency drive (VFD) is a powerful and versatile device designed for motor speed and torque control in various industrial applications. This guide, based on the K-DRIVE KD600M series user manual, provides a detailed overview of the operation panel functions, parameter initialization, password and parameter access restrictions, external terminal forward/reverse control and potentiometer speed adjustment, as well as common fault codes and their resolutions. By mastering these features, users can operate and maintain the VFD efficiently and safely, ensuring optimal performance across different scenarios.

KD600M-4T-2.2G

Operation Panel Functions

The KD600M series VFD’s operation panel is the central interface for user interaction, integrating intuitive buttons, LED indicators, and a 5-digit display for parameter settings, status monitoring, and motor control. Below are the key functionalities:

Buttons and Controls

The panel includes the following buttons:

  • PRG: Enters programming mode to access parameter menus.
  • ESC: Exits the current menu or cancels an operation.
  • OK: Confirms parameter settings or selections.
  • RUN: Starts motor operation.
  • STOP: Stops motor operation or resets faults.
  • QUICK: Quickly sets commonly used parameters.
  • JOG: Enters jog mode for testing or fine-tuning.
  • UP/DOWN: Adjusts parameter values or navigates menus.

For example, to adjust the frequency from 0.00Hz to 5.00Hz, users can press PRG to enter the parameter menu, use the UP/DOWN keys to select the target parameter (e.g., P1-04), input the new value, and press OK to confirm.

LED Indicators

The panel’s LED indicators provide real-time status feedback:

  • RUN: Green, on indicates running, off indicates stopped, flashing indicates sleep mode.
  • L/D/C: Red, off indicates panel control, on indicates terminal control, flashing indicates communication control.
  • FWD/REV: Red, off indicates forward, on indicates reverse, flashing indicates direction mismatch.
  • TUNE/TC: Red, on indicates torque control, flashing indicates tuning or a fault.

Display Screen

The 5-digit LED display shows frequency, current, voltage, fault codes, and other information. Hexadecimal values are prefixed with “H.” (e.g., P7-29 displays as “H.3f”). The display supports multi-level menu navigation (group → code → value), enabling quick access and modification of parameters.

Related Parameters

Key parameters related to operation panel functions include:

  • P7-00 (Jog Run Frequency): Range: 0.00Hz to maximum frequency; Factory default: 6.00Hz.
  • P7-01 (Jog Acceleration Time): Range: 0.0s to 3000.0s; Factory default: 10.0s.
  • P7-02 (Jog Deceleration Time): Range: 0.0s to 3000.0s; Factory default: 10.0s.
  • P7-28 (QUICK/JOG Key Function Selection): Options: 0 (forward jog), 1 (forward/reverse switch), 2 (reverse jog), 3 (panel/remote switch), 4 (panel frequency source switch); Factory default: 0.
  • P7-16 (Keyboard Knob Precision): Options: 0 (0.01Hz) to 10 (10Hz); Factory default: 2.

These features make the operation panel a powerful and flexible tool for various control needs.

Parameter Initialization

Parameter initialization is a critical step for restoring default settings or backing up user configurations. The KD600M series offers the following function codes:

P0-28 (Parameter Initialization)

  • Options:
    • 0: No operation
    • 1: Restore factory settings (excludes motor parameters, records, and P0-20)
    • 2: Clear records
    • 3: Back up user parameters
    • 4: Restore backed-up parameters
  • Factory Default: 0
  • Modifiable State: Running state (★)

To perform initialization, users should enter P0-28 while the device is stopped, set it to 1, and confirm. The VFD will revert to factory settings, preserving motor parameters and run records.

P0-29 (Parameter Upload/Download)

  • Options:
    • 0: No function
    • 1: Upload parameters
    • 2: Download parameters (excludes P4 and A1)
    • 3: Download parameters (includes P4 and A1)
    • 4: Download all parameters
    • 5-7: Download modified parameters
  • Factory Default: 0
  • Modifiable State: Stopped or running state (☆)

This function allows users to back up custom parameters or restore from a backup, suitable for multi-device configurations or fault recovery.

Password and Parameter Access Restrictions

To prevent unauthorized modifications, the KD600M series provides password protection and parameter access restrictions:

Password Protection

  • P7-49 (User Password):
    • Range: 0 to 65535
    • Factory Default: 0
  • PF.00 (Factory Password):
    • Range: 0 to 65535
    • Factory Default: ***** (hidden for security)

Users can enable password protection by setting P7-49. Fault codes like Err25 (EEPROM read/write failure) or Err1A (password entry limit exceeded) may indicate password-related issues, requiring EEPROM chip inspection or technical support.

Parameter Access Restrictions

  • B0-00 (Function Code Read-Only Selection):
    • 0: Invalid (no restriction)
    • 1: Read-only (parameters cannot be modified)
    • Factory Default: 0
  • Parameter Status:
    • : Not modifiable during operation (e.g., P0-03: motor control).
    • : Manufacturer-only modification.
    • : Read-only (e.g., PF group parameters).

These restrictions ensure the security of critical parameters, preventing accidental changes or unauthorized access.

External Terminal Forward/Reverse Control and Potentiometer Speed Adjustment

The KD600M series supports external terminal control for forward/reverse operation and potentiometer speed adjustment, ideal for automated systems.

Forward/Reverse Control

  • Digital Input Terminals (DI1-DI10):
    • DI1: Default forward (function code 1).
    • DI2: Default reverse (function code 2).
    • Supports PNP/NPN modes, switchable via DIP switches.
    • Up to 10 digital inputs with optional IO1/IO2 expansion cards.
  • P5-11 (Terminal Command Mode):
    • 0: Two-wire mode 1
    • 1: Two-wire mode 2
    • 2: Three-wire mode 1
    • 3: Three-wire mode 2
    • Factory Default: 0

Wiring Method:

  • Connect DI1 and DI2 to a PLC or switch, with the COM terminal as the common return.
  • Ensure secure connections to avoid short circuits or poor contact.

Potentiometer Speed Adjustment

  • Analog Input Terminals (AI1, AI2):
    • Supports 0-10V or 4-20mA input.
    • P5-15 (AI1 Minimum Input): Range: 0.00V to 10.00V; Corresponding setting: -100.0% to 100.0%.
    • P5-16 (AI1 Maximum Input): Range: 0.00V to 10.00V; Corresponding setting: -100.0% to 100.0%.
  • Wiring Method:
    • Use a 1-5kΩ potentiometer, connecting to AI1 and +10V-GND terminals (+10V provides up to 10mA power).
    • Recommended wiring length is less than 20 meters to minimize signal interference.

Setup Steps:

  1. Set P5-11 to 0 (two-wire mode 1) to enable terminal control.
  2. Configure P5-15 and P5-16 to define the potentiometer input range.
  3. Rotate the potentiometer and observe frequency changes on the display to ensure proper speed adjustment.

Common Fault Codes and Resolutions

The KD600M series manual lists various fault codes with corresponding resolution methods. Below are common faults and their troubleshooting steps:

Fault CodeFault NameResolution Method
Err01Inverter Module ProtectionCheck U, V, W terminals for shorts or grounding, inspect overheating, wiring, fans, and vents; contact support if unresolved.
Err04Acceleration OvercurrentCheck output circuit, motor parameters, acceleration time (P9-22), V/F gain, voltage, load, and VFD capacity; adjust parameters.
Err05Deceleration OvercurrentCheck output circuit, motor parameters, deceleration time (P9-23), voltage, load, brake unit/resistor, and flux gain; adjust parameters.
Err06Constant Speed OvercurrentCheck output circuit, motor parameters, voltage, load, and VFD capacity; adjust parameters.
Err08Acceleration OvervoltageCheck voltage, external force, acceleration time, brake unit/resistor, and motor parameters; adjust settings.
Err09Deceleration OvervoltageCheck voltage, external force, deceleration time, and brake unit/resistor; adjust settings.
Err10Constant Speed OvervoltageCheck voltage, external force, and resistor installation; adjust parameters.
Err12Undervoltage FaultCheck power stability, voltage range, bus voltage, rectifier, and drive/control board; reset or contact support.
Err13Drive OverloadReduce load, check motor condition, consider upgrading VFD.
Err14Motor OverloadAdjust P9-01 settings, check load and motor condition, upgrade VFD if needed.
Err15Drive OverheatingLower ambient temperature, clean vents, check fans and thermistor, replace module if necessary.
Err17Current Detection FaultCheck wiring, current devices, and main/control board; contact support.
Err20Ground Short CircuitCheck motor and cables for shorts, replace if needed; contact support.
Err23Input Phase LossCheck power supply, drive/lightning/main board; contact support.
Err24Output Phase LossCheck motor wires, output balance, drive/module; resolve fault or contact support.
Err25EEPROM Operation FailureCheck EEPROM chip, replace main board if necessary; contact support.
Err27Communication FaultCheck host, communication settings, and P8 group parameters; adjust wiring/parameters.
Err28External FaultCheck DI terminal input, reset fault.
Err29Speed Deviation ExcessiveExtend acceleration/deceleration time, reset P9-31/P9-32.
Err30/31User-Defined Fault 1/2Check DI terminal input, reset fault.
Err32PID Feedback LossCheck feedback signal, reset PA-13.
Err33Quick Current LimitReduce load, extend acceleration time, or upgrade VFD.
Err34Load Drop FaultReset or adjust P9-28 to P9-30 conditions.
Err35Input Power FaultAdjust voltage, extend power cycle.
Err37Parameter Storage AnomalyCheck DSP-EEPROM communication, replace main board if needed.
Err39Run Time ReachedCheck run time, reset if necessary.
Err40Cumulative Run Time ReachedCheck cumulative run time, reset.
Err42Motor Switching During RunEnsure correct motor switching procedure.
Err46Master-Slave Communication InterruptCheck master-slave communication connections.

General Fault Handling Steps

  1. Power Off Check: Disconnect the VFD power before addressing any fault to ensure safety.
  2. Refer to Manual: Consult the manual’s troubleshooting section for specific steps based on the fault code.
  3. Parameter Adjustment: Adjust relevant parameters (e.g., acceleration time P9-22, deceleration time P9-23) according to the fault cause.
  4. Reset: Use the STOP key or set P9-11 (auto-reset attempts, 0-20, default 0) and P9-13 (reset interval, 0.1s-100.0s, default 1.0s) to reset faults.
  5. Technical Support: Contact K-DRIVE technical support if the fault persists.
K-DRIVE KD600M

Conclusion

The K-DRIVE KD600M series VFD offers robust control capabilities through its intuitive operation panel, flexible parameter settings, and powerful external control features. By mastering the operation panel functions, parameter initialization, password protection, external terminal control, and fault resolution methods, users can ensure stable operation across various industrial scenarios. It is recommended to always refer to the user manual for detailed guidance and safety precautions to maximize the device’s performance and longevity.

Posted on

Comprehensive User Guide for Jintech JTE280 Series Variable Frequency Drive (VFD)

I. Control Panel Operations and Parameter Management

1. Panel Interface Fundamentals

The JTE280 features two panel configurations (Fig.4-1/4-2) with essential controls:

  • RUN: Start operation (requires P0.03=0)
  • REV/JOG: Reverse/Jog (configured via P3.52)
  • STOP/RESET: Halt/Reset faults
  • PRGM: Access parameters (5-sec hold locks keyboard)
  • ▲/▼: Adjust values (real-time speed adjustment)
  • <<: Toggle monitoring parameters (J-00~J-11)

2. Factory Reset Procedure

Execute through hierarchical menu:

graph TD
    A[Press PRGM] --> B[Locate P3.01]
    B --> C[Set tens-digit=1 for default]
    C --> D[Confirm with DATA]
    D --> E[Set tens-digit=2 to clear faults]

3. Security Configuration

  • Password Protection: Set P0.00 (0001-9999)
  • Access Levels (P3.01 units-digit):
  • 0: Full access
  • 1: Only P3.01 adjustable
  • 2: Only P0.02+P3.01 adjustable
  • Keyboard Lock: 5-sec PRGM hold

II. External Control Implementation

1. Terminal-Based Motor Control

Critical Parameters:

P0.03 = 1      ; Terminal control mode
P4.08 = 0      ; 2-wire control scheme 1

Wiring Specification:

  • Forward: FWD-DCM short
  • Reverse: REV-DCM short
  • Stop: Open circuit

2. External Potentiometer Configuration

Parameter Chain:

P0.01 = 0      ; Potentiometer mode
P1.01 = 1.00   ; VI gain default
P1.02 = 0.00V  ; Min voltage
P1.05 = 50.00Hz; Max frequency

Connection Protocol:

  1. Potentiometer wiper → VI terminal
  2. Potentiometer V+ → +10V terminal
  3. Potentiometer V- → ACM terminal

Recommended: 10kΩ linear potentiometer

280-A

III. Fault Diagnosis Matrix

CodeDescriptionRoot CausesCorrective Actions
E-01Acceleration OCLoad surge/short acc.timeIncrease P0.17, inspect mechanics
E-02Deceleration OCRegenerative energyEnable P5.02 overvoltage stall
E-11DC Bus UnderVInput <305VVerify supply, set P5.07=1
E-12DC Bus OverVRapid decelerationAdjust braking parameters
E-15IGBT OverheatCooling failureClean vents, reduce loading

Troubleshooting Flow:

  1. Resolve hardware issues
  2. Press STOP/RESET to clear
  3. Analyze history (P6.00-P6.11)

IV. Advanced Application Techniques

1. Multi-Speed Programming

P4.00=1  # M11=Speed-bit1
P4.01=2  # M12=Speed-bit2
# Speed1: M11 ON
# Speed2: M12 ON
# Speed3: M11+M12 ON

2. Winding Control (Textile Applications)

P9.00=1      ; Enable wobble
P9.04=10.0%  ; Amplitude
P9.06=5.0s   ; Cycle time

3. PID Pressure Regulation

P7.00=1      ; Enable PID
P7.10=0.85   ; Proportional gain
P7.16=25.00  ; Preset frequency
JTE280

Key Operational Notes:

  1. High-altitude (>1000m) requires derating (Fig.1-3)
  2. Long cables (>30m) mandate output reactors (Sec.1.3.8)
  3. Braking resistors must comply with Table 3-25 specifications

This guide synthesizes critical operational knowledge from the 117-page manual. For complete technical specifications, refer to Chapter 9 (Application Examples) and Appendix (MODBUS protocols). Proper implementation of these procedures will optimize drive performance while ensuring operational safety.

Posted on

Toshiba VF-PS1 Inverter Stuck at “ELL0” with All LEDs Lit – Root Causes and Solutions

In the field of industrial automation, inverters play a crucial role in driving motors and optimizing energy efficiency. The Toshiba VF-PS1 series is known for its reliability and versatility across a wide range of applications such as manufacturing, HVAC systems, and water treatment. However, during a recent on-site startup, an unusual issue occurred: the inverter powered up and the screen continuously displayed “ELL0”, while all indicator LEDs on the operation panel (RUN, Hz, %, MODE, EASY, etc.) were fully lit and unresponsive. The device failed to transition to its normal frequency display or any operational mode.

ELL0

This article analyzes this abnormal behavior in depth, including its possible causes, technical diagnostics, and step-by-step troubleshooting solutions based on real-world experience. It aims to provide valuable insight for field engineers and maintenance professionals dealing with Toshiba VF-PS1 inverters.


1. Interpreting the “ELL0” Message

The first observation is that the code “ELL0” is not listed in the VF-PS1 manual’s error or alarm code tables. Most standard error codes for Toshiba inverters follow formats like E-xx (e.g., E-10 for analog input error, E-11 for sequence error) or Errx (e.g., Err4 for CPU fault).

Given this, “ELL0” is not a known error code but likely a simplified or stylized display of a word. Considering the limitations of seven-segment or basic LCD panels, the letter “H” may be rendered as “E”, resulting in the word “HELLO” being shown as “ELL0.”

In fact, several other Toshiba inverter series such as VF-S15 are documented to display “HELLO” during startup as a friendly greeting. While VF-PS1 manuals do not explicitly mention this, it is highly plausible that “ELL0” is simply the inverter saying “HELLO” at startup.

Conclusion: “ELL0” is not an error, but a startup message indicating the inverter is initializing.

However, this message is only meant to appear for a few seconds. If the inverter remains stuck on this screen for an extended time, and the display does not change to frequency output, “STOP,” or any other active status, then the system is failing to complete its initialization sequence.


2. Why Are All the LEDs Constantly Lit?

Electronic devices often illuminate all LEDs during the power-on self-test (POST) to confirm the panel is functional. The VF-PS1 has multiple LEDs on its keypad including RUN, Hz, %, MODE, and EASY.

In a normal power-up, these LEDs briefly flash and then only relevant indicators remain lit based on status:

  • In standby: only Hz and power indicators
  • In run mode: RUN LED is lit
  • During fault: alarm LED or fault code appears

⚠️ If all LEDs remain lit indefinitely, this suggests the system has not successfully exited the boot process. When combined with a stuck “ELL0” display, it is a clear sign the inverter is failing to transition to operational state.


VFAS1

3. Possible Technical Causes of the Fault

After analyzing the inverter’s architecture and behavior, the following are the most probable causes for this issue:

1. Main Control Board (CPU) Failure

The control board houses the CPU, EEPROM, and firmware that drive the entire system. If any of these components fail (e.g., due to static discharge, aging, memory corruption), the inverter may not proceed past startup, effectively freezing on the “HELLO” message.

2. Internal Control Power Supply Instability

Toshiba inverters typically generate low-voltage DC internally (e.g., 5V or 24V) to power logic and display. If these voltages are unstable due to aged capacitors or faulty switching circuits, the system may repeatedly attempt to initialize and fail each time.

3. Operator Panel Communication Failure

The panel communicates with the inverter’s main board through a connector or internal bus. If this link is disrupted—due to loose cables, damaged connectors, or panel PCB faults—the display might not receive valid data and remain stuck at its default state.

4. External Expansion Modules Interfering

If optional communication or I/O modules (e.g., Profibus, DeviceNet, or analog expansion) are connected and one of them malfunctions, it may prevent the system from passing its full self-test. This can effectively freeze the inverter before entering active status.

5. Corrupt Parameters or Firmware

Sudden power loss during write operations or faulty parameter resets may corrupt memory. If the inverter firmware or configuration table cannot initialize correctly, the inverter may hang during startup without even reporting an error.


4. Troubleshooting Steps and Solutions

The following field-tested steps may help restore the inverter to normal operation:

Step 1: Perform a Full Power Reset

  • Power off the inverter completely
  • Wait at least 15 minutes to allow internal capacitors to discharge
  • Re-energize and observe whether the display changes from “ELL0” to frequency display or run status

Step 2: Inspect the Panel Connection

  • If the keypad is external, check cable integrity and re-seat connections
  • If it’s an internal panel, check the physical contact to the main board
  • A faulty keypad may need replacement

Step 3: Remove Optional Modules

  • Disconnect any communication modules, expansion I/O boards, or external terminals
  • Reboot the inverter in minimal configuration
  • If the device initializes successfully, one of the peripherals is likely faulty

Step 4: Check Power Input and Control Voltage

  • Measure voltage at R/S/T terminals; confirm it’s within rated range and phase-balanced
  • If possible, measure internal low-voltage DC power (e.g., 5V or 24V) on the control board to ensure stability

Step 5: Attempt Parameter Initialization (if possible)

  • If the panel becomes responsive after reboot, consider resetting parameters to factory defaults
  • This may clear out any corrupt settings

Step 6: Consider Control Board Replacement

  • If none of the above steps restore operation, it’s likely the control board is faulty
  • Repair or replacement of the control PCB is required
  • Only qualified technicians should attempt internal board-level diagnostics

5. Preventive Measures

To avoid similar issues in the future:

  • Avoid frequent rapid power cycling, which can corrupt firmware or cause startup errors
  • Use surge protection and voltage stabilizers to ensure clean input power
  • Periodically inspect cooling fans and capacitors, which degrade over time
  • Only perform parameter resets under safe, powered-down conditions

6. Final Thoughts

While the appearance of “ELL0” on a Toshiba VF-PS1 inverter display might seem alarming at first, it is not inherently a fault code, but rather a welcome message (“HELLO”) that appears during power-up.

However, if the inverter remains stuck on “ELL0” and all panel LEDs stay on, it indicates a serious problem—typically that the inverter failed to complete its startup self-test. Common causes include CPU failure, unstable internal power, communication breakdown with the panel, or peripheral errors.

Technicians are advised to follow a structured troubleshooting process, starting with simple checks and escalating to control board diagnostics if necessary. If the issue persists and the inverter cannot be brought into operational state, professional service intervention or control board replacement is the likely solution.


Posted on

Detailed steps for configuring the MT500 frequency inverter to “display the actual rotational speed in RPM”:

Goal: make the MT 500 drive’s LED keypad show actual motor speed in r/min (RPM).
Assumptions: drive is stopped, control source = keypad.

1 . Enter the parameter list (“Standard menu”)

ActionExpected displayComment
Press ESC repeatedly from the normal monitor screen‑bSC‑“Basic / Standard menu” root 
Press ENTERP00.00You are now at the parameter index level

Tip: ESC moves up one level; ENTER confirms / goes down.


MT500

2 . Fill in the motor name‑plate data

(needed so the drive can translate Hz → RPM correctly)

2‑a  Locate P11.05 Rated frequency
  1. While P00.00 is shown:
    • Press SHIFT until the left‑most digit blinks.
    • Tap UP until that digit becomes 1 → display reads P10.00.
    • Press SHIFT once to move the cursor to the last digit; UP once → P11.00.
    • Tap UP five more times → P11.05.
  2. Press ENTER – the current value (e.g. 50.00) blinks.
2‑b  Edit the value
  • Use SHIFT to select the digit; UP / DOWN to change it.
  • Press ENTER to save. Display flashes End, then returns to P11.05
2‑c  Repeat for P11.06 Rated speed
  • Navigate to P11.06 the same way; enter the motor’s rated RPM; ENTER to save. 

3 . (Optional) Run auto‑tune P11.10

ActionDisplay
Go to P11.10, ENTERvalue blinks (default 0)
UP1 (stand‑still tune) or 2 (rotating tune)
ENTER to store → EndAuto‑tune will start the first time you press RUN afterwards 

4 . Switch the display unit from Hz to RPM — P21.17

ActionExpected display
Press ESC twice to get back to P00.00; jump to P21.17P21.17
ENTER – value blinks (0 = Hz)
UP once → 1 (= RPM)
ENTER to save → EndThe Hz and A LEDs now light together, meaning the keypad shows RPM 

5 . See the live speed

  1. Press ESC until the normal monitor screen returns.
  2. The default monitored variable is r27.00. Because P21.17 = 1, its value is already in RPM. 
  3. Press SHIFT (>>) to step through other view pages if needed; the Hz + A LEDs confirm the unit remains RPM.

mt500-7r5-t4b

6 . (Optional) Show only speed on the monitor page

If you dislike the rotating multi‑page display:

  1. Navigate to P21.11 (run‑mode sequence) and set it to 0001.
  2. Do the same for P21.12 (stop‑mode sequence) if desired.

Now the keypad will lock onto a single page that shows r27.00 in RPM.


Quick trouble‑shooting

SymptomLikely causeFix
Still shows HzP21.17 not saved, or you are viewing another variableRe‑enter 1; check Hz+A LEDs
RPM reading off by a lotWrong name‑plate data or no auto‑tuneRe‑check P11.05 / P11.06, run P11.10
Cannot enter parametersUser lock activeEnter password in P00.00 or restore defaults

Ultra‑short recap

  1. ESC‑bSC‑ENTER → parameter list.
  2. Set P11.05 (rated Hz) & P11.06 (rated rpm).
  3. (Option) P11.10 = 1 or 2, auto‑tune after RUN.
  4. P21.17 = 1 → units = RPM.
  5. Monitor page now shows real speed; enjoy!
Posted on

User Guide to the SZOR Shenzhen Delta Inverter TD9000 Series Manual

The TD9000 series inverter, developed by SZOR Shenzhen Delta, is a high-performance, highly stable general-purpose drive. It is widely used in applications such as fans, pumps, conveyors, and machine tools. This article introduces the key functions of the TD9000 inverter, including the control panel, password settings, parameter restrictions, parameter initialization, terminal control wiring, potentiometer speed adjustment, and fault diagnostics. It aims to help users operate and maintain the TD9000 series more efficiently and safely.


SZOR INVERTER

1. Control Panel Functions

The TD9000 inverter features an LED digital display and keypad panel. Key functions include:

  • RUN: Starts the inverter.
  • STOP/RESET: Stops operation or resets a fault.
  • PROG: Enters or exits the parameter menu.
  • DATA/ENTER: Confirms parameter modifications.
  • ▲/▼: Scrolls through parameters or adjusts values.

The panel displays parameter codes, output frequency, current, voltage, and other running data. It also supports copy functions to clone parameters from one drive to another, making batch configuration fast and convenient.


2. Password Setup and Parameter Access Restrictions

To prevent unauthorized changes, the TD9000 offers password protection and access-level control.

1. Set Password

  • Parameter P00.08:
    • Set to 0000: No password protection.
    • Set to a 4-digit code (e.g., 1234): Enables password protection.

2. Remove Password

  • If the password is forgotten, hold down special key combinations (e.g., PROG + STOP) during power-up or access maintenance mode to reset it (should be done by qualified personnel).

3. Parameter Access Restriction

  • P00.07: Limits access to basic parameter groups only.
  • P00.12 = 1: Activates user-access mode to restrict changes to key parameters.

3. Restoring Factory Settings

To initialize all parameters:

  • Set P00.13 = 1 to restore factory defaults. The inverter will reboot automatically. Use with caution, as all settings will be erased.

4. Terminal Forward/Reverse Control & External Potentiometer Speed Adjustment

The TD9000 supports terminal-based control and analog input via external potentiometers.

1. Forward/Reverse Terminal Wiring

  • Terminals:
    • S1: Forward run command (default).
    • S2: Reverse run command (customizable).
    • COM: Common ground.
  • Parameter Settings:
    • F00.06 = 2 (terminal control mode).
    • F10.00 = 1 (S1 = Forward).
    • F10.01 = 2 (S2 = Reverse).

Closing the respective terminal switch triggers forward or reverse operation.

2. Potentiometer Speed Control Wiring

  • Wiring:
    • 10V: Power supply to potentiometer.
    • AI1: Signal input from potentiometer center tap.
    • GND: Ground.
  • Parameters:
    • F00.05 = 1 (set AI1 as frequency reference).
    • Fine-tuning via F11.00 ~ F11.02.

Adjusting the potentiometer varies the output frequency for smooth speed control.


TD9000

5. Fault Codes and Troubleshooting

TD9000 has advanced fault diagnostics. Faults are displayed as “ErrXX” codes on the panel.

CodeMeaningCausesSolution
Err01OvercurrentShort circuit, too short accel timeCheck wiring, increase accel time
Err02OvervoltageGrid surge, braking circuit issuesInstall brake resistor, adjust voltage
Err04OverloadHeavy load, frequent starts/stopsReduce load, optimize control sequence
Err05OverheatFan failure, high ambient tempClean fan, improve ventilation
Err08Communication errorPoor RS485 wiring or parameter mismatchCheck communication settings and wiring
Err09Input phase lossMissing phase, grid imbalanceCheck power input and phase integrity
Err10Output phase lossBroken cable or terminal looseInspect output wiring and motor leads

Press STOP/RESET or cycle power to clear most transient faults. If faults persist, consult service engineers.


6. Conclusion and Best Practices

The TD9000 inverter series is versatile and user-friendly. Key suggestions for optimal use:

  • Backup parameters regularly.
  • Assign user-level passwords.
  • Ensure proper cooling and dust-free environment.
  • Follow all safety and wiring instructions in the manual.

By following this guide, users can effectively configure and troubleshoot the TD9000 inverter series for reliable industrial performance.


Posted on

User Guide for the JLS Inverter E Series Manual

Introduction

The JLS Inverter E Series is a high-performance motor control device widely used in industrial automation. Its user manual provides comprehensive guidance on installation, configuration, and maintenance, enabling users to operate the inverter efficiently. This article, based on the manual, offers a detailed guide on the operation panel functions, terminal-based forward/reverse control, external potentiometer frequency adjustment, and common fault codes with their solutions. The goal is to provide users with a practical and thorough reference for utilizing the JLS Inverter E Series effectively.


Functional Diagram of the Operation Panel for Julishen (or Julishen Brand) E-series Frequency Inverter

1. Operation Panel Functions

The operation panel is the primary interface for interacting with the JLS Inverter E Series, allowing users to configure parameters, monitor operations, and diagnose faults. Below is an overview of its key functions and usage instructions.

1.1 Display and Function Buttons

  • Display Screen: The LCD screen displays real-time information such as parameter values, operating frequency, output current, and fault codes. It supports multiple language options for user convenience.
  • Function Buttons:
    • PRG/ENTER Key: Enters parameter programming mode or confirms parameter changes.
    • Up/Down Keys (▲/▼): Navigate through parameter lists or adjust parameter values.
    • Left/Right Keys (◄/►): Switch between parameter groups or move the cursor during parameter editing.
    • RUN Key: Starts the inverter, initiating motor operation.
    • STOP/RESET Key: Stops the inverter or resets it during a fault condition.
  • DIP Switch: Located inside the operation panel, used to set parameter access restrictions.

1.2 Restoring Factory Settings

To reset the inverter to its default configuration, follow these steps to restore factory settings:

  1. Press the PRG/ENTER Key to enter programming mode.
  2. Use the ▲/▼ Keys to select the parameter group “F0” (Basic Function Group).
  3. Use the ◄/► Keys to locate parameter “F0.00” (Restore Factory Settings).
  4. Set “F0.00” to “1” (indicating a factory reset).
  5. Press the PRG/ENTER Key to confirm.
  6. The inverter will restart automatically, restoring all parameters to their factory defaults.

1.3 Setting and Clearing Passwords

To prevent unauthorized parameter modifications, the inverter supports password protection. Below are the steps to set and clear a password:

  • Setting a Password:
    1. Enter programming mode by pressing the PRG/ENTER Key.
    2. Select the “F0” parameter group.
    3. Navigate to parameter “F0.01” (Password Setting).
    4. Enter a 4-digit password (e.g., “1234”).
    5. Press the PRG/ENTER Key to save the password.
  • Clearing a Password:
    1. Enter programming mode.
    2. Input the current password to unlock parameter access.
    3. Navigate to parameter “F0.01”.
    4. Set “F0.01” to “0” (to disable the password).
    5. Press the PRG/ENTER Key to confirm.

1.4 Parameter Access Restrictions

Parameter access can be restricted using the DIP switch inside the operation panel. Follow these steps:

  1. Open the operation panel to access the internal DIP switch.
  2. Set the switch position based on the desired access level:
    • Position 1 (ON): Allows access to all parameters.
    • Position 2 (OFF): Restricts access to advanced parameters, allowing only basic parameters to be modified.
  3. Close the panel and restart the inverter to apply the settings.

Standard Wiring Diagram for Julishen E-series Frequency Inverter

2. Terminal-Based Forward/Reverse Control and External Potentiometer Frequency Adjustment

The JLS Inverter E Series supports motor forward/reverse control via terminals and frequency adjustment using an external potentiometer. Below are the detailed steps for implementation.

2.1 Wiring Configuration

  • Forward/Reverse Control:
    • Connect an external switch or PLC output to the inverter’s “FWD” (forward) and “REV” (reverse) terminals.
    • Connect the control signal’s common terminal to the “COM” terminal.
  • External Potentiometer Frequency Adjustment:
    • Connect the potentiometer’s middle tap to the “AI1” terminal (Analog Input 1).
    • Connect the potentiometer’s two ends to the “+10V” (power supply) and “GND” (ground) terminals.

2.2 Parameter Settings

  • Forward/Reverse Control:
    1. Enter programming mode.
    2. Select parameter group “F1” (Operation Control Group).
    3. Set “F1.00” (Operation Command Source) to “1” (Terminal Control).
    4. Set “F1.01” (Forward Control) to “0” (FWD terminal controls forward rotation).
    5. Set “F1.02” (Reverse Control) to “1” (REV terminal controls reverse rotation).
  • External Potentiometer Frequency Adjustment:
    1. Enter programming mode.
    2. Select parameter group “F2” (Frequency Setting Group).
    3. Set “F2.00” (Frequency Reference Source) to “2” (AI1 Analog Input).
    4. Based on the potentiometer’s characteristics, configure parameters “F2.01” (AI1 Minimum Input) to “F2.04” (AI1 Maximum Input) to calibrate the frequency range.
      • Example: Set “F2.01” to 0V corresponding to 0Hz and “F2.04” to 10V corresponding to 50Hz.

3. Fault Codes and Troubleshooting

The JLS Inverter E Series manual lists common fault codes and their troubleshooting methods. Below are typical faults and their solutions:

  • E001: Overcurrent Fault
    • Cause: Excessive motor load, overly short acceleration time, or output short circuit.
    • Solution:
      • Check and reduce motor load.
      • Extend acceleration time (adjust parameter “F3.01”).
      • Inspect output wiring to ensure no short circuits.
  • E002: Overvoltage Fault
    • Cause: High supply voltage, overly short deceleration time, or faulty braking resistor.
    • Solution:
      • Verify power supply voltage stability.
      • Extend deceleration time (adjust parameter “F3.02”).
      • Check the braking resistor for damage or poor connection.
  • E003: Undervoltage Fault
    • Cause: Low supply voltage or poor wiring connections.
    • Solution:
      • Ensure the power supply voltage is within the specified range.
      • Check wiring connections for secure contacts.
  • E004: Overheat Fault
    • Cause: Poor heat dissipation, high ambient temperature, or faulty fan.
    • Solution:
      • Improve ventilation to enhance heat dissipation.
      • Reduce ambient temperature.
      • Inspect fan operation and replace if necessary.
  • E005: Motor Overload
    • Cause: Excessive load or incorrect motor parameter settings.
    • Solution:
      • Reduce motor load.
      • Verify that motor parameters match the actual motor specifications.

Conclusion

The JLS Inverter E Series is a versatile and robust solution for industrial motor control, offering flexible configuration options and reliable performance. Mastering the user manual’s instructions is critical for ensuring stable operation and extending the equipment’s lifespan. This article has provided a comprehensive guide to the operation panel functions, terminal control setup, and fault troubleshooting, serving as a practical reference for users. In practice, adhere strictly to the manual’s guidelines and perform regular maintenance to ensure the inverter’s safety and reliability.

Posted on

User Guide for the Yuxin L Series Inverter Manual

Introduction

A Variable Frequency Drive (VFD) is an electronic device that controls the speed of an AC motor by adjusting the power supply’s frequency and voltage. It is widely used in industrial automation, energy management, and mechanical equipment control. The Yuxin L Series Inverter is a high-performance product known for its reliability and user-friendliness. This guide provides detailed instructions on using the inverter, covering the operation panel functions, terminal-based forward/reverse control, external potentiometer frequency adjustment, fault codes, and troubleshooting methods. The aim is to help users quickly master the device and utilize it effectively.


Structural Schematic Diagram of Yuxin L-series Frequency Inverter

Part 1: Operation Panel Functions

The operation panel is the primary interface for interacting with the Yuxin L Series Inverter, enabling parameter configuration, status monitoring, and fault resetting. This section details the panel’s functionalities and specific settings.

1.1 Panel Layout and Button Functions

The Yuxin L Series Inverter’s operation panel typically features an LCD display and several function buttons. The display shows operational status, parameter numbers, parameter values, and fault codes. Common buttons and their functions include:

  • MENU/ESC: Enter or exit the parameter setting menu.
  • UP/DOWN: Navigate the menu or adjust parameter values.
  • ENTER: Confirm selections or save parameter settings.
  • RUN: Start the inverter’s operation.
  • STOP/RESET: Stop the inverter or reset a fault condition.

Users are advised to familiarize themselves with the panel layout and refer to the manual’s panel diagram to ensure accurate operation.

1.2 Restoring Factory Settings

In cases such as incorrect parameter configurations or the need for reinitialization, restoring the inverter to factory settings may be necessary. Follow these steps:

  1. Press the MENU/ESC button to access the main menu.
  2. Use the UP/DOWN buttons to locate the “Parameter Management” or similar option (refer to the manual for the exact name).
  3. Press ENTER to enter the submenu.
  4. Select the “Restore Factory Settings” option.
  5. Press ENTER to confirm. The inverter will reset all parameters to their default values.
  6. Wait for the display to indicate completion, typically taking a few seconds.

Note: Restoring factory settings will erase all custom parameters. Back up important data beforehand.

1.3 Setting and Clearing a Password

To prevent unauthorized parameter changes, the Yuxin L Series Inverter supports password protection. Below are the steps to set and clear a password:

Setting a Password

  1. Navigate to the “Parameter Management” menu.
  2. Locate the “Password Setting” option.
  3. Press ENTER and input a 4-digit password (e.g., “1234”).
  4. Press ENTER to save. The password will take effect.
  5. The next time you access parameter settings, the password will be required.

Clearing a Password

  1. Enter the “Password Setting” menu.
  2. Input the current password for verification.
  3. Set the password value to “0000” or leave it blank (check the manual for specifics).
  4. Press ENTER to save, and the password will be cleared.

Tip: If you forget the password, restoring factory settings may be required, but this will also reset other parameters.

1.4 Parameter Access Restrictions

Parameter access restrictions allow locking specific parameters to prevent accidental or unauthorized modifications. The process is as follows:

  1. Access the “Parameter Management” menu.
  2. Select the “Parameter Lock” or similar option.
  3. Specify the parameter group to lock (e.g., advanced parameters or specific function parameters).
  4. Set the lock status (typically “1” for locked, “0” for unlocked).
  5. Press ENTER to save.
  6. If a password is set, it will be required to modify locked parameters.

This feature allows flexible control over parameter accessibility, ensuring safe operation.


Standard Wiring Diagram for Yuxin L-series Frequency Inverter

Part 2: Terminal-Based Forward/Reverse Control and External Potentiometer Frequency Adjustment

The Yuxin L Series Inverter supports terminal-based control and frequency adjustment, enabling precise motor control. This section explains how to implement forward/reverse control and frequency adjustment using an external potentiometer, including wiring and parameter settings.

2.1 Terminal-Based Forward/Reverse Control

Terminal-based forward/reverse control is a common method for applications requiring external switches or PLC control.

Wiring Method

  • Connect the forward switch to the digital input terminal DI1 and the common terminal COM.
  • Connect the reverse switch to the digital input terminal DI2 and the common terminal COM.
  • Ensure secure connections and refer to the manual’s terminal layout diagram to confirm terminal positions.

Parameter Settings

  1. Set parameter P0.01 (Control Mode) to “1” to select terminal control mode.
  2. Set parameter P4.00 (DI1 Function) to “1” to designate DI1 as the forward run command.
  3. Set parameter P4.01 (DI2 Function) to “2” to designate DI2 as the reverse run command.
  4. Save the settings. Closing the DI1 switch initiates forward rotation, and closing the DI2 switch initiates reverse rotation.

Note: Parameter numbers may vary by model. Refer to the manual’s parameter table for accuracy.

2.2 External Potentiometer Frequency Adjustment

Using an external potentiometer for frequency adjustment allows smooth speed control, ideal for applications requiring manual adjustments.

Wiring Method

  • Connect the potentiometer’s center tap to the analog input terminal AI1.
  • Connect one end of the potentiometer to the +10V terminal (provides reference voltage).
  • Connect the other end to the GND terminal (ground).
  • Use an appropriate potentiometer (typically 10kΩ) and ensure correct wiring.

Parameter Settings

  1. Set parameter P0.03 (Frequency Reference Source) to “2” to select analog input AI1 for frequency setting.
  2. Verify parameter P4.10 (AI1 Input Range) matches the potentiometer’s voltage range (typically 0-10V).
  3. Save the settings. Rotating the potentiometer adjusts the output frequency.

Tip: If the frequency adjustment range is not as expected, adjust related parameters (e.g., maximum frequency P0.11).


Part 3: Fault Codes and Troubleshooting

During operation, the inverter may encounter faults, displayed as fault codes on the screen. This section lists common fault codes and their solutions, but refer to the manual’s fault list for specific codes.

3.1 Common Fault Codes and Solutions

  • E001: Overcurrent
    • Possible Causes: Excessive motor load, short acceleration time, or incorrect motor wiring.
    • Solutions:
      1. Check motor wiring for short circuits or poor connections.
      2. Reduce the load or increase the acceleration time (parameter P0.12).
      3. Restart the inverter to check if the issue resolves.
  • E002: Overvoltage
    • Possible Causes: High input voltage, short deceleration time, or braking unit failure.
    • Solutions:
      1. Verify the power supply voltage is within the specified range.
      2. Extend the deceleration time (parameter P0.13).
      3. If frequent, check the braking resistor for proper function.
  • E003: Undervoltage
    • Possible Causes: Low power supply voltage or unstable power.
    • Solutions:
      1. Ensure the input power voltage is stable.
      2. For multiple devices, confirm adequate power supply capacity.
  • E004: Motor Overload
    • Possible Causes: Excessive load or incorrect motor parameter settings.
    • Solutions:
      1. Reduce the load or select a motor with higher power capacity.
      2. Verify motor parameters (P1 group) match the actual motor.
  • E005: Inverter Overheating
    • Possible Causes: High ambient temperature or blocked/faulty cooling fan.
    • Solutions:
      1. Improve ventilation and reduce ambient temperature.
      2. Clean the fan and heatsink to ensure proper cooling.

3.2 General Troubleshooting Steps

  1. Record the fault code and consult the manual for its specific meaning.
  2. Inspect wiring, power supply, and load conditions to rule out external issues.
  3. Press STOP/RESET to attempt a reset. If unsuccessful, power cycle the inverter.
  4. If the issue persists, contact technical support with detailed fault information.

Conclusion

The Yuxin L Series Inverter offers robust functionality and flexible configuration, making it an excellent choice for motor control applications. This guide has detailed the operation panel’s usage, terminal-based control and frequency adjustment methods, and fault troubleshooting procedures. Due to model variations and application complexity, users should always refer to the official Yuxin L Series Inverter Manual for precise details. By mastering these foundational skills, you can fully leverage the inverter’s capabilities, enhance equipment efficiency, and address potential issues promptly.

Posted on

Analysis and Solutions for ERR04 Fault (Constant Speed Overcurrent) of Ruishen RCP600 Series Inverter

I. Fault Phenomenon and Definition

ERR04 is a common fault code for the Ruishen RCP600 series inverter during operation, indicating a constant speed overcurrent issue. This fault is triggered when the inverter detects that the output current continuously exceeds 150% to 200% of the rated value during the constant speed stage (non-acceleration/deceleration process). The fault phenomena include:

  • Display of “ERR04” or “Constant Speed Overcurrent” alarm on the inverter panel.
  • Equipment shutdown protection, possibly accompanied by abnormal noise or motor overheating.
  • The fault can be reset for brief operation but tends to recur.

This fault directly affects the continuous operation capability of the equipment and requires systematic troubleshooting from three aspects: electrical parameters, mechanical load, and hardware status.

E004

II. Fault Cause Analysis and Diagnostic Process

1. Classification of Core Causes

CategorySpecific Causes
Parameter SettingsMismatch of motor parameters (e.g., rated current, number of poles), over-aggressive PID tuning, excessive torque compensation
Load AnomaliesMechanical jamming, sudden load changes (e.g., drive mechanism failure), increased resistance due to motor bearing damage
Electrical FaultsOutput side short circuit/ground fault, cable insulation aging, current detection circuit anomalies (e.g., Hall sensor drift or damage)
Cooling IssuesPoor heat dissipation leading to degraded IGBT module performance and reduced carrier capability

2. Scientific Diagnostic Process

Step 1 – On-site Observation and Data Recording

  • Record the operating frequency, current value, and DC bus voltage (readable via the panel’s U0 parameter group) at the time of fault occurrence.
  • Check for abnormal noises, temperature rise, or visible mechanical damage in the motor and mechanical load.

Step 2 – Distinguishing Between Load-Side and Electrical-Side Faults

  • Disconnect the motor load and run the inverter under no load: If ERR04 disappears, the issue is on the load side; if it persists, check electrical parameters and hardware.
  • Use a megohmmeter to test the motor winding insulation to ground (requirement: ≥5MΩ) to rule out ground faults.

Step 3 – Parameter Verification and Waveform Analysis

  • Verify the motor nameplate parameters and check if the P0 group (basic parameters) and A2 group (motor parameters) settings match the actual motor.
  • Observe the output current waveform for distortions (e.g., excessive harmonics) using an oscilloscope or the inverter’s built-in waveform recording function.
RCP600

III. Targeted Solutions

1. Parameter Optimization and Adjustment

  • Motor Self-Learning: Perform the inverter’s “Motor Parameter Auto-Tuning” (refer to the PA group function in the manual) to ensure stator resistance and inductance values match the actual motor.
  • Reduce Torque Compensation: Adjust the P2-21 parameter (constant speed torque compensation coefficient) and gradually reduce it to 80% to 100% for testing.
  • PID Parameter Reset: If PID control is applied, reset the PA-03 (proportional gain) and PA-04 (integral time) to their default values to avoid over-tuning.

2. Load-Side Fault Handling

  • Mechanical System Inspection: Check coupling alignment, bearing lubrication, and belt tension to eliminate jamming points.
  • Load Matching Verification: Ensure the motor power matches the mechanical load to avoid long-term overload operation. For example, a 22kW motor driving a 30kW load requires an upgraded inverter and motor combination.

3. Electrical Hardware Maintenance

  • Output Side Insulation Test: Use a 500V megohmmeter to measure the U/V/W terminal insulation to ground. If <5MΩ, replace the motor cable or repair the winding.
  • Current Detection Calibration:
    • Check for loose Hall sensor connections.
    • Recalibrate the current detection accuracy using the AC-20 to AC-27 parameters (analog calibration parameters), with a tolerance deviation within ±2%.
  • Cooling System Maintenance: Clean the air duct dust, test the cooling fan operation (set temperature threshold via P8-47), and replace aged fans if necessary.

4. Advanced Debugging Techniques

  • Carrier Frequency Adjustment: Reduce the carrier frequency in the A5-01 parameter (PWM modulation method) (e.g., from 12kHz to 8kHz) to reduce switching losses and temperature rise.
  • Overcurrent Stall Suppression: Enable the P3-19 (overcurrent stall control) and P3-20 (suppression intensity) parameters, setting the action current to 130% to 150% of the rated value.

IV. Preventive Maintenance Recommendations

  1. Regular Parameter Backup: Utilize the inverter’s “User Parameter Backup” function (P7 group) to save optimized parameters and prevent失调due to accidental resets.
  2. Hardware Inspection Regimen:
    • Quarterly inspection of output terminal tightness to prevent increased contact resistance.
    • Annual thermal imaging scan of IGBT modules and rectifier bridges to address abnormal temperature rise points.
  3. Load Monitoring: Install mechanical vibration sensors and current trend recorders for early fault warnings.

V. Maintenance Case Reference

Case Background: An RCP600-22kW inverter for an injection molding machine frequently reported ERR04, operating normally under no load but triggering the fault after 10 minutes under load.

Troubleshooting Process:

  • No-load current was 12A (normal), but under load, it rose to 48A (rated current 42A).
  • Motor insulation test was normal, but disassembly revealed rusted and jammed reducer bearings.
  • After replacing the bearings and adjusting the P2-21 parameter (torque compensation) from 150% to 110%, the fault was resolved.

VI. Summary

Resolving the ERR04 fault requires a three-tiered troubleshooting approach focusing on “parameters, load, and hardware,” combined with real-time data and equipment status analysis. The key is to distinguish between transient overcurrent and sustained overload, avoiding unnecessary component replacements. Through scientific debugging processes and preventive maintenance, the stability of the inverter system can be significantly improved, reducing the risk of unplanned downtime.

Posted on

AUT-DRIVE DV6000 VFD (Variable Frequency Drive) User Guide and E-03 Fault Solution


I. Operation Panel Functions and Basic Settings

1. Operation Panel Function Introduction

  • Key Functions:
    • RUN Key: Starts the VFD operation; requires configuration of the operation command channel.
    • STOP/RESET Key: Stops the device during operation or resets alarms during fault states.
    • PRG Key: Enters the parameter editing menu, supporting three-level menu navigation (Function Group → Function Code → Parameter Value).
    • Direction Keys (▲/▼): Switches between displayed parameters or adjusts values, supporting cyclic selection and bit modification.
    • FUN Key: Can be customized for jog operation or forward/reverse switching (configured via F7.03).
  • Display Area:
    • 5-Digit LED Display: Shows operating frequency, fault codes, parameter values, etc.
    • Status Indicators: Include operating status (RUN/TUNE), forward/reverse (FWD/REV), local/remote control (LOCAL/REMOTE), and fault (TRIP) indicators.

2. Restoring Factory Default Settings

  • Steps:
    1. Navigate to Function Group F0 → Select F0.13 (Function Parameter Restore).
    2. Set to 1 (Restore Factory Defaults) → Press the confirmation key (ENT) to save.
  • Note: After restoration, key parameters (e.g., motor nameplate data, control mode) must be reconfigured.

3. Password Setup and Access Restrictions

  • Setting Password: Input a 4-digit number (range 0~65535) via F7.00 (User Password); non-zero values take effect.
  • Removing Password: Set F7.00 to 0 or restore factory defaults.
  • Parameter Access Restrictions:
    • A valid password is required to enter editing mode (display “PASS” before input).
    • Some parameters (marked with “-“) are manufacturer-specific and cannot be modified by users.

E-03

II. External Terminal Control and Speed Adjustment Settings

1. External Terminal Forward/Reverse Control

  • Terminal Connections:
    • Forward Terminal: X1 (default function code F5.04=1).
    • Reverse Terminal: X2 (default function code F5.05=2).
    • Common Terminal: COM.
  • Parameter Settings:
    1. Set F0.01 (Operation Command Channel) to 1 (Terminal Command Channel).
    2. Configure F5.07 (Terminal Control Mode):
      • 0 (Two-Wire Control): X1 for forward, X2 for reverse; both closed stops the drive.
      • 1 (Three-Wire Control): Requires an additional terminal as an enable signal (e.g., configure X3 as “Three-Wire Operation Control”).

2. External Potentiometer Speed Adjustment

  • Terminal Connections:
    • Potentiometer Signal Input: VS1 (0~10V) or VS2 (0~10V/4~20mA, selected via jumper).
    • Signal Ground: GND.
  • Parameter Settings:
    1. Set F0.03 (Frequency Command Selection) to 2 (Analog VS1) or 3 (Analog VS2).
    2. Calibrate Input Range (Optional): Adjust F5.09~F5.12 (VS1 Upper/Lower Limit Corresponding Values) to ensure 0~10V corresponds to 0%~100% frequency.
    3. For current signals (4~20mA), switch VS2 jumper to current mode (JP2 position).

III. E-03 Fault Analysis and Solution

1. Fault Definition and Symptoms

  • E-03 Fault: Overcurrent during constant-speed operation, triggering protective shutdown. The LED display shows “E-03” and flashes.

2. Possible Causes

  • Load Sudden Change: Mechanical jamming, abnormal drive system (e.g., gear damage).
  • Power Supply Abnormality: Input voltage fluctuations or instantaneous drops.
  • Improper Parameter Configuration: Motor parameters (Group F2) do not match actual values, or carrier frequency (F0.11) is set too high.
  • Hardware Issues: Abnormal current detection circuit, aged IGBT module.

3. Solution Steps

  • Step 1: Check Load and Mechanical System
    • Disconnect the motor from the load and test under no-load conditions to check if the fault persists.
    • Inspect couplings and bearings for jamming; eliminate mechanical abnormalities.
  • Step 2: Optimize Parameter Configuration
    • Adjust F0.11 (Carrier Frequency): Reduce the carrier frequency (e.g., from 8kHz to 4kHz) to reduce switching losses.
    • Calibrate Group F2 (Motor Parameters): Perform motor self-learning (F0.12=1 or 2) to ensure accurate stator resistance and inductance values.
  • Step 3: Check Power Supply and Hardware
    • Measure three-phase input voltage to ensure balance deviation <15%.
    • Detect DC bus voltage; if abnormal fluctuations occur, install an input reactor.
    • Troubleshoot current sensor (Hall element) or drive circuit faults; replace modules if necessary.

4. Preventive Measures

  • Regularly clean the cooling fan to ensure the inverter module temperature (F7.09) <85°C.
  • Enable F8.07 (Automatic Current Limiting Function) and set the current limiting level (F8.07=150%) to suppress sudden overcurrents.

DV6000

IV. Conclusion

The AUT-DRIVE DV6000 VFD offers flexible parameter configuration and terminal control functions to meet complex industrial requirements. Operators must strictly follow the manual instructions, perform regular maintenance, and record operational data. For E-03 faults, systematically troubleshoot load, power supply, parameter, and hardware issues, combined with function code adjustments and mechanical maintenance, to ensure stable device operation. Password protection and parameter access restrictions further enhance equipment management security.